ML6284 NON-SPRING RETURN DIRECT COUPLED DAMPER ACTUATOR

Fig. 9. Common transformer with two controller outputs 

and two ML6284D,F actuators.

Fig. 10. Common transformer with one controller output 

and two ML6284A,C actuators.

CHECKOUT

Perform the following steps to checkout the ML6284

 Non-Spring Return Direct Coupled Damper Actuator.

1.

Check the actuator position indicator and the damper 

shaft position to see that they agree.

2.

If the actuator has time-out function, apply 24 Vac to 

black (T1) lead and red (T2) lead. See Fig. 5.

3.

Apply 24 Vac control signal to blue (B) lead with respect 

to black (T1) lead (see Fig. 5). Actuator should drive 

damper open.

4.

Apply 24 Vac control signal to yellow (W) lead with 

respect to black (T1) lead (see Fig. 5). Actuator should 

drive damper closed.

5.

If 24 Vac control signal is removed, actuator should 

stop.

TROUBLESHOOTING

Perform the following troubleshooting steps if the actuator 

does not drive, travel full stroke, or operate properly during the 

checkout. 

NOTE: Perform these steps before replacing the actuator.

1.

Check the actuator label to verify that proper power and 

control signal requirements have been met.

2.

Check for 24 Vac at actuator black (T1), yellow (W) or 

blue (B), and red (T2) [if actuator has time-out function] 

leads when the actuator should be driving. If the voltage 

is not present or is low, check power supply and 

controller.

3.

If the actuator does not drive in the correct direction 

when a control signal is applied, reverse the yellow and 

blue wires.

4.

Remove power and fully depress and hold disengage 

button down while turning damper shaft clockwise 

 

and counterclockwise

. If the damper shaft turns 

freely through the entire 90¡ stroke and the actuator is 

installed correctly, replace the actuator.

5.

If the damper shaft will not turn freely for the full 90° 

check for any bind and make sure the actuator is loose 

on the mounting bracket. If necessary, adjust mounting 

bracket to prevent binding.

6.

If no binding is noticed in the actuator and damper 

assembly, remove the actuator and turn the damper 

shaft clockwise

and counterclockwise

. If 

the damper does not turn freely, repair or replace the 

damper.

7.

If the damper turns, fully depress and hold the actuator 

disengage button down and turn the actuator hub 

clockwise

 and counterclockwise

. If the 

actuator hub does not turn, replace the actuator.

8.

If the actuator and damper turn freely, remount the 

actuator to the damper in accordance with the 

instructions in the Installation section. Make sure the 

actuator and mounting bracket do not bind. Make sure 

the actuator and damper are both at the same end stop 

(clockwise

or counterclockwise

) when they 

are assembled. Hook up the wires and repeat the 

checkout. Troubleshoot again, if necessary.

L1 

(HOT)

L2

1

1

RED
BLACK

RED

BLACK

ML6284D,F

ML6284D,F

M4886A

POWER SUPPLY.  PROVIDE DISCONNECT MEANS 

AND OVERLOAD PROTECTION AS REQUIRED.

CONTROLLER

CONTROLLER

BLUE

YELLOW

BLUE

YELLOW

L1 

(HOT)

L2

1

1

BLACK

BLACK

ML6284A,C

ML6284A,C

M4887A

POWER SUPPLY.  PROVIDE DISCONNECT MEANS 

AND OVERLOAD PROTECTION AS REQUIRED.

CONTROLLER

BLUE

YELLOW

BLUE

YELLOW

Summary of Contents for ML6284

Page 1: ...it switch adjustments by limiting stall torque to 250 lb in 28 3 N m maximum 95 stroke provides necessary compression of rubber neoprene gaskets commonly used on 90 low leakage dampers Manual clutch allows for manual adjustment 92 second synchronous timing can eliminate need for feedback position indication in closed loop temperature control applications Removable splined output hub permits premou...

Page 2: ...t Duty Feedback Resistor 500 ohm linear potentiometer Cable Ratings Control Standard models include nonplenum UL CSA rated 30V 60 C 20 gauge cable Auxiliary Switch UL CSA rated 300V 90 C 18 gauge Controller Type Floating spdt Torque Ratings at Rated Voltages Lift and Hold Minimum 150 lb in 17 N m Breakaway Minimum 150 lb in 17 N m Stall Minimum 150 lb in 17 N m Stall Maximum 250 lb in 28 3 N m Tor...

Page 3: ...or and mounting bracket in in mm 9 32 7 3 PLACES 1 17 32 39 3 3 32 79 4 102 7 16 11 1 1 4 32 7 11 16 196 8 7 16 215 36 914 1 2 12 5 8 17 13 32 10 1 2 13 3 4 19 7 8 22 1 25 3 5 32 80 1 2 13 1 2 13 1 11 16 43 2 1 2 63 3 5 16 84 4 1 2 114 5 127 6 152 1 4 6 1 1 REMOVABLE RETAINING RING FOR REMOVAL OF HUB SLEEVE M7618B 1 4 6 1 8 3 2 51 15 16 24 1 29 32 48 ...

Page 4: ...ing accessories and for servicing Mounting The ML6284 Non Spring Return Direct Coupled Damper Actuator is designed to operate a damper by driving the damper shaft either cw or ccw depending on damper design All actuators are shipped in the fully closed position The ML6284 Non Spring Return Direct Coupled Damper Actuator is designed with removable hub inserts to accommodate specific damper shaft si...

Page 5: ...e bracket tab is midway in the actuator slot Mark the screw holes for installing the mounting bracket on the damper housing 4 Remove the mounting bracket and actuator 5 Drill or center punch the starting holes for the mounting bracket screws or use no 10 self tapping sheet metal screws not supplied 6 Place the actuator and mounting bracket back into position over the damper shaft and install the m...

Page 6: ...act It stops when neither contact is made IMPORTANT The ML6284 can operate with DDC controller that emulates an spdt break before make switch Do not short cycle the actuator Short cycling of the actuator can cause premature failure The actuator has a position indicator to show shaft position As the indicator moves with the shaft it gives an angular representation of the damper position There are f...

Page 7: ...NS AND OVERLOAD PROTECTION AS REQUIRED 500 OHM POTENTIOMETER ORANGE OPEN TAN GREEN CLOSED L1 HOT L2 1 1 2 2 3 3 MOTOR TIME OUT 24 VAC B BLUE W YELLOW T2 RED T1 BLACK ML6284 M4884A POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED TIME OUT FUNCTION AVAILABLE WITH ML6284D F MODELS 500 OHM POTENTIOMETER ORANGE OPEN TAN GREEN CLOSED 12 82 M7877A COMMON COMMON NO NO NC NC WHITE ...

Page 8: ...s low check power supply and controller 3 If the actuator does not drive in the correct direction when a control signal is applied reverse the yellow and blue wires 4 Remove power and fully depress and hold disengage button down while turning damper shaft clockwise and counterclockwise If the damper shaft turns freely through the entire 90 stroke and the actuator is installed correctly replace the...

Reviews: