ID3000/ID2000 Fire Panel Configuration Tool Manual
T
ime-of-day Program
5 - 2
997-291, Version 3.05
November 2010
5.2
Manual Override
If manual override is configured for the TOD
program, the action of the program can be
reversed by the operator at the panel.
Special Case
If identical non-zero start and end times are
set and manual override is configured and is
then operated, the TOD program becomes
active. Associated Control Matrix actions are
then suppressed until the time next reaches
the start/end time, on the same day or the next
day. (If manual override is not configured, the
TOD program remains permanently disabled.)
Disablement/Enablement Override
Manual override can be used to enable a one-
shot advance on the next programmed change-
over time for disablement/enablement. For
example, if a zone is disabled using TOD from
21:00 to 19:30 and manual override is operated
at 20:00, the zone will be enabled and not be
disabled again until the following day at 19:30.
To avoid confusion,
configure the Manual
Override option for only
one time-of-day program.