**  Difference between switching pressure and pos-

sible reset.

***  Mean switching differential at min. and max. set-

ting

 

Deviation from the switching point during testing 
pursuant to EN 1854: air pressure switch: ± 15%.

 

If the DL does not trip at the desired switch-
ing point, correct the adjusting range using the 
hand wheel. Relieve the pressure and repeat 
the process.

Function check

 

We recommend a function check once a year.

DL..A

 

Press the test key during operation – the pressure 
switch switches.

TEST

+

 

In case of differential pressure, press both keys 
simultaneously.

TEST

TEST

+

Accessories

Z-angle bracket

49,5 (1.9")

44,5 (1.7")

2,7

(0.11")

3,5

(0.14")

ø 6,1 (ø 0.24")

50 (1.97")
30 (1.18")

20

(0.79")

25 (0.98")

45 (1.77")

24 (0.94")

43

 -0,3

 (1.69")

64 (2.52")

6 (0.24")

16

(0.63")

39 (1.53")

4,20

 +0,1

(0.17")

5,2 (0.2")

11,3 (0.44")

7 (0.27")

7,5 (0.3")

10 (0.4")

 DL..A: Rp ¼

(DL..AT: ¼" NPT)

 DL..A: Rp ¼

(DL..AT: ¼" NPT)

DL 1,5A

DL 3A

DL 3K

DL 5–150A

DL 5–150K

2,7

(0.11")

3,5

(0.14")

64 (2.5")

54,5 (2.1")

2,7

(0.11")

45 (1.8")

49,5 (1.9")

44,5 (1.7")

40 (1.6")

59 (2.3")

ø 5,5 (0.22")

ø 6 (0.22")

ø 4,2 (0.17")

10 (0.39")

1 (0.04")

DL..K: Order No.: 74916158
DL..A: Order No.: 74913661

Fastening set with screws, U-shape bracket

M4 x 10

M4 x 12

50 (1.97")

47,5 (1.87"

)

75 (2.95")

30 (1.18")

20

(0.79")

25 (0.98")

45 (1.77")

20

(0.79")

24 (0.94")

43

 -0,3

 (1.69")

64 (2.52")

40 (1.57")

6 (0.24")

16

(0.63")

39 (1.53")

4,20

 +0,1

(0.17")

5,2

(0.2")

10

(0.4")

Order No.: 74915387

Restrictor orifice for DL..A

In the case of high pressure fluctuations, we recommend 
using a restrictor orifice (contains non-ferrous metals).

R

 

¼

Rp

 

¼

Hole diameter Ø 0.2 mm, Order No.: 75456321.
Hole diameter Ø 0.3 mm, Order No.: 75441317.

Standard coupler plug

Order No.: 74916159

Pilot lamp set, red or blue

Summary of Contents for kromshroeder DL H Series

Page 1: ...d electricians Conversion spare parts All technical changes are prohibited Only use OEM spare parts Changes to edition 09 18 The following chapters have been changed Installation Technical Data Logistics Certification Checking the usage DL H DL N For monitoring increasing and decreasing air or flue gas pressure DL H switches and locks off with rising pressure DL N switches and locks off with falli...

Page 2: ...heel Installation position as required preferably with vertical diaphragm Then the switching point pS corresponds to the scale value SK set on the hand wheel In other installation positions the switching point pS will change and no longer correspond to the scale value SK set on the hand wheel Check the switching point pS SK pS SK 0 18 mbar pS SK 0 18 mbar Connection facilities For 1 mm thick mount...

Page 3: ...t damaged during opera tion note the switching capacity see page 5 Technical data In the case of low switching capacities such as 24 V 8 mA for example we recommend us ing an RC module 22 Ω 1 μF in air containing silicone or oil NO C 1 µF 2 NC 1 COM 3 1 Disconnect the system from the electrical power supply M16 x 1 5 ø 4 10 mm 3 4 2 5 6 7 Contacts 3 and 2 close when subject to increas ing pressure...

Page 4: ...imultaneously TEST TEST Accessories Z angle bracket 50 1 97 30 1 18 20 0 79 25 0 98 45 1 77 2 11 3 0 44 7 0 27 7 5 0 3 10 0 4 40 1 6 59 2 3 ø 5 5 0 22 ø 6 0 22 ø 4 2 0 17 10 0 39 1 0 04 DL K Order No 74916158 DL A Order No 74913661 Fastening set with screws U shape bracket M4 x 10 M4 x 12 50 1 97 47 5 1 87 75 2 95 30 1 18 20 0 79 25 0 98 45 1 77 20 0 79 24 0 94 43 0 3 1 69 64 2 52 40 1 57 6 0 24 1...

Page 5: ...max withstand pressure 300 mbar Diaphragm pressure switch silicone free Diaphragm NBR Housing glass fibre reinforced PBT plastic with low gas release Max tightening torque see Technical Information bulletin DL D GB F www docuthek com Weight DL A 200 g 7 1 oz DL K 190 g 6 7 oz Electrical data Micro switch to EN 61058 1 Contact gap 3 mm μ Switching capacity U I cos φ 1 I cos φ 0 6 DL 24 250 V AC 0 0...

Page 6: ...g for the first time If stored for longer than this the overall service life will be reduced by the corresponding amount of extra storage time Packaging The packaging material is to be disposed of in ac cordance with local regulations Disposal Components are to be disposed of separately in accordance with local regulations Certification Declaration of conformity We the manufacturer hereby declare ...

Reviews: