HONEYWELL IDENTIPOINT™ INTELLIGENT SMARTCARD SYSTEM
95-7767
26
DETAILED WIRING DIAGRAMS
Single Reader with REX and without IOM
Fig. 21. Connections for single reader with REX and without IOM
In the above configuration, one IdentIPoint reader operates in
stand-alone mode to control door access. It authenticates
users as well as releases the door lock using its relay contact.
Minimum Connections:
1.
Connect the Ethernet/PoE cable to the RJ45 port of the
reader through the CAT5 pigtail. (Frame-GND connec-
tion to building GROUND Earth is recommended for
better electro-static discharge resilience.) See Fig.7.
2.
If PoE switch is not used, connect a 12-24VDC power
supply to pins 1-2 (Power-IN - Power-GND) of port J9 of
the reader. See section
Wire the Readers
and
IOM of
Wiring the Readers and IOM
topic for details on power
supply connections.
3.
Connect pin(s) 3/4/5 (Relay-C/Relay-NC/Relay-NO) of
port J9 to the door lock depending on the type of lock
(magnetic lock or door strike) used and the safety codes
to be followed. Also connect a power line to the lock.
See
Wiring Other Devices
topic for detailed wiring of
locks.
4.
Connect pins 6-7 (SAI-0 - SAI-0-GND) and 8-9 (SAI-1 -
SAI-1-GND) to a Request-to-Exit (REX) switch and door
sensor with proper termination circuit as described in
section
Supervisory Analog Input (SAI) termination cir-
cuit
of
Wiring Other Devices
topic. An additional sensor
can be connected to SAI-2 of port J10.
To Door Sensor
Power-OUT
SAI-1-GND
Power-GND
SAI-1
8
2
9
1
J10
PIN
PIN
J9
To LAN
Ethernet
2KΩ
1KΩ
DC – Power
2KΩ
1KΩ
2
8
3
RS485-A
SAI-0-GND
7
4
RS485-B
SAI-0
6
5
RS485-GND
5
O
N
-
y
a
l
e
R
6
DO
Relay-NC
4
7
DOGnd
Relay-C
3
SAI-2
Power-GND
To Door Lock
To REX Switch
DC Power
12 to 24V
If PoE is not used.
1
9
2
8
SAI 2
Power GND
SAI-2-GND
Power-IN
Frame-GND
10
To electrical
earth.
If unavailable,
connect to
Power-GND.
S1
IdentIPoint Reader
Power – Min. 18 AWG
Power Gnd – Min. 18 AWG
Ethernet – CAT5
Signal/Power – Min. 18 AWG
Signal – Min 18 AWG
LEGEND
Signal
Min. 18 AWG
Signal – Min. 18 AWG