INNCOM e7w THERMOSTAT USER GUIDE
25
31-00302-01
7.
Press
F
C
button
twice to exit
SERVICE MODE
.
NOTE:
For more details
,
refer applicable commissioning document.
Binding S541.RF Door, Window or Balcony Switches
To communicate with any in-room RF devices like an S541.RF Door, Window or Balcony switches.
Follow the steps below to binding the S541.RF Door Switch reporting device using the e7w.
1.
Enter
SERVICE MODE
on the e7w.
2.
Press
UP/DOWN
arrow button to select
Io.
3.
Press
MODE
button. This action displays
Io
value.
Following are the Default I/O values:
i )
0 – Default I/O map value for Entry Door.
i i )
2 – Default I/O map value for Window or Balcony Door.
4.
Press
UP/DOWN
arrow button
to change
Io
value range from 0 to 255, set Io value to the
required
I/O
map number.
5.
Press
FAN
button. This action displays “
bnd
” to initiate a Reverse Binding.
6.
Press
S1
switch on the S541.RF to start binding process.
On completing of binding, device LED flashes light and send a message to make e7w beep,
confirming that binding of e7w with S541.RF is successful.
7.
Press
F
C
button
twice to exit
SERVICE MODE
.
NOTE:
If an RF Lock (Saflok, Timelox, Salto) is installed in each room, the lock reports door position. The
e7w can be used to bind and test the RF Lock. Refer
Binding and Testing RF Locks Using e7w
Verifying In-Room Installed Devices
User can verify the communication of all the non-battery powered devices installed in the room by
pinging the device from the e7w.
Follow the steps below to verify:
1.
Enter
SERVICE MODE
on the e7w.
2.
Press
UP/DOWN
arrow button to select
PnG.
3.
Press
MODE
button. This action displays
PnG
value.
4.
Press
UP/DOWN
arrow button
to select target device address (select the correct target that
need be pinged by e7w).
NOTE
: Refer applicable document, to check the list of supported devices and their address.
5.
Press
FAN
to start pinging the target device.