Programming
Master Programming Level
Ademco Contact ID Format - Secondary Central Station Phone Number
The information shown in Table 3.5 is automatically programmed for the Secondary Central Station phone number Event Codes when
Ademco Contact ID Format is selected. To disable event reporting, select the desired Event Code to be disabled and press
0
or
Clear
and
then
Enter
to disable it. (
Enter
must be pressed to save the selection. Pressing
Escape
will not save the selection).
Event Description
Event Code Settings
Active
Secondary # Zone 1 - 10 Alarm
115
Secondary # Zone 1 - 10 Disabled
570
Secondary # Drill
604
Secondary # AC Fault
301
Secondary # Zone 1 - 10 Fault
380
Secondary # Zone 1 - 10 Dirty
380
Secondary # Earth Fault
310
Secondary # Low Battery Fault
302
Secondary # No Battery Fault
311
Secondary # Telco Primary Line Fault
351
Secondary # Telco Secondary Line Fault
352
Secondary # NAC #1 Fault
321
Secondary # NAC #2 Fault
322
Secondary # NAC #3 Fault
326
Secondary # NAC #4 Fault
327
Secondary # NAC #1 Disable
521
Secondary # NAC #2 Disable
522
Secondary # NAC #3 Disable
526
Secondary # NAC #4 Disable
527
Secondary # Charger Fault
300
Secondary # Comm Trouble Primary #
354
Secondary # Comm Trouble Secondary #
354
Secondary # Printer Fault
336
Secondary # ANN-BUS Fault
330
Secondary # Option Card Fault
333
Secondary # CS CALC Fault
304
Secondary # System Off Normal
308
Secondary # System Test Message
602
Secondary # System Abnormal Test Message
608
Secondary # Upload/Download Request
411
Secondary # Upload Successful
416
Secondary # Download Successful
412
Secondary # Upload/Download Failed
413
Secondary # Voice EVAC Fault
330
Secondary # Power Supply Sync fault
300
Table 3.5 Ademco Contact ID Secondary # Event Codes
76
GF505 & GF510 Manual —
P/N
53164
:B5 6/12/2018