INNCOM e7w THERMOSTAT USER GUIDE
31-00302-01
46
RST
–
Resetting e7w (
rSt
)
rSt
parameter is used to reset the e7w, reboot the e7w back to Factory default settings or Reset a
remote device.
1.
Enter
SERVICE MODE
2.
Press
UP/DOWN
arrow buttons to select
rSt
.
3.
Press
MODE
button. This action displays default value 0.
4.
Press
UP/DOWN
button to the select the reset value.
For reset value, refer below table:
0
Reset the e7w
255
Reboot the e7w back to factory default settings
1-240
Address of in-room device to Reset. The e7w will send a 420 reset command
to this P5 address
5.
Press the
FAN
button to execute the Reset.
6.
Press the
F
C
button to return
SERVICE MODE
or press
UP
arrow button to display
next mode.
Or
Press the
F
C
button twice to exit
SERVICE MODE.
WAN
–
Verifying Wide Area Network (
WAn
)
WAn
mode is used to verify, if the Room Gateway device in the room is connected to the INNCOM
Server via its associated B574/B578 Edge Router or B576 Floor Bridge.
NOTE:
This test mode only applies to a network or online installation
1.
Enter
SERVICE MODE
2.
Press
UP/DOWN
arrow buttons to select
WAn
.