Page 1 of 3
702711/01
Digital to Analog Display / Display Controller
DX2011 DX2012
DX2011 & DX2012 units accept either single or dual inputs of 0 to 20mA, 4 to 20mA, or (with jumper change) 0 to 10 volts. Inputs can be
independently scaled to directly display chosen physical quantities on the 5-digit plus sign display. A selectable ‘combined-mode’ adds a third
scaleable display of an arithmetic combination of dual signals.
DX2012 only: Two PNP switching transistors provide preset-adjustable control outputs. In single-input mode both outputs act on input A displayed
values. In dual-input mode output 1 acts on input A displayed value, output 2 on input B displayed value. In combined-mode both outputs act on
the displayed value of (A– B) differential algorithm.
Programming Menus
There are two menus. ‘Basic settings’ menu establishes the functional configuration of the unit. ‘Operating parameters’ menu scales the system
to display numeric values representing chosen physical values; also the arithmetic algorithm of the ‘combined-mode’ display, and (DX2012 only)
presets digital setpoints for the two switching outputs.
*
Units are factory set to these default settings. To reset to the default settings: press & hold the ‘Mode/Enter’ pushbutton while applying power
to the unit.
Menu-point.
Settings (*default)
Mode
Input A only
Inputs A and B
Consult factory
Input A minus input B
Consult factory
Consult factory
Display % brightness
(80,60,40,20)
No locks
All locked
Locked except setpoint
preset (DX2012)
Output 1 normally open
Output 1 normally closed
Consult factory
Consult factory
Output 2 normally open
Output 2 normally closed
Consult factory
Consult factory
Consult factory
Consult factory
Programming
Basic settings menu
Simultaneously press & hold ‘Mode/Enter’ & ‘Set’
pushbuttons to enter ‘Basic settings’ menu.
Mode/Enter
Set
Mode/Enter
Set
Mode/Enter
Set
Pressing ‘Set’, step & view ‘modE’ options.
etc…
etc…
Select required option; press ‘Mode/Enter’ to enter
& move to next menu-point.
Pressing ‘Set”, step & view ‘brightness’ options.
Select required option; press ‘Mode/Enter’ to enter
Then…
Complete the ‘Basic settings’ menu.
After pressing ‘Mode/Enter’; wait 10 secs to exit
into operating mode, alternatively push-and-hold
‘Mode/Enter’ >3 secs.
DX2011
DX2012
*
*
*
*
*
Concerning Safety
...ifm efector makes every effort to build a dependable product, but
every product will eventually fail. Therefore, your equipment must be designed to prevent
property damage and personal injury if our products fail. ifm efector switches are not
designed to be used as stand-alone devices to protect or guard human life or limb.
TEL: 800-441-8246 • FAX: 800-329-0436
www.ifmefector.com
ifm efector