Type label

DL

CE

 

2
1

3

D-49018 Osnabrück, Germany

Max. inlet pressure p

max.

 = withstand pressure, mains 

voltage, ambient temperature, enclosure: see type 
label.

Installation

 CAUTION

Please observe the following to ensure that the DL 
is not damaged during installation and operation:
–   Dropping the device can cause permanent dam-

age. In this event, replace the entire device and 
associated modules before use.

–   Check max. ambient temperature  – see 

page 5 (Technical data).

–   When using silicone tubes, only use silicone 

tubes which have been sufficiently cured.

–   Vapours containing silicone must not be allowed 

to get into the housing.

–   Condensation must not be allowed to get into 

the housing. At subzero temperatures, malfunc-
tions/failures due to icing can occur.

–   The service life will be shorter if subject to ozone 

concentrations exceeding 200 μg/m

3

. When 

installing outdoors, place the DL in a roofed 
area and protect from direct sunlight (even IP 65 
version).

–   Avoid subjecting the DL to strong or violent 

vibrations.

–   In case of highly fluctuating pressures, install 

a restrictor orifice, see page  4 (Restrictor 
orifice for DL..A).

 

Ensure that there is sufficient installation space.

 

Ensure unobstructed view of the hand wheel.

 

Installation position as required, preferably with 
vertical diaphragm. Then the switching point p

S

 

corresponds to the scale value SK set on the 
hand wheel. In other installation positions, the 
switching point p

S

 will change and no longer 

correspond to the scale value SK set on the hand 
wheel. Check the switching point.

p

S

 = SK p

S

 = SK + 0.18 mbar p

S

 = SK - 0.18 mbar

Connection facilities

 

For 1 mm thick mounting plates, use self-tapping 
screws for plastic:

 

 DL..AH, DL..AN: Ø 3.5 x 8 mm or Ø 4 x 8 mm. 
 DL..KH, DL..KN: Ø 3.5 x16 mm.

 1 

 Fit the DL.

64 (2.5")

45 (1.8")

54,5 (2.1")

ø 2,7 x 16 

(ø 0.11" x 0.6)

Rp ¼

DL..AH,

DL..AN

DL..KH,

DL..KN

ø 2,7 x 8

(ø 0.11" x 0.3")
ø 3,5 x 8

(ø 0.14" x 0.3")

49,5 (1.9")

44,5 (1.7")

M16 x 1,5

28,5 (1.1")

M16 x 1,5

28,5 (1.1")

ø 6,1 (ø 0.24")

 2 

 Connect the pressure line.

 

DL..A: upon delivery, port 2 is closed off by a 
rubber cap.

DL..A

1 = Rp 1/4 (+)

2 = ø 4,75 x 1 mm (+)

3 = ø 4,75 x 1 mm (-)

(4 = Rp 1/8 (-))

2 = ø 4,75 x 1 mm (+)

3 = ø 4,75 x 1 mm (-)

(4 = Rp 1/8 (-))

DL 5–150A

1

DL 5–150K

2

3(4)

3(4)

2

T est

 

Positive pressure, port 1 or 2

 

Negative pressure, port 3; after unscrewing 
port 3 also port 4

DL..K

1 = Rp 1/4 (+)

2 = ø 4,75 x 1 mm (+)

3 = ø 4,75 x 1 mm (-)

(4 = Rp 1/8 (-))

2 = ø 4,75 x 1 mm (+)

3 = ø 4,75 x 1 mm (-)

(4 = Rp 1/8 (-))

DL 5–150A

1

DL 5–150K

2

3(4)

3(4)

2

T est

 

Positive pressure, port 2

 

Negative pressure, port 3; after unscrewing 
port 3 also port 4

Positive pressure measurement

 

1 or 2 = positive pressure port (+).

 

If port 2 is used, close off port 1.

 

3 or 4 = remains open to ventilate the upper 
diaphragm chamber.

Summary of Contents for kromshroeder DL H Series

Page 1: ...d electricians Conversion spare parts All technical changes are prohibited Only use OEM spare parts Changes to edition 09 18 The following chapters have been changed Installation Technical Data Logistics Certification Checking the usage DL H DL N For monitoring increasing and decreasing air or flue gas pressure DL H switches and locks off with rising pressure DL N switches and locks off with falli...

Page 2: ...heel Installation position as required preferably with vertical diaphragm Then the switching point pS corresponds to the scale value SK set on the hand wheel In other installation positions the switching point pS will change and no longer correspond to the scale value SK set on the hand wheel Check the switching point pS SK pS SK 0 18 mbar pS SK 0 18 mbar Connection facilities For 1 mm thick mount...

Page 3: ...t damaged during opera tion note the switching capacity see page 5 Technical data In the case of low switching capacities such as 24 V 8 mA for example we recommend us ing an RC module 22 Ω 1 μF in air containing silicone or oil NO C 1 µF 2 NC 1 COM 3 1 Disconnect the system from the electrical power supply M16 x 1 5 ø 4 10 mm 3 4 2 5 6 7 Contacts 3 and 2 close when subject to increas ing pressure...

Page 4: ...imultaneously TEST TEST Accessories Z angle bracket 50 1 97 30 1 18 20 0 79 25 0 98 45 1 77 2 11 3 0 44 7 0 27 7 5 0 3 10 0 4 40 1 6 59 2 3 ø 5 5 0 22 ø 6 0 22 ø 4 2 0 17 10 0 39 1 0 04 DL K Order No 74916158 DL A Order No 74913661 Fastening set with screws U shape bracket M4 x 10 M4 x 12 50 1 97 47 5 1 87 75 2 95 30 1 18 20 0 79 25 0 98 45 1 77 20 0 79 24 0 94 43 0 3 1 69 64 2 52 40 1 57 6 0 24 1...

Page 5: ...max withstand pressure 300 mbar Diaphragm pressure switch silicone free Diaphragm NBR Housing glass fibre reinforced PBT plastic with low gas release Max tightening torque see Technical Information bulletin DL D GB F www docuthek com Weight DL A 200 g 7 1 oz DL K 190 g 6 7 oz Electrical data Micro switch to EN 61058 1 Contact gap 3 mm μ Switching capacity U I cos φ 1 I cos φ 0 6 DL 24 250 V AC 0 0...

Page 6: ...g for the first time If stored for longer than this the overall service life will be reduced by the corresponding amount of extra storage time Packaging The packaging material is to be disposed of in ac cordance with local regulations Disposal Components are to be disposed of separately in accordance with local regulations Certification Declaration of conformity We the manufacturer hereby declare ...

Reviews: