32

Connect Ethernet cable 

Ethernet cable can be with Power over Ethernet. The Enclosure 

has been designed to lead the Ethernet cable as smooth as pos

-

sible and to lead away from the tamper switch.

Summary of Contents for MPA1C1

Page 1: ...MPA1C1 Access Control Unit Installation Guide For MPA1C1 Controller and MPA1ENCP Plastic Enclosure Document 800 26169 09 2020 Rev E ...

Page 2: ... without prior notice Ordering Information Please contact your local Honeywell representative or visit us on the web at www honeywellaccess com for information about ordering Feedback Honeywell appreciates your comments about this manual Please visit us on the web at www honeywellaccess com to post your comments Digital Manuals and manuals in other languages Honeywell provides this manual in Engli...

Page 3: ...ll App beginning on page 13 Mounting and Installing Options beginning on page 14 MPA1ENCP Plastic Enclosure Installation beginning on page 15 Commission the MPA1C1 beginning on page 33 Hardware Specifications beginning on page 39 Maintenance beginning on page 44 Troubleshooting beginning on page 45 Technical Support beginning on page 49 ...

Page 4: ...3 Introduction This document describes how to install the MPA1C1 access control unit ...

Page 5: ...d the system then either grants or denies access to specific areas and resources Administration includes the creation and modification of user accounts and access privileges An access control system consists of hardware and software usually configured in a network environment over a standard network protocol Access control units readers door strikes and video and other devices for example are conf...

Page 6: ... intended for monitoring and programming use only MPC and WIN PAK software are intended for monitoring and programming use only and have not been evaluated by UL Panel Components and Descriptions Note This device complies with part 15 of the FCC Rules Operation is subject to the following two conditions 1 This device may not cause harmful interference and 2 this device must accept any interference...

Page 7: ...locks are rated for 12 26 AWG wiring UL Listed and suitably rated ferrule connectors have to be used in case of braid copper wires or in case of two wires connected to one screw terminal The cross section of the ferrule connectors and the wire gauges have to match To fix the ferrule connectors please use a proper crimping tool Canadian Electrical Code part 1 Local Authority Having Jurisdiction ...

Page 8: ...7 MPA1C1 door with single reader and door strike MPA1C1 door with two readers and door strike ...

Page 9: ...ision Normal Alarm Short and Cut One input is used for door status on each door There is one tamper input in the MPA1C1 All three inputs can also be used as additional inputs when not required for their default purpose By default non supervised inputs are used for Request to Exit REX button Door Position Switch DrCnt and Tamper T LID Note The MPA1C1 can only connect to OSDP readers For MPA1C1 read...

Page 10: ... pri mary power Ensure the battery coin cell has been placed in the battery holder when MPA1C1 is commissioned and when in normal operation Replace the battery only with CR1220 Coin Cell type Using another type of battery may result in a risk of Fire Or Explosion Refer the Owner s Manual for Safety Instructions Caution Risk of Fire Explosion And Burns Do Not Recharge Disassemble Heat Above 100 C o...

Page 11: ... of total current for the 12VDC external power to eg read ers and locks See Hardware Specifications beginning on page 39 for further details on current limits using PoE Use of PoE and compliance with safety regulations PoE can be connected if the Ethernet cable is installed only inside the building If the connected Ethernet cableis partly installed outside the building then the MPA1C1 must be powe...

Page 12: ...e connected to the power source Recommended backup power source For ULC60839 11 1 and UL294 and CAN ULC60839 11 1 Complaint systems DC Power shall be provided through a UL ULC listed access control or burglar alarm power supply with class 2 limited output The 7Ah lead acid battery in the external power supply is not evaluated by UL294 and CAN ULC60839 11 1 The battery or UPS provides standby backu...

Page 13: ...as a reset button While MPA1C1 is powered up and RUN LED is blinking press the reset button for 20 seconds to reset to factory default configurations and activate the Blue tooth communication for the commissioning application ...

Page 14: ...ownload the application from the App Store or Play Store Scan this QR code for the application in the App Store Get Device Utility App Here Scan this QR code for the application in the Play Store Get Device Utility App Here Minimal required Mobile Operating System iPhone iOS 13 or higher Android Android 6 or higher ...

Page 15: ...rain relief and use the provided zip tie for additional CAT5 Cable strain relief Push the MPA1C1 into the junction box with LEDs visible MPA1C1 in a single gang US electrical gang box Place the light blocking label on the back of the single gang cover plate Attach any provided cover plate For compliance with UL294 and CAN ULC60839 11 1 the MPA1C1 is intended to be installed within the secure prote...

Page 16: ...lastic enclosure with tamper is available as MPA1ENCP The MPA1C1 Controller slides and snaps into the enclosure inner base without using any tools Make sure that the RJ45 Connector is on the outer left side The below figures show how to insert the MPA1C1 controller in the MPA1ENCP inner base ...

Page 17: ...16 Note The MPA1C1 Controller has been installed already in the MPA1ENCP enclosure ...

Page 18: ...e tamper switch The Lid tamper switch wires connect with the T Lid inputs as demonstrated below Note There is an additional internal accelerometer tamper switch that will detect any movement from the wall or from a gang box ...

Page 19: ...rings The design of the base is so that the wiring can be lead neatly in the cabinet using the openings at the edges of the inner base The cables can be tied down the using the cable ties at the cable tie points ...

Page 20: ...19 Break out tabs in the cover Cables can be lead in the side of the cover when breaking out the break out tabs per picture below ...

Page 21: ...crews not included in the accessory bag Make sure the secure fixing is suitable for the material of the wall Note the location of the fixing holes Install the cables and close the cover aligning the top side first and snap in the bottom part Fix the lid screw as indicated in the drawing below ...

Page 22: ...Inner Base The inner part inner base of the base can be snapped out of the outer part Turn the base facing the full base from the back side Push the indicated plastic clips out Move the inner base towards you ...

Page 23: ...22 Take out the inner base and turn it facing the labels toward you and snap in the MPA1C1 panel ...

Page 24: ...23 The inner base with MPA1C1 can now be mounted on other devices or in a metal cabinet using 2 or 4 short cabinet mount ing screw supplied in the accessory bag ...

Page 25: ... a MPA2 controller a MAXPRO intrusion smart power supply or on the bottom of the metal enclosure The inner base can also be mounted on a DIN Rail using DIN Rail adapters Note Above mounting option is not evaluated by UL294 and CAN ULC60839 11 1 ...

Page 26: ...r drawn is 500mA for the readers The maximum recommended length of the OSDP readers wiring is 50m 164 ft using Cat5E cable per OSDP reader The length is based on 250mA current consumption per reader 2 readers and therefore a voltage drop of 2 1V 10VDC at the reader Addressing OSDP readers An OSDP reader address is default factory set to 00 In this setting the reader will be readdressed to the firs...

Page 27: ...To connect OUT reader power off MPA1C1 and connect the OUT reader in addition to the IN reader The OUT reader will be automatically readdressed 02 when the panel is powered up again Note For OSDP reader addressing settings see reader instruction installation manuals are manufacturer dependent If areader is already addressed as 01 or 02 thereader will not be readdressed ...

Page 28: ...ow The 12VDC OUTislimited to 500mA In thiscase the controller may bepowered using PoE or external 12VDC The DR LCK SWITCHED GROUND SW GND door operation can be set in the web user interface and host software as FAIL SAFE or FAIL SECURE If the door operation is set for FAIL SECURE a door strike that locks without power can be connected If the door operation is set for FAIL SAFE the door strike that...

Page 29: ...ressor kits as shown below The 12VDC must be taken from the external Power supply as shown below If needed the AUX OUT door operation can be set in the web user interface and host software as Fail safe and Fail secure If the door operation is set as Fail Secure a door strike that locks without power can be connected If the door operation is set as Fail Safe a magnetic lock that releases without po...

Page 30: ...tage potential free connections upto 2A 30VDC Power Factor is 0 6 There are 3 outputs at the AUX OUT terminal block N C Normally Closed Connected to COM when relay is not energized COM Common Connected to either N C or N O N O Normally Open Connected to COM when relay is energized ...

Page 31: ... config ured as Normally Open or Normally Closed contacts and as supervised or non supervised All inputs on the Controller Board and the additional inputs have default functions but they can be configured for general purpose inputs Default Board Configuration Terminal Block DrCnt Door Contact N C DR INPUTS GND DrCnt REX Request To Exit N C DR INPUTS GND REX T LID Cover Tamper N C TAMPER GND T LID ...

Page 32: ...rd 2 2K ohm resistors will be used The MPA1C1 panel accepts only 2 2K ohm values The wire used for the inputs cannot exceed 30 ohms over the entire length of the cable Remember that the distance from the panel to the door must be doubled to determine the total resistance The system has not been verified for compliance with UL1076 Burglar Alarm units and systems ...

Page 33: ...32 Connect Ethernet cable Ethernet cable can be with Power over Ethernet The Enclosure has been designed to lead the Ethernet cable as smooth as pos sible and to lead away from the tamper switch ...

Page 34: ...tofactory default configurations and activate the Bluetooth communication for the commissioning application The Bluetooth on the MPA1C1 will remain active for 30 minutes Step 4 After downloading the commissioning configuration to the MPA1C1 the MPA1C1 will automatically restart Step 5 Check for the RUN LED for a successful power up If the LED is blinking green slowly the panel is powered up succes...

Page 35: ...ction provides wiring diagrams for each of the system configurations Ethernet Connection for standalone web mode Note UL294 and CAN ULC60839 11 1 evaluation consists of the stand alone mode of this device MPA1C 1 Panel MPA1C 1 Panel ...

Page 36: ...e The Network must provide DHCP server or use dedicated Network configuration with a router as shown in next section The Network must provide firewall protection from unauthorized access EVL is not evaluated by UL294 and CAN ULC60839 11 1 MPA1C 1 Pri mary MPA1C1 Primary ...

Page 37: ...36 Ethernet Virtual Loop network dedicated to Access Control Note The router must provide DHCP service EVL is not evaluated by UL294 and CAN ULC60839 11 1 ...

Page 38: ...ns Note EVL is not evaluated by UL294 and CAN ULC60839 11 1 The network must provide DHCP server or use dedicated Network configuration with a router shown in next section It is recommend for the network to provide firewall protection from unauthorized access ...

Page 39: ...Locations 2 and 3 Controllers that are on a different subnetwork than the Master which is likely the case for loops across multiple locations will NOT be automatically discovered by the Primary controller In this case it is recommended that you request an IP address reservation from your network provider or administrator This address will be needed when the user sets up the Master controller There...

Page 40: ...face OSDP READER Reader Power See Power outputs section Maximum output current for reader s is 500mA 12VDC nominal Reader Data Communication Single half duplex RS485 OSDP V2 1 8 with multi drop support at 9600 Baud Power input PWR IN An External DC power supply can be connected PWR IN 12V IN and GND The input voltage is specified at 10 to 15VDC 12VDC Nominal Maximum input current is 900mA 12VDC Po...

Page 41: ...is split between on board power consumption and external load consumption A maximum current capacity of 700mA 12VDC is available for all external devices combined Note If connected to a PoE or higher Power Sourcing Equipment PSE the MPA1C1 will successfully negotiate Class 3 power so the MPA1C1 can be plugged into any PSE device but will only draw up to Class 3 power Two readersper door can still ...

Page 42: ...lable in the PoE 802 3af Power Class 3 standard is 15 4W This limit is generally at 48VDC and it is measured at the output of the power injector or PoE switch Line losses cause a decrease in the power available at the panel when you use longer Ethernet cable lengths You can minimize these line losses by using either of the following methods Device Element Current Door strike or magnetic lock curre...

Page 43: ...oE powered 32 to 120 F 0 to 49 C if powered from external 12VDC Power supply Humidity 5 to 85 RHNC For Canada Humidity 93 2 at a temperature of 32 2 C Indoor dry MPA1C1 Controller Height 3 95 100mm Width 1 78 45mm Depth 1 1 28mm The Controller is designed to fit in a single gang US junction Box MPA1ENCP Plastic Enclosure Height 5 51 140mm Width 7 09 180mm Depth 1 7 43mm MPA1P MPA1 Kit in Plastic E...

Page 44: ...rance IV Standby Power I Cable Specifications Description AWG Maximum Distance Feet Meters Readers 8 Conductor Shielded CAT 5E 6E FTP 22 24 OSDP 150 m 500 Ft Depending on minimum voltage input of the reader Alarm Input Twisted Pair Shielded CAT 5E 6E FTP 22 24 300 m 1000 Ft Relay Outputs Twisted Pair Shielded CAT 5E 6E FTP 22 24 300 m 1000 Ft ...

Page 45: ...one associated with the card If it is not a valid card the door relay remains locked Door Egress REX Door Lock Door Status Operation Step 1 Activate the door egress input REX Step 2 The panel energizes the door relay associated with the particular door egress input for a default time of 10 seconds Step 3 If the door status goes from close to open to close again during the 10 second door open perio...

Page 46: ...ice Utility App to reconfigure the unit No communica tions exist with the Ethernet port Only a panel set up to be a PRIMARY Panel will have communications on the Ethernet port If the panel is set up to be a SECONDARY panel in EVL Ethernet Virtual Loop Mode then access the panel via the PRIMARY panel after registering the SECONDARY panel in the PRIMARY panel If you need to the access the panel dire...

Page 47: ...orrect addressing on the OSDP readers Addresses other than 00 01 or 02 are not recognized Set the reader in one of these addresses 00 for auto addressing 01 for entry reader 02 for exit reader Option 3 Make sure that the reader baud rate is set to 9600 Baud Option 4 Make sure that the reader accepts secure channel communication Problem Solution ...

Page 48: ...oor contact DrCnt input is triggered or released Tamper T LID input is triggered or released LED RUN Green RUN Activity LED slowly blinks 1 second on one second off in normal operation Blinks rapidly when the RESET button is pressed for 20 seconds Turns OFF after 20 seconds of continuous pressing of the RESET button LED BLE Blue Bluetooth LED for commissioning with Device Utility App Blinks slowly...

Page 49: ...220 battery for Controller MPA1ENCP Plastic Enclosure for MPA1C1 Listed by UL Packing List MPA1 Plastic enclosure including Tamper switch and cable MPA1P Kit Including MPA1C1 and MPA1ENCP Listed by UL Packing List MPA1 Controller mounted in MPA1 Plastic enclosure including Tamper switch and cable QR code for online manuals and translations Printed English Installation manual Printed English Quick ...

Page 50: ...it an e mail support question and we will respond within 2 business days Schedule Technical Support Coordinate a scheduled time that works best for you and your customer Hours for Scheduled Support are 10AM 4PM EST USA 800 323 4576 Monday through Friday 7 00 am to 7 00 pm Central Standard Time CST except company holidays EMEA Monday through Friday 9 00 am to 7 00 pm EST The 800 323 4576 is correct...

Page 51: ...cess the Download Center for the latest firmware and software updates Knowledge Base Library Technical bulletins user guides and how to documents Case History Ability to view cases recorded by Technical Support and view the status of a database service Notification Center Sign up to receive up to date product notifications Web For technical assistance visit https www honeywellaccess com ...

Page 52: ... W Forest Hill Avenue Oak Creek WI 53154 United States 800 323 4576 414 766 1798 Fax www honeywellaccess com Specifications subject to change without notice Honeywell All rights reserved Document 800 26169_ Rev E Date September 2020 ...