GREEN CLASS METER
18
62-0340-01
METER TECHNICAL SPECIFICATIONS
Part number configuration
Green Class sub meter
Pulse
Voltage
Current
SUBG
208: 208 Volts
100: 100 Amps
P: Pulse
480: 480 Volts
200: 200 Amps
600: 600 Volts
400: 400 Amps
800: 800 Amps
1600: 1600 Amps
3200: 3200 Amps
Input Voltage Configuration:
3-Wire (Delta) or 4-Wire (Wye)
MAINS Voltage Input:
Up to 480 VAC RMS Available
Input
Power:
6VA
Maximum
Rating
Current Sensor Rating:
Up to 3200 Amp RMS AC Available
Power
Factor:
.5
leading
or
lagging
Line
Frequency:
50-60
Hz
Metering Accuracy:
Certified to ANSI C12.16 (+/- 1% from 1% to 100% of rated load)
Voltage Operating Range:
+/- 10% of rated load
Temperature Range (Standard indoor enclosure):
-20 degrees C to +50 degrees C
Temperature Range: (NEMA 4X outdoor enclosure):
-20 degrees C to +70 degrees C
Relative
Humidity
Range:
0-95%
Non-Condensing
Altitude:
2000
meters
maximum
Voltage Overload:
+25% Continuously; +100% for 20 Cycles
Current Sensor Overload:
100% for 1 minute without damaging meter
Pollution Degree:
Degree 2 in accordance with IEC 664
Installation (Overvoltage) Category:
Category III
Measurement
Category:
Category
III
Indoor Housing Rating (Standard):
NEMA 12
Outdoor Housing Rating (Optional):
NEMA 4X
Display Readout:
KWh Accumulated, cost to date, Instantaneous kW, projected
hourly cost, total CO2 emissions, projected hourly CO2
emissions
Standard Ranges:
4-Wire Wye, 120/208 VAC:
100, 200, 400, 800, 1600 and 3200 Amp
2 Phase, 120/240 VAC:
100, 200, 400, 800, 1600 and 3200 Amp
4-Wire Wye, 277/480 VAC:
100, 200, 400, 800, 1600 and 3200 Amp
3-Wire Delta, 220/240 VAC:
100, 200, 400, 800, 1600 and 3200 Amp
3-Wire Delta, 480 VAC:
100, 200, 400, 800, 1600 and 3200 Amp
IDR Interface Port:
Cable Specificatons:
UL Listed/Rated Telephone Cord, 6-conductor
300
VAC,
stranded
conductors,
22-26
AWG.
Input/Output Voltage:
+5 VDC/18 VAC
Cable
Connector:
RJ-45
male
IDC
Ckt Input Isolation:
5.3K VAC for 1 Minute
Ckt
Output
Isolation:
2.5K
VAC
Isolated Pulse/Alarm Outputs (TB5, TB6):
Output Voltage Potential:
0 VDC to +5 VDC Logic Levels
Mating Plug Connector:
Weidmuller PN: 152876
Signal Isolation Voltage:
5.3K VAC for 1 Minute
Recommended in-Line Fuse:
Manufacturer:
Littlefuse
Mfg
Part
No.:
KLDR.100
Rating:
100mA,
Time
Delay,
600
VAC
Cartridge
Fuse