Max. inlet pressure p
max.
= withstand pressure, mains
voltage, ambient temperature, enclosure: see type
label.
Installation
CAUTION
Please observe the following to ensure that the DL
is not damaged during installation and operation:
– Dropping the device can cause permanent dam-
age. In this event, replace the entire device and
associated modules before use.
– Check max. ambient temperature – see
– When using silicone tubes, only use silicone
tubes which have been sufficiently cured.
– Vapours containing silicone must not be allowed
to get into the housing.
– Condensation must not be allowed to get into
the housing. At subzero temperatures, malfunc-
tions/failures due to icing can occur.
– The service life will be shorter if subject to ozone
concentrations exceeding 200 μg/m
3
. When
installing outdoors, place the DL in a roofed
area and protect from direct sunlight (even IP 65
version).
– Avoid subjecting the DL to strong or violent
vibrations.
– In case of highly fluctuating pressures, install
a restrictor orifice, see page 4 (Restrictor
orifice for DL..A).
▷
Ensure that there is sufficient installation space.
▷
Ensure unobstructed view of the hand wheel.
▷
Installation position as required, preferably with
vertical diaphragm. Then the switching point p
S
corresponds to the scale value SK set on the
hand wheel. In other installation positions, the
switching point p
S
will change and no longer
correspond to the scale value SK set on the hand
wheel. Check the switching point.
p
S
= SK p
S
= SK + 0.18 mbar p
S
= SK - 0.18 mbar
Connection facilities
▷
For 1 mm thick mounting plates, use self-tapping
screws for plastic:
DL..AH, DL..AN: Ø 3.5 x 8 mm or Ø 4 x 8 mm.
DL..KH, DL..KN: Ø 3.5 x16 mm.
1
Fit the DL.
64 (2.5")
45 (1.8")
54,5 (2.1")
ø 2,7 x 16
(ø 0.11" x 0.6)
Rp ¼
DL..AH,
DL..AN
DL..KH,
DL..KN
ø 2,7 x 8
(ø 0.11" x 0.3")
ø 3,5 x 8
(ø 0.14" x 0.3")
49,5 (1.9")
44,5 (1.7")
M16 x 1,5
28,5 (1.1")
M16 x 1,5
28,5 (1.1")
ø 6,1 (ø 0.24")
2
Connect the pressure line.
▷
DL..A: upon delivery, port 2 is closed off by a
rubber cap.
DL..A
1 = Rp 1/4 (+)
2 = ø 4,75 x 1 mm (+)
3 = ø 4,75 x 1 mm (-)
(4 = Rp 1/8 (-))
2 = ø 4,75 x 1 mm (+)
3 = ø 4,75 x 1 mm (-)
(4 = Rp 1/8 (-))
DL 5–150A
1
DL 5–150K
2
3(4)
3(4)
2
T est
▷
Positive pressure, port 1 or 2
▷
Negative pressure, port 3; after unscrewing
port 3 also port 4
DL..K
1 = Rp 1/4 (+)
2 = ø 4,75 x 1 mm (+)
3 = ø 4,75 x 1 mm (-)
(4 = Rp 1/8 (-))
2 = ø 4,75 x 1 mm (+)
3 = ø 4,75 x 1 mm (-)
(4 = Rp 1/8 (-))
DL 5–150A
1
2
3(4)
3(4)
2
T est
▷
Positive pressure, port 2
▷
Negative pressure, port 3; after unscrewing
port 3 also port 4
Positive pressure measurement
▷
1 or 2 = positive pressure port (+).
▷
If port 2 is used, close off port 1.
▷
3 or 4 = remains open to ventilate the upper
diaphragm chamber.