Negative pressure measurement

 

3 or 4 = negative pressure port (-).

 

1 or 2 = remains open to ventilate the upper 
diaphragm chamber.

Differential pressure measurement

 

1 or 2 = port for the higher positive pressure or 
lower negative pressure (+).

 

3 or 4 = port for the lower positive pressure or 
higher negative pressure (-).

 3 

 Seal the ports that are not in use.

Wiring

 

If the DL..G has switched a voltage > 24 V and 
a current > 0.1 A once, the gold plating on the 
contacts will have been burnt through. It can 
then only be operated at this power rating or 
higher power rating.

 

Pressure switch DL can be used in Zone 1 (21) 
and 2 (22) hazardous areas if an isolating am-
plifier is installed upstream in the safe area as 
“Ex-i” equipment pursuant to EN 60079-11 
(VDE 0170-7):2012.

 

DL as “simple electrical equipment” pursuant to 
EN 60079-11:2012 corresponds to the Tempera-
ture class T6, Group II. The internal inductance/
capacitance is Li = 0.2 μH/Ci = 8 pF.

CAUTION

To ensure that the DL is not damaged during opera-
tion, note the switching capacity, see page  
(Technical data).

 

In the case of low switching capacities, such as 
24 V, 8 mA, for example, we recommend us-
ing an RC module (22 Ω, 1 μF) in air containing 
silicone or oil.

NO

C = 1 µF

2

NC

1

COM

3

 1 

  Disconnect the system from the electrical power 

supply.

M16 x 1,5:

ø 4–10 mm

3

4

2

5

6

7

 

Contacts 

3

 and 

2

 close when subject to increas-

ing pressure. Contacts 

1

 and 

3

 close when sub-

ject to falling pressure.

COM

3

NC

1

NO

2

NO

2

NC

1

COM

3

L1

Adjustment

 

The switching point is adjustable via hand wheel.

 1 

  Disconnect the system from the electrical power 

supply.

 2 

 Detach the housing cover, see page 5 (Tech-

nical data).

 3 

 Connect an ohmmeter.

NO

2

NC

1

COM

3

COM

3

NC

1

NO

2

0

1 cm = 1 mbar

 4 

 Set the switching point using the hand wheel.

 5 

 Connect a pressure gauge.

NO

2

NC

1

COM

3

COM

3

NC

1

NO

2

0

1 cm = 1 mbar

 6 

  Apply pressure. In doing so, monitor the switching 

point on the ohmmeter and the pressure gauge.

 

Max. inlet pressure p

max.

 = 300 mbar = withstand 

pressure.

Type

Adjusting 

range* 

[mbar]

Reset pres-

sure** [mbar]

DL 10..H, ..N

1 – 10

0.4 – 1

DL 50..H, ..N

2.5 – 50

1 – 2

DL 150..H, ..N

30 – 150

2 – 5

*  Adjusting tolerance = ± 15% of the scale value.

Summary of Contents for kromshroeder DL H Series

Page 1: ...d electricians Conversion spare parts All technical changes are prohibited Only use OEM spare parts Changes to edition 09 18 The following chapters have been changed Installation Technical Data Logistics Certification Checking the usage DL H DL N For monitoring increasing and decreasing air or flue gas pressure DL H switches and locks off with rising pressure DL N switches and locks off with falli...

Page 2: ...heel Installation position as required preferably with vertical diaphragm Then the switching point pS corresponds to the scale value SK set on the hand wheel In other installation positions the switching point pS will change and no longer correspond to the scale value SK set on the hand wheel Check the switching point pS SK pS SK 0 18 mbar pS SK 0 18 mbar Connection facilities For 1 mm thick mount...

Page 3: ...t damaged during opera tion note the switching capacity see page 5 Technical data In the case of low switching capacities such as 24 V 8 mA for example we recommend us ing an RC module 22 Ω 1 μF in air containing silicone or oil NO C 1 µF 2 NC 1 COM 3 1 Disconnect the system from the electrical power supply M16 x 1 5 ø 4 10 mm 3 4 2 5 6 7 Contacts 3 and 2 close when subject to increas ing pressure...

Page 4: ...imultaneously TEST TEST Accessories Z angle bracket 50 1 97 30 1 18 20 0 79 25 0 98 45 1 77 2 11 3 0 44 7 0 27 7 5 0 3 10 0 4 40 1 6 59 2 3 ø 5 5 0 22 ø 6 0 22 ø 4 2 0 17 10 0 39 1 0 04 DL K Order No 74916158 DL A Order No 74913661 Fastening set with screws U shape bracket M4 x 10 M4 x 12 50 1 97 47 5 1 87 75 2 95 30 1 18 20 0 79 25 0 98 45 1 77 20 0 79 24 0 94 43 0 3 1 69 64 2 52 40 1 57 6 0 24 1...

Page 5: ...max withstand pressure 300 mbar Diaphragm pressure switch silicone free Diaphragm NBR Housing glass fibre reinforced PBT plastic with low gas release Max tightening torque see Technical Information bulletin DL D GB F www docuthek com Weight DL A 200 g 7 1 oz DL K 190 g 6 7 oz Electrical data Micro switch to EN 61058 1 Contact gap 3 mm μ Switching capacity U I cos φ 1 I cos φ 0 6 DL 24 250 V AC 0 0...

Page 6: ...g for the first time If stored for longer than this the overall service life will be reduced by the corresponding amount of extra storage time Packaging The packaging material is to be disposed of in ac cordance with local regulations Disposal Components are to be disposed of separately in accordance with local regulations Certification Declaration of conformity We the manufacturer hereby declare ...

Reviews: