![Honeywell Green Class meter Installation Instructions Manual Download Page 14](http://html.mh-extra.com/html/honeywell/green-class-meter/green-class-meter_installation-instructions-manual_151843014.webp)
GREEN CLASS METER
14
62-0340-01
KWh Meter Hardware Functions
Hardware
Function
AMR Jack
8-pin RJ-45-used to connect kWh meter to the Honeywell Energy automatic meter reading system.
Peripheral Jack
6-pin RJ-11-used to interface with Honeywell meter options such as the P2 Pulser or D/A Converter.
Check Sensor LED
When lit, indicates that the current sensor is backwards or on the incorrect phase.
Meter Pulse LED
Blinks to show the meter load. Blink rate increases with load.
Power On LED
When lit, indicates power to meter is on.
Reset PB
Press (RESET) to reset display to zero.
Display Test PB
Press (CPU) to test display. Shows “88888888” then amp rating of meter.
DIP Switch
Meter set-up. Used ONLY by Honeywell factory personnel.
CPU Active LED
One blink per second indicates normal operation.
Standard Confi guration
ST Confi guration
Meter
Terminal Block
Check Sensor LED
Meter Pulse LED
Power ON LED
AMR Jack Peripheral Jack
Power On LED AMR Jack Peripheral Jack
Fig. 3. Main circuit board located inside meter enclosure.