HCL-1PH
User’s
Manual
29
13.4
Hardware Menu
HArd
•
Push simultaneously
L/R
and
F
for few seconds to
access
to the menu (
Nenu
flashing).
•
Select by arrows
UP
and
DOWN :
Hard
then press
F.
•
Select by arrows
UP
and
DOWN :
5
as password
then press
F.
•
You have access to the parameter on
Hard
menu.
•
Select by arrows
UP
and
DOWN
the required parameter.
•
If the parameter is
Write/Read (W/R)
press
F
(parameter flashing) then select by
arrows
UP
and
DOWN
the required velue, press
F
to set the new value.
•
Push simultaneously
L/R
and
F
for few seconds to
Exit
from the menu
Set Analog input Value:
Parameter
Display
Parameter
Name
Contents
UM
Default
Value
UM
Min
Value
DEC
Max
Value
DEC
Min
Value
UM
Max
Value
UM
Par.
Type
Α_1ν
A_1n Input
type V 3
*
0 255 0 255
R/W
Set Minimum input1 value:
Parameter
Display
Parameter
Name
Contents
UM
Default
Value
UM
Min
Value
DEC
Max
Value
DEC
Min
Value
UM
Max
Value
UM
Par.
Type
ΛιΑ1
L A1
Save value
Minimum
input 1
Sw 0 0 1 0 1
R/W
Set Maximum input1 value:
Parameter
Display
Parameter
Name
Contents
UM
Default
Value
UM
Min
Value
DEC
Max
Value
DEC
Min
Value
UM
Max
Value
UM
Par.
Type
ΗιΑ1
HiA1
Save value
Maximum
input 1
Sw 0 0 1 0 1
R/W
Sample Values and Note
1 = 0-10 Vdc / 10Kpot
0_10
2 = 4-20 mA
4_20
3= 0-20 mA
0_20
Sample Values and Note
Default Value
δεΦ
Save Value
ΣΑυε
Sample Values and Note
Default Value
δεΦ
Save Value
ΣΑυε