Installation
ANN-BUS Devices
GFANN-LED Board Layout and Connection to FACP
Figure 2.23 illustrates the GFANN-LED board wiring connections to the FACP.
2.8.5 GFANN-RLY Relay Module
The GFANN-RLY relay module provides 10 programmable Form-C relays when used with a compatible FACP.
Specifications
•
Operating Voltage: 24 VDC
•
Max. Current:
Alarm: 75 mA
Standby: 15 mA
•
Relay Contact Ratings:
2 amps @ 30 VDC (resistive)
0.5 amps @ 30 VAC (resistive)
•
Operating Temperature: 32
o
F to 120
o
F (0
o
C to 49
o
C)
•
For indoor use in a dry location only
Figure 2.23 GFANN-LED Board Layout and Connection to FACP
FACP
GFANN-LED
Primary ANN-BUS
+24 VDC
-24 VDC
ANN-BUS (ID#)
Address DIP switch
TB3
ann
le
dt
o5
x.w
m
f
40
GF505 & GF510 Manual —
P/N
53164
:B5 6/12/2018