2

TECHNICAL FEATURES

1. Flame detection

- Yellow- as well as blue-burning oil- and gas flames can be

monitored.

- The flame detector is suitable for operation where the

ambient temperature is within the range -20

°

 to +60

°

 C.

- The flickering detector IRD 1020.1 becomes active not

before a minimum threshold-level of steady light is
exceeded. That guarantees that neither electromagnetic-
nor ignition-spark noise are affecting the IRD.

- Sensitivity is adjustable.
- LED 1 is a warning indicator for the pre-purge phase as

well as normal operation. LED 2 indicates the actual status
of the detector: On or off.

- During pre-purge, LED 1 indicates possible stray light,

which may be produced either by a flickering or by
a steady light source, before the detector switches on
(LED 2).

- When the burner is operating normally, LED 1 acts as a

warning indication of the flame signal current sensitivity
being set too low - it begins to flicker or extinguishes
before the detector switches off.

- The compact size makes it possible to mount the detector

on any burner. For this reason the IRD mounting flange
M93 has the same dimensions and fixing holes as the FZ
flange M74. This magnetic flange provides the switch-off
facility specified in the European standard. The IRD 1020.1
therefore only functions with the M93 flange.

2. Installation instructions

- The detector probe should be fitted so that it receives the

light which pulsates most strongly. This can be achieved
by positioning the detector as close as possible to the
flame or by directing it at a particular zone of the flame (e.g.
by using a sighting tube).

- No stray light must be allowed to fall on the detector (e.g.

through cracks or from a sight glass). Pulsating stray light
(e.g. from fluorescent lighting or light bulbs) could cause
the system to switch to lockout. Due to the very high
sensitivity of the detector, it should not be exposed
directly or indirectly (reflections) to the ignition spark.

- The infra-red flicker detector should be fitted in such a way

that the ambient temperature cannot under any
circumstances rise above 60 

°

C. At higher temperatures,

there is a risk of incorrect operation and the life expectancy
of the unit could be reduced. In addition, care should be
taken that the detector is not subjected to unusually harsh
vibration and receives no hard knocks.

- It is necessary for the magnetic IRD M93 flange to be

mounted on a flat surface to avoid any mechanical stress
which could otherwise damage it.

COMMISSIONING AND MAINTENANCE

During commissioning and after servicing, the flame
monitoring system should be checked for faultless operation
as follows:
1. Check that the detector is connected properly. Wrong

connections are a risk to safety, and could cause damage
to the detector unit or burner system.

2. Adjust to maximum sensitivity and start the burner: If the

LED indicator is lit after the start impulse, carefully adjust
the sensitivity control until LED 1 extinguishes. No LED
should light up during the pre-purge phase.

3. When the burner is operating normally, carefully turn

back the sensitivity control until LED 1 begins to flicker.
Increase the setting again by one or two increments until
both LED’s are lit. If LED 1 does not flicker even at
position 1: Leave potentiometer at position 1-2. This
adjustment should be carried out when the flame signal
current is weakest (at a cold-start, shortly after flame
establishment or after stabilisation).

4. The flame detection device requires no maintenance of

any kind, and as it is classed as safety equipment, no
attempt should be made to open the housing.

5. Because the nature of the flame can change in time due

to the accumulation of dirt, the indicators on the detector
should be checked periodically.

Please note:

Burner operating normally

= both LED’s on

Burner in pre-purge phase = both LED’s off

For safety reasons the sensitivity must not be set
higher than necessary.

Safety Checks:

1. Shut off the fuel supply when the burner is in the "run"

position. The indicator LEDs should extinguish and the
control box go to lockout.

2. Start the burner with the fuel supply shut off. The control

box must go to lockout at the end of the safety time due
to absence of flame.

3. Remove the detector from its mounting flange during a

pause, fit onto it a second flange M93. Start the burner
with straylight on the detector (e.g. by a cigarette-lighter,
bulb or a neonlight. Daylight or a torch is not suitable).
The control box must go to lockout due to stray light
either immediately or at the end of the pre-purge,
depending on the model.

Test switch-off facility:

1. Remove the detector durning the "run" position from its

special M93 flange. The control box must go to lockout
due to the activated switch-off facility.

IRD 1020.1

Summary of Contents for IRD 1020.1

Page 1: ... 930 DKG 972 DLG 974 976 DMG 970 971 972 973 TFI 812 2 MMI 810 811 812 815 816 962 TMG 740 2 740 3 SGU 930 930i CONSTRUCTIONAL FEATURES The infra red sensor and the pre amplifier are hermetically sealed in glass and along with the electronics form an integrated unit in the flame detector Wiring is by way of a plug connection The sensitivity control and two LED s for indication of the flame signal ...

Page 2: ... harsh vibration and receives no hard knocks It is necessary for the magnetic IRD M93 flange to be mounted on a flat surface to avoid any mechanical stress which could otherwise damage it COMMISSIONING AND MAINTENANCE During commissioning and after servicing the flame monitoringsystemshouldbecheckedforfaultlessoperation as follows 1 Check that the detector is connected properly Wrong connectionsar...

Page 3: ...t or faulty wiring b Sensitivity set too low c Detector positioned wrongly receives no light d Detector or viewing window dirty e Defective detector f IRDflangeM93defective cracksorothermechanical defects g wrong IRD flange special magnetic IRD flange M93 is needed IRD 1020 1 Control box type TFI 812 DKG 97 DMG 97 DLG 97 Terminal no 8 8 8 Terminal no 1 1 2 Terminal no 9 9 9 Control box type MMI Te...

Page 4: ...16533 Mounting flange Flange M93 230V 59093 Sensor cable Plug type 3 wire 0 6 m with tag wire ends 7236001 The above ordering information refers to the standard version Special versions are also included in our product range Specifications subject to change without notice FLICKER DETECTOR IRD 1020 1 VARIANTS 35 3 26 4 5 15 1 48 ø20 5 4 17 14 104 29 50 44 ø13 5 21 8 HOLDER M93 Satronic IRD 1020 1 S...

Reviews: