background image

HM700A1000

13

33-00118—01

Start Up Procedure

1.

Examine the humidifier and installation for damage 

and/or improper installation.

2.

Ensure the cylinder is properly seated in the drain valve 

and that the electrode plugs are pushed all the way 

down on the cylinder pins.

3.

Ensure that the front cover is in place and secured with 

its retaining screws.

4.

Open the supply water shut off valve.

5.

Turn on the main power using the installed disconnect.

WARNING

Personal Injury Hazard.

Damaged or improperly installed units must not be 

operated. Damaged or improperly installed units may 

present a danger to persons and property.

6.

Turn the On/Off switch on the front of the humidifier to 

On.

• The humidifier will perform a self-diagnostic 

sequence during which the LED’s and internal 

components will be momentarily activated. See 

“LED Status Lights” on page 14 for an explanation 

of the LEDs and sequences.

• If an error is detected during the self-diagnostic 

sequence the humidifier will not start. The yellow 

status LED will flash in sequence to indicate the 

detected fault. See Tables 7 and 8 for information 

on diagnosing and correcting faults.

• After the system test the humidifier is in normal 

operation mode.

7.

Check and adjust the control setpoint on the control and 

high limit humidistat.

8.

When the external humidistat generates a demand for 

humidity and the security loop is closed the green 

humidifying LED on the front of the humidifier will light 

up, the power relay on the control board will engage, the 

fill valve will activate (after a delay) and the cylinder will 

slowly fill with water.

NOTE: While the cylinder is filling with water there 

should be no water flowing down the drain. If 

water is flowing down the drain it can indicate 

excessive backpressure or a leaking drain valve. 

See Troubleshooting.

9.

If a fan enable relay is used, the green LED will continue 

to flash until the air proving closes. Once the air closes, 

the flashing green LED will become solid and the 

humidifier will start steam production as described in 

step 8.

10.

It can take 5 – 10 minutes for the water to be heated up 

by the submerged electrodes and for steam to be pro-

duced.

NOTE: If operated on low conductivity water it may take 

several hours for the HM700 to reach full output 

capacity. This is normal. During this time the 

humidifier will not perform any drains and the 

conductivity of the water in the cylinder will 

increase. To expedite this process, add a 

1/4 teaspoon of salt to the cylinder. This will 

immediately increase water conductivity and 

initiate heating.

Summary of Contents for HM700A1000

Page 1: ...tions without the need to change its configuration NOTE Because the humidifier is factory configured for optimal performance Honeywell strongly discourages changes to the jumpers or the potentiometer doing so will void the warranty and could damage the humidifier Contact Honeywell Customer Care for further information Before Installation 1 Ensure that available voltage and phase corresponds with h...

Page 2: ...he HM700 produces steam at atmospheric pressure No devices which could block steam output should be connected to the steam outlet Steam lines must be installed so that no restriction can produce backpressure in the humidifier CAUTION Water quality The Honeywell HM700 requires a cold water connection from your home s main water supply between 30 100 PSIG A throttle valve may be necessary and a wate...

Page 3: ...er will automatically fill to a higher water level to maintain full capacity during the life of the cylinder Eventually because of scale formation it will no longer be possible for the humidifier to reach its full capacity The HM700 software monitors this condition and when detected will stop operating and flash the yellow LED in a repeating sequence of 4 flashes DRAINS As steam is produced minera...

Page 4: ...d 22 GPD when run on 240 V See Figures 15 for details on configuring the HM700 to run on a different voltage Table 3 contains AHRI recommendations for humidity requirements and Table 4 shows what humidifiers and output configuration will satisfy the humidification requirements Table 3 AHRI Recommended Humidity in gallons per day Optional 1 R HUM 2 HUM 3 C 4 N A 8 AP 19 Gf 20 Rf 21 N A 1 8 NPT to 1...

Page 5: ...for servicing NOTE Do not mount on hot surfaces where freezing can occur vibrating surface or floor Mounting with Keyholes 1 The HM700 humidifier is wall mounted using a keyhole located on the back of the unit cabinetry 2 Use 8 x 2 in 5 cm screws mounted into 2x4 studs or better 2 screws are needed one for hanging the unit and one for securing so it will not lift off the keyhole 3 Install the top ...

Page 6: ... ºF 1 to 20 ºC Install water shut off valve before humidifier to facilitate servicing The drain line should not end in a sink used frequently by personnel or where plumbing codes prohibit it Route to a floor drain or equivalent for safety reasons Ensure drain line is adequately sized to provide free and easy draining and that an air gap is installed as shown A restricted drain can cause cylinder w...

Page 7: ... Fig 6 Fig 7 Distributor installed horizontally in a horizontal duct Fig 8 Distributor installed horizontally in a vertical duct Rotate the distributor 45º so that steam is discharged toward the center of duct in the direction of the air flow Fig 9 Distributor installed vertically in a horizontal duct This configuration is not recommended Part Number Description Notes HM700ADISTKIT Stainless Steel...

Page 8: ...er the copper tube Fasten in place with the spring clamp Fig 10 Condensate return MAIN RULES FOR ATMOSPHERIC STEAM LINES Steam lines must not have any restrictions which could result in back pressure Follow recommended materials size and length see tables Install steam line in a vertical upwards fashion from the HM700 to the distribution nozzle Consult Figures 11 13 for other installation options ...

Page 9: ...305 MINIMUM RADIUS CONDENSATE LINE SUPPORT BRACKETS 12 305 2 51 MINIMUM CONNECT STEAM HOSE TO CYLINDER CONDENSATE LINE 12 305 MINIMUM M35718 SUPPORT BRACKETS CONDENSATE TRAP TO DRAIN 12 305 MINIMUM RADIUS 12 305 MINIMUM BEFORE ANY BEND M35719 TO DRAIN OBSTRUCTION 12 305 MINIMUM 12 305 MINIMUM RADIUS 12 305 MINIMUM BEFORE ANY BEND SUPPORT BRACKETS USE FULL SIZE CONDENSATE TEE AT LOW POINT SLOPE LIN...

Page 10: ...possible and remove excess Fig 15 Primary power connection NOTES Honeywell requires the use of a GFI circuit on this device to protect the homeowner from electrical shock When installed correctly the green wire should be removed from the drain valve The green wire comes pre installed from the factory to protect the homeowner in case of an improper installation or when it is not possible to retrofi...

Page 11: ...idity drafts doorways sunlight or an overhang such as a shelf can affect reading Optional Outdoor Temperature Sensor not shown included with HumidPRO Mount outside in area representing air temperature Fig 16 Wiring the steam humidifier with a digital thermostat Fig 17 Wiring the steam humidifier with a mechanical thermostat NOTE If a Prestige VisionPRO Lyric or similar are used to control humidity...

Page 12: ...ugh an On Off humidistat and other security devices in series Fused Disconnect Correct voltage amps phase per spec label optional Mounting Unit level Screws into structural member Steam Line Adequate slope No restrictions No kinks in hose Condensate traps on long runs High Limit On Off optional In series between terminals 1 and 2 Jumper between terminals 1 and 8 must be removed Note U or HUM termi...

Page 13: ...is in normal operation mode 7 Check and adjust the control setpoint on the control and high limit humidistat 8 When the external humidistat generates a demand for humidity and the security loop is closed the green humidifying LED on the front of the humidifier will light up the power relay on the control board will engage the fill valve will activate after a delay and the cylinder will slowly fill...

Page 14: ... action Green LED On Indicates steam is being produced Selecting a Relative Humidity Setpoint The optimum humidity setpoint depends on the reasons that a space is being humidified The ASHRAE Handbook HVAC Applications recommends specific design relative humidity for specific applications Health and Comfort The benefit of humidity is most pronounced for health and comfort in the 40 60 range A humid...

Page 15: ...er components Steam Outlet Condensate Return Fill Cup Drain Valve Drain Canal Fill Valve Cylinder Cylinder Plug High Water Sensor Plug On Off Drain Switch Control Board Power Relay High Voltage Terminal Block Transformer Control Terminal Strip ...

Page 16: ...s input and output connections to humidifier components Fill Cup Provides an air gap for backflow prevention Fill Valve Controls flow of water into humidifier High Voltage Terminal Block Primary power connection from remote disconnect to humidifier High Water sensor Plug Used to detect max water level in cylinder On Off Drain Switch Turns power on off to humidifier controller and drains the cylind...

Page 17: ... not responsible for any damages resulting from or attributed to the failure to replace a spent cylinder see Manufacturer s Warranty NOTE Honeywell recommends keeping a replacement cylinder in stock throughout the humidification season This will prevent possible downtime when the humidifier reports cylinder end of life REPLACEMENT CYLINDER The label on the existing cylinder identifies the cylinder...

Page 18: ...ith the external discon nect 5 Remove the two screws securing the front cover 6 Remove the cylinder plugs from the cylinder pins by pulling vertically 7 Using a flat screwdriver loosen the hose clamp where the hose is connected to the cylinder 8 Tip the top of the cylinder forward to pivot it out of the steam hose When free of steam hose lift the cylinder out NOTE The HM700 has a re usable tie str...

Page 19: ... end of hose and reattach to valve Slide hose clamp back in place and place valve into drain pan 9 Secure valve with 2 screws to drain pan Fig 23 Drain valve Fig 24 Drain valve actuator assembly Installing the New Cylinder CAUTION Make sure the new cylinder is a HM700ACYL2 Use of any other model or remanufactured cylinders will void the HM700 warranty 1 Insert cylinder into drain valve Tilt cylind...

Page 20: ...ty for an extended period of time This feature will reduce or prevent the possibility of corrosion of the electrodes and the accumulation of algae and bacteria growing in the cylinder The cylinder will remain empty until there is a call for humidity at which time the fill valve will open and refill the cylinder The unit will go through its normal process for optimum operation STARTING AFTER EXTEND...

Page 21: ...to the manuals that were provided with the auxiliary equipment and to Table 8 Troubleshooting HM700 Faults on page 23 Table 7 General troubleshooting Symptom Cause Corrective Action s Nothing happens when On Off switch is turned on Fuse blown Check inline fuse between transformer and control board Incorrect Voltage Check voltage against spec label and correct Step Down Transformer not outputting 2...

Page 22: ...quired Incorrect steam line installation Check that steam line has been installed with condensate traps and slope See Steam Lines and Condensate Return Instructions on page 8 Condensation in duct Installation clearances not observed Refer to distributor installation manual for required clearances Relocate distributor if required Design conditions changed Check supply air temperature and humidity t...

Page 23: ...ing down the potentiometer Wrong cylinder installed Install correct cylinder model Cylinder Spent but not detected by software Replace the cylinder see maintenance chapter Condensate from other source Remove condensate returns other than from steam line Back pressure Eliminate back pressure 2 flashes No Current Fill valve activated for long time but high water level not reached Fill should be fast...

Page 24: ... R HUM AP GF RF C HUM N A N A 120 L1 EXTERNAL INTERNAL 240 P ON OFF DRAIN SWITCH TRANSFORMER N A 120 L1 240 P S STATUS LAMPS G Y NOTE INSTALL JUMPER FROM PTO TERMINAL CORRESPONDING TO MAINS VOLTAGE HOT NEUTRAL GROUND HOT HOT GROUND 240 VAC 120 VAC NOTE DRY POINTS FOR FURNACE FAN ENABLE 24 V PILOT CONTROL ONLY N A FACTORY INSTALLED TERMINAL HUMIDITY CONTROL 24V HUM CALL M35721 ...

Page 25: ...consumer Honeywell s sole responsibility shall be to repair or replace the product within the terms stated above HONEYWELL SHALL NOT BE LIABLE FOR ANY LOSS OR DAMAGE OF ANY KIND INCLUDING ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES RESULTING DIRECTLY OR INDIRECTLY FROM ANY BREACH OF ANY WARRANTY EXPRESS OR IMPLIED OR ANY OTHER FAILURE OF THIS PRODUCT Some states do not allow the exclusion or limitatio...

Page 26: ...HM700A1000 33 00118 01 26 ...

Page 27: ...HM700A1000 27 33 00118 01 ...

Page 28: ...nd Control Solutions Honeywell International Inc 1985 Douglas Drive North Golden Valley MN 55422 customer honeywell com U S Registered Trademark 2015 Honeywell International Inc 33 00118 01 M S 11 15 Printed in United States ...

Reviews: