CONNECTION OF IRD 1020.1 TO SATRONIC BURNER CONTROL BOXES

IRD

1020.1

IRD

1020.1

IRD

1020.1

blue

black

brown

blue

black

brown

blue

black

brown

IRD 1020.1 TERMINALS

1

2

3

4

5

6

7

1

2

brown

black

blue

Possible faults

1. LED’s light up during the pre-purge phase (control

box  switches to lockout):

a)

Sensitivity set too high

b) Stray light
c)

Ignition spark visible to detector (directly or reflection).
Correct by preventing direct sight of ignition spark.

d) Interference from ignition cable (lay cables some

distance apart, or possibly screen the detector).

2. No indication from LED’s after establishment of flame:

a)

Incorrect or faulty wiring

b) Sensitivity set too low
c)

Detector positioned wrongly (receives no light)

d) Detector or viewing window dirty
e)

Defective detector

f)

IRD flange M93 defective (cracks or other mechanical
defects)

g) wrong IRD flange, special magnetic IRD flange M93

is needed.

IRD 1020.1

Control box type

TFI 812

DKG 97.

DMG 97.

DLG 97.

Terminal no.

8

8

8

Terminal no.

1

1

2

Terminal no.

9

9

9

Control box type

MMI

Terminal no.

8

Terminal no.

2

Terminal no.

9

Control box type

TMG 740

SGU 930(i)

Terminal no.

8

N

Terminal no.

1

15

Terminal no.

20

1

SENSITIVITY –CHARACTERISTIC OF IRD 1020.1 (BLUE, WHITE)

IRD-Type

Sensitivity

Characteristic

blue

standard

For Gas- or dual fuel burner
Immune to Ignition spark detection

white

increased

For Gas- or dual fuel burner for difficult to detect flame
Immune to Ignition spark detection

Summary of Contents for IRD 1020.1

Page 1: ... 930 DKG 972 DLG 974 976 DMG 970 971 972 973 TFI 812 2 MMI 810 811 812 815 816 962 TMG 740 2 740 3 SGU 930 930i CONSTRUCTIONAL FEATURES The infra red sensor and the pre amplifier are hermetically sealed in glass and along with the electronics form an integrated unit in the flame detector Wiring is by way of a plug connection The sensitivity control and two LED s for indication of the flame signal ...

Page 2: ... harsh vibration and receives no hard knocks It is necessary for the magnetic IRD M93 flange to be mounted on a flat surface to avoid any mechanical stress which could otherwise damage it COMMISSIONING AND MAINTENANCE During commissioning and after servicing the flame monitoringsystemshouldbecheckedforfaultlessoperation as follows 1 Check that the detector is connected properly Wrong connectionsar...

Page 3: ...t or faulty wiring b Sensitivity set too low c Detector positioned wrongly receives no light d Detector or viewing window dirty e Defective detector f IRDflangeM93defective cracksorothermechanical defects g wrong IRD flange special magnetic IRD flange M93 is needed IRD 1020 1 Control box type TFI 812 DKG 97 DMG 97 DLG 97 Terminal no 8 8 8 Terminal no 1 1 2 Terminal no 9 9 9 Control box type MMI Te...

Page 4: ...16533 Mounting flange Flange M93 230V 59093 Sensor cable Plug type 3 wire 0 6 m with tag wire ends 7236001 The above ordering information refers to the standard version Special versions are also included in our product range Specifications subject to change without notice FLICKER DETECTOR IRD 1020 1 VARIANTS 35 3 26 4 5 15 1 48 ø20 5 4 17 14 104 29 50 44 ø13 5 21 8 HOLDER M93 Satronic IRD 1020 1 S...

Reviews: