background image

INNCOM e7w THERMOSTAT USER GUIDE 

31-00302-01 

50 

 

 

 

5.

 

The 

PIr

 motion test is active for one minute, then automatically timeout.

 

6.

 

Press the 

F



button to return 

SERVICE MODE

 or press 

UP

 arrow button to display next 

mode.

 

Or

 

Press the 

F



button twice to exit 

SERVICE MODE

 

WIN 

 Verifying Window Position (

Win

)  

Use 

Win

 to verify the monitored window position in the guestroom is reporting correctly.

 

NOTE

 

To perform window test, Following two conditions must be satisfied for window test:

 

 

A device in the room that is monitoring and reporting window position via a 0x0002A1 Win-
dow Open message

 

 

A device in the room that has its “P5 Window Server” enabled that reports a 0x0002B01 
“Window Server Reports window is Open” for the e7w window test to work.

 

The e7w watches for the0x0002B01 “Window Server Reports Window is Open” message for its win-
dow test.

 

1.

 

Enter 

SERVICE MODE

 

 

2.

 

Press 

UP/DOWN 

arrow buttons to select 

Win

 

 

Summary of Contents for INNCOM e7w

Page 1: ...U S Registered Trademark Copyright 2020 Honeywell Inc All Rights Reserved 31 00302 01 INNCOM e7w Thermostat USER GUIDE Jan 2020 ...

Page 2: ...Honeywell By acceptance hereof each recipient agrees to use the information contained herein only for the purpose anticipated by INNCOM by Honeywell and not to dis close to others copy or reproduce any part hereof without the written consent of INNCOM by Honeywell The recipient agrees to return this document to INNCOM by Honeywell immedi ately upon request ...

Page 3: ... high voltages on normally low voltage wiring Low voltage wiring can carry hazard ous high voltages under unsafe conditions Never install or connect wiring or equip ment during electrical storms Improperly protected wiring can carry a fatal lightning surge for many miles All outdoor wiring must be equipped with properly grounded and listed signal circuit protectors which must be installed in compl...

Page 4: ...well will have no liability for any damages arising out of your use or modification to the literature You will de fend and indemnify Honeywell its affiliates and subsidiaries from and against any liability cost or damages including attorneys fees arising out of or resulting from any modification to the literature by you The material in this document is for information purposes only The content and...

Page 5: ...SYSTEM ENVIRONMENTAL CONSIDERATIONS 8 DEPLOYMENTS AND MAINTENANCE CONSIDERATIONS 8 NETWORK COMMUNICATION NOTICE 9 E7W THERMOSTAT WIRING 10 WIRING X47 L P 24VAC WITH E7W THERMOSTAT 10 WIRING X47 H P 120VAC WITH E7W THERMOSTAT 11 USER INTERACTION 12 DORMANT MODE 12 USER INTERACTION MODE 12 E7W INTERFACE NAVIGATION 12 DISPLAY FUNCTIONS 13 INSTALLATION 16 REQUIRED INSTALLATION HARDWARE 16 REQUIRED COM...

Page 6: ...Output selected as the Gr Group in step 4 39 PNG VERIFYING DEVICE COMMUNICATION PNG 44 RH MEASURING ROOM HUMIDITY RH 45 RST RESETTING E7W RST 46 WAN VERIFYING WIDE AREA NETWORK WAN 46 DOR VERIFYING DOOR POSITION DOR 47 PIR VERIFYING MOTION SENSOR PIR 49 WIN VERIFYING WINDOW POSITION WIN 50 BND BINDING AUXILIARY DEVICES BND 51 VER VERIFYING E7W VERSION VER 53 PRR REMOTE MOTION SENSOR PRR 54 BAU E7W...

Page 7: ...elated technical literature Literature Number Literature Name 31 00308 INNCOM e7w Thermostat Installation Instructions Abbreviation and Nomenclature Abbreviation Definition IRAS 2 0 Integrated Room Automation System next generation DMN Deep Mesh Network FCU Fan Coil Unit VAC Volts AC Alternating Current VDC DC Volts DC Direct Current OTW Over The Wire BS British Standard reference to a 70 x 70mm b...

Page 8: ... that helps to track room status energy use equipment alarm reporting integration to PMS BMS and other systems It will help user to proactively deliver a rewarding guest experience The e7w Thermostat comes with inbuilt temperature and humidity sensor to measure room temperature and humidity The thermostat sends the collected report to the HVAC controller partner that is physically con nected to th...

Page 9: ...UK stand ard gang Applications requires PC502 4G and X47 Basic Thermostat Traditional HVAC control Basic EMS Optimizes in room energy based on occupancy detection via a built in and or remote motion sensor Advanced EMS Optimizes in room energy based on occupancy detection via a motionsensor and a door sensor or a lock integration Networked EMS Optimizes in room energy by occupancy and room status ...

Page 10: ...Temperature 60 to 85 F 1 F 15 to 30 C 0 5 C Power Input 6VDC Four AA Batteries of 1 5VDC each Output N A Color Variants Ice White and Black Onyx Display resolution High Twisted Nematic HTN LCD 0 5 C 0 1 F in test mode Standard dead band 2 F 1 C between heating and cooling Thermostat Measurement range 33 to 99 F 1 to 37 C 1 8 F Outdoor air temperature display 0 to 99 F 18 to 37 C as reported from w...

Page 11: ...ed Deep Mesh Network 2 4 GHz Approvals EN Product Standard EN 60730 1 2011 and EN 60730 2 9 2010 EMC Standard ETSI 301489 1 V2 2 1 ETSI 301 489 17 V 3 2 0 and EN 55032 UL UL 60730 1 5th edition and UL 60730 2 9 4th edition IEC and EN EMC standards EU RoHs EN 50581 2012 per EU RoHS Directive 2011 65 EU EN 50581 2012 per EU RoHS Directive 2011 65 EU CSA CSA IEC Based Note 1 on standards Note 2 on as...

Page 12: ...ctions Figure 1 System Block Diagram e7w Thermostat Application Distributed Load Application The e7w thermostat is designed to support intelligent distributed load control and actuation This is the primary architecture found in the domestic retrofit and new construction markets In the diagram below the e7w thermostat communicates with the PC502 4G room gateway and other in room devices like MODEVA...

Page 13: ...w Load Center architecture diagram the e7w Thermostat provides the user interface to the guestroom controls but does not directly control the HVAC unit The e7w communicates via RF with PC502 4G room gateway which further communicates with other in room devices The in room devices like MODEVA switch X47 or X47 L P HVAC controller etc communicates via S5 system bus with the PC502 4G For example when...

Page 14: ... server workstations storage servers firewall devices routers and mobile devices 4 Do not use weak passwords for server administrators or operators Different user role for ex ample administrator user guest etc shall have different password and user should not share common passwords 5 It is recommended to change password in every 3 months 6 Keep the EngINN or INNcontrol log for at least 3 months fo...

Page 15: ...a secured by industry standard cryptographic methods 2 To keep maximum integration compatibility with legacy devices in room wired devices are less secure from data confidentiality and authentication thus not recommended for new de sign It is always highly recommended to use deep mesh wireless network communication to gain maximum protection and latest updates 3 In case of Deny of Service attacks ...

Page 16: ...OFF AUTO button and cycling through OFF AUTO HEAT and COOL The e7w thermostat works in conjunction with an HVAC controller partner such as an INNCOM X47 L P X47H P to send room temperature updates temperature change request humidity levels and motion detection Wiring X47 L P 24VAC with e7w Thermostat In the below diagram the e7w Thermostat communicates with the PC502 4G room gate way and other in ...

Page 17: ...DE 11 31 00302 01 Wiring X47 H P 120VAC with e7w Thermostat Below figure shows e7w Thermostat communication with PC502 4G room gateway and other devices like X 47H P 120 VAC HVAC controller via RF Channel Thermostat Wire Connections ...

Page 18: ...er the thermostat will then display the modes heat and cool and the measured temperature e7w Interface Navigation Part Numbers List No Long Description 201 528 6V BK 6V Wireless Thermostat Black Onyx 201 528 6V WH 6V Wireless Thermostat Ice White 201 528 24 BK 24VAC Thermostat Black Onyx 201 528 24 WH 24VAC Thermostat Ice White 201 528 100 BK 100 277VAC Thermostat Black Onyx 201 528 100 WH 100 277...

Page 19: ...nd X47 are required for e7w to interface with HVAC system Display Functions Characters in the display are shown in the below figure for reference The characters will be illuminated in certain combinations to support all the intended applications Whenever the guest views any temperature in Fahrenheit only whole numbers no decimals should be displayed 11 11 5 5 4 4 6 6 9 9 1 1 10 10 8 8 7 7 3 3 Othe...

Page 20: ...ature shown on the display and the measured room temperature Low Medium High Fan Speed Low Medium and High fan speeds are selected by pressing the fan button The fan will run at the selected speed in heating or cooling in order to maintain desired SET tempera ture 4 Heat Mode Heat mode displayed when the thermostat is configured only for heat mode 5 Cool Mode Cool mode display when the thermostat ...

Page 21: ... door balcony or lanai is open 9 Low Battery Alarm The low battery alarm will be displayed on the battery powered models when the batteries need to be replaced 10 Bluetooth The Bluetooth icon is displayed in SERVICE MODE when the Bluetooth transceiver is enabled 11 Equipment Alarm The equipment alarm will be displayed in service mode This can be pro grammed to display for various equipment malfunc...

Page 22: ...s This tool is used in conjunction with Honeywell s EngINN commissioning software when ad vanced commissioning of the e7w is required by a trained and certified INNCOM technician Contact Honeywell technical support for more information NOTE One PC 503 USB Commissioning Tool and USB cable per property or project is shipped to the site DO NOT THROW AWAY OR LOSE THESE UNITS Figure 4 PC 503 USB commis...

Page 23: ... ducts Radiant heat from sun or appliances Concealed pipes or chimneys Unheated un cooled areas behind the thermostat Near other RF sources transmitters to avoid interference When the thermostat is equipped with PIR consider view angle range characteristics and mounting position for proper coverage Figure 5 Recommended mounting location e7w Setup The INNCOM e7w battery operated thermostat can be m...

Page 24: ...Check the battery voltage 6 Hook the tabs at the top rear of the e7w housing into the matching depressions at the top of the Smart Mounting Plate and rotate the bottom of the housing toward the wall until it snaps into place 7 After startup the e7w will cycle through RF Channels 26 25 24 all the way to 11 and send a 0x00061 Battery Powered thermostat exchange message on each RF Channel looking for...

Page 25: ... Reference 1 Battery Compartment Holds 4 AA Alkaline Batteries 2 Insert the 4 AA alkaline batteries matching the terminals on the batteries to the sym bols in the battery compartment as shown in Fig 6 Caution Risk of explosion if other type of battery used Dispose the used batteries as per instructions under WEEE Directive 2012 19 EC ...

Page 26: ...smart wall plate is properly connected If you see SWp on the display most likely the unit is not connected or fitted on the smart wall plate Unscrew the captive screws and re fit the thermostat Once properly connected the dis play will start up as rId Avoid over tightening of screws and irregularity on the wall surface that may lead to an insecure connection between the smart wall plate and thermo...

Page 27: ...Use UP DOWN arrow button to change the value range is 0 6 and press FAN to continue 3 Set the Medium value MED Two fan dots indicate medium value displayed with 55 as a default value Use UP DOWN arrow button to change the value range is 0 99 and press FAN to continue 4 Set the Low value LO Single fan dots indicate low value displayed with 35 as a default value Use UP DOWN arrow button to change th...

Page 28: ...n mode or press F C to return the Initialization Mode Setup PAn ID Figure 9 Setup PAn ID 1 After PAn is displayed press MODE 0 default PAn value displayed 2 Use UP DOWN arrow to change the value ranging from 0 to 255 3 Press FAN the unit beeps to confirm the value stored in the memory and the displays back to PAn 4 Press MODE to check the PAn value 7 Press UP arrow button to display rF mode or pre...

Page 29: ... key for 5 sec 2 Press and release MODE button 3 Press and release FAN button 4 Release F C key This action displays Parameter and rld value on the screen NOTE Then e7w will start searching for other HVAC partner by displaying RF channel 26 25 24 down to 11 if The HVAC partner example X47 has different address other than 14 The RF gateway device example PC502 4G which will communicate between e7w ...

Page 30: ...th its HVAC Partner Address the next step is to use either the e7w or the EngINN software with the PC503 USB commissioning tool to commission the other devices in the room NOTE The e7w can be used as commissioning tool refer applicable commissioning document for exact steps Binding the RF to S5 Gateway Used by the e7w In order for the e7w to communicate with any in room S5 Bus devices the e7w must...

Page 31: ...Binding 6 Press S1 switch on the S541 RF to start binding process On completing of binding device LED flashes light and send a message to make e7w beep confirming that binding of e7w with S541 RF is successful 7 Press F C button twice to exit SERVICE MODE NOTE If an RF Lock Saflok Timelox Salto is installed in each room the lock reports door position The e7w can be used to bind and test the RF Loc...

Page 32: ...ends a 0x000281 Door Open message to the e7w c The device in the room that is the Door Server sends a 0x0002981 Door Server Reports Door Open message to the e7w 4 After receiving 0x0002981 Door Server Reports Door Open message the e7w plays a buzzer sound and increment the displayed door open count 5 The e7w stops the buzzer sound when the opened door is close 6 Press F C button twice to exit SERV...

Page 33: ... verify humidity 0 to 99 rSt Use to reset the thermostat VAL 0 or remote device with specified address or VAL 0 to 255 WAn Use to verify WAN communication Sends an event to the server The server in turn will reply with a command that lets the room ID scroll over the display of the thermostat 0 dor Use to verify Door sensor The buzzer will sound as long as the door is open and the LCD counts the nu...

Page 34: ...2V 4 AA batteries for 1 minute 0 to 255 SEr Use to run menu parameters of the CBL32 partner device e g X47 0 to 255 P5C Use to view or set the P5 Channel of e7w default channel is 1 0 to 7 PA Set P5 partner address This address considers as default address of the HVAC controller partner which is configured with e7w This partner address receives any message sent by e7w 1 to 255 Pi5 Use to read and ...

Page 35: ...an speed dots displays indicating the high digit is displayed Note The five digit number is comprised of three fields high value HI medium value MED low value LO HI MED LO 3 Set the High value HI Three fan dots indicate high value displayed with 06 as a default value Use UP DOWN arrow button to change the value range is 0 6 and press FAN to continue 4 Set the Medium value MED Two fan dots indicate...

Page 36: ...tton to store the new Room ID number scrolling across the display The unit beeps to confirm the value is stored in memory Once the scrolling is completed the screen displays rld Or Press FAN button to toggle between three modes to verify the Room ID 7 Press the F C button to return to SERVICE MODE or press UP arrow button to display next mode Or Press the F C button twice to exit SERVICE MODE Medi...

Page 37: ...stored in the memory display will be back to PAn 6 Press the F C button to return to SERVICE MODE or press UP arrow button to display next mode Or Press the F C button twice to exit SERVICE MODE RF Setting e7w RF Channel rF 1 Enter SERVICE MODE 2 Use the UP DOWN arrow buttons to select rF and then press MODE 3 The current rF channel value is displayed on the screen 4 Use the UP DOWN arrows to set ...

Page 38: ...value Follow the steps below to configure Adr parameter NOTE Before user start configuring ADR mode user need configure Room ID PAN ID and RF Chan nel in the e7w if not already done 1 Enter SERVICE MODE 2 Use the UP DOWN arrow buttons to select Adr 3 Press MODE button This action displays preconfigured Adr address 4 Use the UP DOWN arrow buttons to change Adr value to the desired address 5 Press F...

Page 39: ...e target device into a Bind Ready mode This can be done by pressing any button on the target device two times quickly then press and hold the button for 5 7 seconds b Press MODE button on e7w The e7w send a Forward Bind Request c After receiving the Forward Bind Request the target device flashes LED confirm ing that it receives the Forward Bind Request For binding RF devices press bind button on t...

Page 40: ...onfiguring IO mode you need configure Room ID PAN ID and RF Channel in the e7w 1 Enter SERVICE MODE 2 To prevent setting an unknown address into the target device set Adr value to 0 a Use the UP DOWN arrow buttons to select Adr b Press MODE button to view the value if the displayed value is non zero change the value to zero c Use the UP DOWN arrow buttons to change Adr value to 0 and press FAN but...

Page 41: ... the target device d After the target device receives and accepts the bind offer containing the new I O Map the target device will RESET and send a sound buzzer message to e7w e After receiving the message the e7w beep three times to confirm the binding NOTE For more details refer applicable commissioning document Forward Binding Forward binding is supported by devices such as an L208 RF Evora Mod...

Page 42: ... the bind request For binding Non RF devices press bind button once on the target de vice to accept the bind request d After accepting the new I O Map the target device RESET and send message to e7w to make it sounds its audible buzzer e After receiving the message e7w beep three times to confirm the binding 7 Press the F C button to return SERVICE MODE or press UP arrow button to display next mod...

Page 43: ...ODE This action displays Gr value 4 Use the UP DOWN arrow buttons to change the Gr value to the required CBL32 Group For example Group 9 for Thermostat 9 X registries or Group 7 for 7 X Input Output reg istry s 5 Press the MODE button to continue This action displays the KEY value This is the Regis try Key value 6 Use the UP DOWN arrow buttons to change the KEY value to the required CBL32 Key For ...

Page 44: ...arrow buttons to select the desired 09 YY parameter offset b Press the MODE button to read and display the value if the selected offset The e7w will send a 00018C09YY0000 Read Registry 09 YY Offset value to the HVAC partner If a reply is received the display will show Value and the value of the selected offset in deci mal and the e7w will beep In the below example Parameter 8 of the selected 9 YY ...

Page 45: ...partner to verify the selected Registry 07 YY XX exists If the selected Registry 07 YY XX exists in the HVAC partner the e7w will beep and Pa rameter and 0 will be displayed 1 Use the UP DOWN arrow buttons to select the desired 07 YY XX parameter offset 2 Press the MODE button The e7w will send a 00018C07YYXX00 Read Registry 07 YY XX Offset value If a reply is received the display will change to s...

Page 46: ...on returns to the previous Group Key or Group Key Index level Press the F C button as many times as required to back out to the desired Group Key or Group Key Index For example if currently viewing Registry 9 1 Group 9 Key 1 Parameter 8 value b When the desired level is reached use the Up Down arrow buttons to select the de sired Group Key or Index value then press the MODE button to view the valu...

Page 47: ... Down button to set value to 8 then press MODE Value changed to 15 Current Value is 10 Use Up arrow button to change value to 15 Press FAN button to store the new value Cloud Sun symbol blinks to indicate registry value has been changed Value Value Value Press F C Button 4 times to exit out of rEG menus until Str Store appears on display Use Up Down button to select Gr value then press MODE Use Up...

Page 48: ...14 Press MODE Enter Service Mode and select PA parameter Press MODE to view value 14 Change value to 30 press FAN to store change e7w will beep and return to display PA Value Value Select rE6 parameter and press MODE Change Group value to 7 and press MODE Change Key value to 3 and press MODE Change Index value to 1 and press MODE Parameter and 0 will appear Change Parameter value to 20 and press M...

Page 49: ...value to 14 press FAN to store change e7w will beep and return to display PA Value Value Press F C button to exit back to reG rE6 and press F C again to get Str Store on the display Press FAN button to store the change The e7w will RESET and exit Service Parameter Mode The e7w will RESET and exit out of Service Parameter mode ...

Page 50: ... MODE 2 Press UP DOWN arrow buttons to select PnG 3 Press MODE button This action will display the PnG value and will be 000 by default 4 Use the UP DOWN arrow button to change the displayed value to the P5 address to be pinged For example refer below figure which shows address 227 5 Press the FAN button to start the Ping The e7w will constantly send 4 commands to read the below values from the ta...

Page 51: ...ess the F C button twice to exit SERVICE MODE RH Measuring Room Humidity rH rH parameter is used to read and display measured room humidity via the e7w built in humidity sen sor 1 Enter SERVICE MODE 2 Press UP DOWN arrow buttons to select rH 3 Press MODE button This action display rH value Relative Humidity percentage For example 31 rH is displayed humidity percentage 4 Press the F C button to ret...

Page 52: ...tory default settings 1 240 Address of in room device to Reset The e7w will send a 420 reset command to this P5 address 5 Press the FAN button to execute the Reset 6 Press the F C button to return SERVICE MODE or press UP arrow button to display next mode Or Press the F C button twice to exit SERVICE MODE WAN Verifying Wide Area Network WAn WAn mode is used to verify if the Room Gateway device in ...

Page 53: ...wing are the possible reasons for a WAN test failure No device in the room is configured to be the Room Gwy or the Room Gateway de vice is not powered or configured correctly The edge router or floor bridge the room communicates through which is not powered or is not configured correctly 5 Press the F C button to return SERVICE MODE or press UP arrow button to display next mode Or Press the F C bu...

Page 54: ...buttons to select dor 3 Press MODE button This action displays dor value O is the default dor value displayed Open the room entry door The following sequence should happen The device used for monitoring and reporting entry door position sends a 0x000281 Door open message to the e7w a The device used for reporting entry door position sends a 0x000281 Door open mes sage into the room b The door serv...

Page 55: ...motion sensor is functioning correctly and identify ing good location of the e7w for detecting guest movement in the room 1 Enter SERVICE MODE 2 Press UP DOWN arrow buttons to select Plr 3 Press MODE button This action displays Plr value O00 is the default Plr value displayed Walk sideways in the front of the thermostat so that the PIR motion sensor can detect the occupancy 4 When the PIR sensor d...

Page 56: ...in the guestroom is reporting correctly NOTE To perform window test Following two conditions must be satisfied for window test A device in the room that is monitoring and reporting window position via a 0x0002A1 Win dow Open message A device in the room that has its P5 Window Server enabled that reports a 0x0002B01 Window Server Reports window is Open for the e7w window test to work The e7w watche...

Page 57: ...minute 6 Press the F C button to return SERVICE MODE or press UP arrow button to display next mode Or Press the F C button twice to exit SERVICE MODE BND Binding Auxiliary Devices bnd Use the bnd parameter to open a two minute bind window in a remote device The typical use of this feature is to use the e7w to open the Bind Window in a PC502 4G or Evora RF Lock proxy when bind ing the PC502 Evora a...

Page 58: ...elect the bnd parameter 7 Press MODE button This action displays bnd value 8 Use the UP DOWN arrow buttons to change the value to the Address of the PC502 Evora or device that is the RF lock proxy The e7w will send the Open Bind Window command to this address in Step 9 Refer to the below example A PC502 4G with address 227 is the lock proxy ...

Page 59: ...o the PC502 Evora RF Lock Proxy the PC502 Evora RF Lock Proxy will send 3 sound buzzer requests into the room then and RESET NOTE Any device capable of sounding its buzzer should beep buzz three times 12 Press the F C button to return SERVICE MODE or press UP arrow button to display next mode Or Press the F C button twice to exit SERVICE MODE NOTE For more details refer applicable commissioning do...

Page 60: ... sensor 1 Enter SERVICE MODE 2 Press UP DOWN arrow buttons to select Prr 3 Press MODE button This action displays Prr value Create the motion in view of the remote PIR device The remote PIR device should send a 0x000351 when it senses motion and 0x000350 when the motion stops When the e7w sense the 0x000351 followed by the 0x000350 it will increment the displayed count and a beep to indicate motio...

Page 61: ...a low battery symbol on its display in dicating that the 4 AA batteries need replacement This condition will also result in a low battery alarm in the INNcontrol software Refer below image 1 Enter SERVICE MODE 2 Press UP DOWN arrow buttons to select bAu 3 Press MODE button This action displays bAu value ranging from 0 255 bAu Voltage VDC 255 6 4 239 6 0 199 5 0 159 4 0 119 3 0 Table 1 Voltage tabl...

Page 62: ...ed Run Param eter value listed in Parameter column in Table 1 5 Press the MODE button to view the value to use Use the UP DOWN arrow buttons to se lect the desired value 6 Press the FAN button to execute The e7w will send a 0019100XX00YY command to the address of its HVAC partner XX Run Parameter defined in Step 5 in Hex YY Value defined in step 5 that the selected Run parameter will execute in He...

Page 63: ...Menu 10 with value 5 7 Press the F C button to return SERVICE MODE or press UP arrow button to display next mode Or Press the F C button twice to exit SERVICE MODE Table 2 Run Parameter Value Value Value Change the desired Run Parameter value to 10 using the Up Down buttons Press MODE Change value to 5 using Up Arrow Press FAN button to execute ...

Page 64: ...alue ranging from 1 7 4 Use the UP DOWN arrow buttons to change the P5c value 5 Press the FAN button to store the value The e7w play beep sound 6 Press the F C button to return SERVICE MODE or press UP arrow button to display next mode Or Press the F C button twice to exit SERVICE MODE PA PA Partner Address Parameter PA Use PA mode to set default address used by the HVAC partner of the e7w Any mes...

Page 65: ... SERVICE MODE or press UP arrow button to display next mode Or Press the F C button twice to exit SERVICE MODE PI5 Process Image Viewer Parameter Pi5 Use Pi5 mode to read any Process Image PI offset value 0 31 from the HVAC partner device The Pi5 Process Image viewer is an advanced feature intended to be used by an INNCOM technician for ad vanced troubleshooting 1 Enter SERVICE MODE 2 Press UP DOW...

Page 66: ...hed 5 Press the FAN button to execute The e7w sends a 0010000XX XX E0 FF read Process image offset read command to its defined HVAC partner address If a reply value is received from the HVAC partner the Pi5 value is displayed in decimal for mat 6 If no reply is received the selected PI Offset value remains and a warning triangle icon is displayed 7 Press the F C button to return SERVICE MODE or pr...

Page 67: ... E7W value 7 Press the FAN button to store the value The e7w play beep sound 8 Press the F C button to return SERVICE MODE or press UP arrow button to display next mode Or Press the F C button twice to exit SERVICE MODE OAT Outside Air Temperature Parameter oAt Use the OAT menu to Enable or Disable the ability of the e7w to display outside air temperature When the e7w is configured to display outs...

Page 68: ...N button to store the change The e7w will beep and return to the main OAT menu 4 Press the F C button to return SERVICE MODE or press UP arrow button to display next mode 5 With OAT enabled anytime the e7w enters dormant mode the measured outside temper ature will be displayed above the target temperature 6 To disable the displaying outside air temperature on the e7w when in dormant mode re peat a...

Page 69: ...ter 3 PIR sensor detections occur 4 Report detected motion only after 5 PIR sensor detections occur Use the UP DOWN arrow buttons to select the desired value 4 Press the FAN button to store the change The e7w will beep 5 Press the F C button to return SERVICE MODE or press UP arrow button to display next mode Or Press the F C button twice to exit SERVICE MODE CTR Contractor Mode Parameter Ctr Cont...

Page 70: ...ained by the e7w while in contractor mode 5 Press FAN to continue The display scrolls the set temperature and the unit beeps to confirm the set value 6 Press the F C button twice to exit SERVICE MODE The unit displays the target measured temperature and an alert icon to indicate Contrac tor mode is active After 5 seconds just the locked target temperature and the alert icon will be displayed ...

Page 71: ...ge these values are locked out To exit CONTRACTOR MODE 1 Enter SERVICE MODE 2 Press UP DOWN arrow buttons to select Ctr 3 Press MODE button This action displays and Value 4 Press FAN button to turn off CONTRACTOR MODE After turning off CONTRACTOR MODE e7w play beep sound 5 Press the F C button twice to exit SERVICE MODE The alert icon should clear ...

Page 72: ...pened or closed 3 Enter service parameter mode on the e7w 4 Set the desired Room ID RF Channel and PAN ID into the e7w that the particular Inncom Proxy Room Gateway typically a PC502 4G and lock should be using for the particular room 5 On the e7w go to the Adr Address Teach parameter and press Mode to view the value Change the displayed value to 67 then press the Fan button Bnd will appear on the...

Page 73: ...et the value to the address of the device being used as the Timelox RF Lock Proxy This will typically be a PC502 address 227 if using an e7w How ever consult applicable documentation 7 Press the Fan button on the e7w to make it sends a 0x00113 Open Bind Window command to the address defined in step 6 The PC502 will open a 2 minute bind window waiting to see a bind request from the lock 8 Hold the ...

Page 74: ...This will typically be a PC502 Address 227 if using an e7w However consult applicable documentation 7 Press the Fan button on the e7w to make it send a 0x00113 Open Bind Window command to the address defined in step 6 The PC502 will open a 2 minute bind window waiting to see a bind request from the lock 8 On the Salto handheld PPD Tool select Update Locks from the PPD menu and insert the 3 pin cab...

Page 75: ...e firmware Follow the steps below to upgrade e7w firmware 1 Open EngINN tool and click Select File to load the new firmware file 2 Click Connect button EngINN tool opens the COM port with baud rate 115200 EngINN sends Start OTW command to the device and get ready for ECDH negotiation pro cess 3 The device receives the Start OTW command and start the ECDH negotiation process When the process finish...

Page 76: ...pletes upgrade After all of the selected firmware is updated EngINN tool sends End OTW command to the e7w to indicate that the OTW process is finished After receiving the End OTW command the e7w reply an acknowledgement to EngINN and restart After the EngINN receives the acknowledgement it displays firmware update success ...

Page 77: ...he content and the product described are subject to change without notice Honeywell makes no representations or warranties with respect to this document In no event shall Honeywell be liable for technical or editorial omissions or mistakes in this document nor shall it be liable for any damages direct or incidental arising out of or related to the use of this document No part of this document may ...

Reviews: