background image

ML6284 NON-SPRING RETURN DIRECT COUPLED DAMPER ACTUATOR

7

63-2505

Fig. 4. ML6284 Actuator typical mechanical connection.

Fig. 5. ML6284A,C typical wiring diagram.

Fig. 6. ML6284D,F typical wiring diagram.

Fig. 7. ML6284 Actuator wiring for auxiliary switches.

Fig. 8. Common transformer with two controller outputs 

and two ML6284A,C actuators.

M7874

MOUNTING

BRACKET

TO JUNCTION

BOX (UP TO

3 FT AWAY)

30

30

0

60

60

90

12

12

L1 

(HOT)

L2

1

1

2

2

MOTOR

24 VAC

B

BLUE

W

YELLOW

T1 BLACK

ML6284A,C

M4883A

POWER SUPPLY.  PROVIDE DISCONNECT MEANS AND OVERLOAD

PROTECTION AS REQUIRED.

500 OHM POTENTIOMETER.

ORANGE (OPEN)

TAN

GREEN (CLOSED)

L1 

(HOT)

L2

1

1

2

2

3

3

MOTOR

TIME OUT

24 VAC

B

BLUE

W

YELLOW

T2

RED

T1

BLACK

ML6284

M4884A

POWER SUPPLY.  PROVIDE DISCONNECT MEANS AND 

OVERLOAD PROTECTION AS REQUIRED.

TIME OUT FUNCTION AVAILABLE WITH ML6284D,F MODELS.

500 OHM POTENTIOMETER.

ORANGE (OPEN)

TAN

GREEN (CLOSED)

12 

82 

M7877A

COMMON

COMMON

NO

NO

NC

NC

WHITE/RED

WHITE/BLUE
WHITE/YELLOW
BLACK/RED

BLACK/BLUE

BLACK/YELLOW

INTERNAL

AUXILIARY

SWITCH

3A, 24 VAC

SWITCHES SHOWN AT ACTUATOR (CCW)

CLOSED POSITION.

L1 

(HOT)

L2

1

1

BLACK

BLACK

ML6284A,C

ML6284A,C

M4885A 

POWER SUPPLY.  PROVIDE DISCONNECT MEANS 

AND OVERLOAD PROTECTION AS REQUIRED.

CONTROLLER

CONTROLLER

BLUE

YELLOW

BLUE

YELLOW

Summary of Contents for ML6284

Page 1: ...it switch adjustments by limiting stall torque to 250 lb in 28 3 N m maximum 95 stroke provides necessary compression of rubber neoprene gaskets commonly used on 90 low leakage dampers Manual clutch allows for manual adjustment 92 second synchronous timing can eliminate need for feedback position indication in closed loop temperature control applications Removable splined output hub permits premou...

Page 2: ...t Duty Feedback Resistor 500 ohm linear potentiometer Cable Ratings Control Standard models include nonplenum UL CSA rated 30V 60 C 20 gauge cable Auxiliary Switch UL CSA rated 300V 90 C 18 gauge Controller Type Floating spdt Torque Ratings at Rated Voltages Lift and Hold Minimum 150 lb in 17 N m Breakaway Minimum 150 lb in 17 N m Stall Minimum 150 lb in 17 N m Stall Maximum 250 lb in 28 3 N m Tor...

Page 3: ...or and mounting bracket in in mm 9 32 7 3 PLACES 1 17 32 39 3 3 32 79 4 102 7 16 11 1 1 4 32 7 11 16 196 8 7 16 215 36 914 1 2 12 5 8 17 13 32 10 1 2 13 3 4 19 7 8 22 1 25 3 5 32 80 1 2 13 1 2 13 1 11 16 43 2 1 2 63 3 5 16 84 4 1 2 114 5 127 6 152 1 4 6 1 1 REMOVABLE RETAINING RING FOR REMOVAL OF HUB SLEEVE M7618B 1 4 6 1 8 3 2 51 15 16 24 1 29 32 48 ...

Page 4: ...ing accessories and for servicing Mounting The ML6284 Non Spring Return Direct Coupled Damper Actuator is designed to operate a damper by driving the damper shaft either cw or ccw depending on damper design All actuators are shipped in the fully closed position The ML6284 Non Spring Return Direct Coupled Damper Actuator is designed with removable hub inserts to accommodate specific damper shaft si...

Page 5: ...e bracket tab is midway in the actuator slot Mark the screw holes for installing the mounting bracket on the damper housing 4 Remove the mounting bracket and actuator 5 Drill or center punch the starting holes for the mounting bracket screws or use no 10 self tapping sheet metal screws not supplied 6 Place the actuator and mounting bracket back into position over the damper shaft and install the m...

Page 6: ...act It stops when neither contact is made IMPORTANT The ML6284 can operate with DDC controller that emulates an spdt break before make switch Do not short cycle the actuator Short cycling of the actuator can cause premature failure The actuator has a position indicator to show shaft position As the indicator moves with the shaft it gives an angular representation of the damper position There are f...

Page 7: ...NS AND OVERLOAD PROTECTION AS REQUIRED 500 OHM POTENTIOMETER ORANGE OPEN TAN GREEN CLOSED L1 HOT L2 1 1 2 2 3 3 MOTOR TIME OUT 24 VAC B BLUE W YELLOW T2 RED T1 BLACK ML6284 M4884A POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED TIME OUT FUNCTION AVAILABLE WITH ML6284D F MODELS 500 OHM POTENTIOMETER ORANGE OPEN TAN GREEN CLOSED 12 82 M7877A COMMON COMMON NO NO NC NC WHITE ...

Page 8: ...s low check power supply and controller 3 If the actuator does not drive in the correct direction when a control signal is applied reverse the yellow and blue wires 4 Remove power and fully depress and hold disengage button down while turning damper shaft clockwise and counterclockwise If the damper shaft turns freely through the entire 90 stroke and the actuator is installed correctly replace the...