HM700A1000
33-00118—01
4
Fig. 2. Typical HM700 Installation.
SIZING
IMPORTANT
The HM700 should only be installed if it has been
sized properly.
Do not use square feet when sizing
a humidifier installation.
Instead, cubic feet must
be used, since the humidity is filling a volume of
space (width x length x height). Also, take into
consideration the “tightness” of a home’s
construction.
The HM700 produces 11 gallons per day (GPD) when run on
120 V and 22 GPD when run on 240 V. See Figures 15 for
details on configuring the HM700 to run on a different voltage.
Table 3 contains AHRI recommendations for humidity
requirements and Table 4 shows what humidifiers and output
configuration will satisfy the humidification requirements.
Table 3. AHRI Recommended Humidity (in gallons per day).
(Optional)
1
- R/HUM
2
- HUM
3
- C
4
- N/A
8
- AP
19
- Gf
20
- Rf
21
- N/A
1/8 NPT to
1/4 compression
or LDPE water
line
Construction
Type
8,000 ft
3
12,000 ft
3
16,000 ft
3
20,000 ft
3
24,000 ft
3
28,000 ft
3
32,000 ft
3
Tight
3.3
4.3
5.4
7.5
9.6
11.7
16
Average
7.6
9.6
11.8
16
20.3
24.4
33
Loose
11.7
14.9
18.1
24.5
30.8
37.1
50