background image

4188-1075 issue 3_Part 2_08/14

4

Loop Loading

Loop Cable length

The loop cable length is de

fi

 ned as the sum of the length of cable used on the main loop plus that used on all the spur circuits off 

the main loop having system devices.
 

Loop device load and length calculations for 2Km loop card  

The loop device load can be up to 200 devices and the Loop Cable length can be up to 2Km when using Loop Card (VIG-LPC-EN 
or COMPACT-LPC-EN), where both device count and cable length are dictated by the number of alarm devices on the loop and 
how they are positioned, distributed or lumped together.  

Calculations to determine the Total alarm current

To determine the loop cable length and the number of devices that can be connected on up to 2Km loop the alarm current taken by 
each device is required. So 

fi

 rst calculate the 

total alarm current

 using 

Table 1

. Then use 

Table 2

 or 

3 / 4 or 5

 to trade between 

the loop cable length and device count for lumped alarm device load. 

 

To calculate the ‘Total Alarm Current’:

1. Enter in Table 1 column 

 the total number of each device type on a loop.

2. Multiply columns 

 x 

 to determine the alarm current for each device type.

3. Sum up all device type’s alarm current to 

fi

 nd out the 

total alarm current

 

A

Table 1 - Total Alarm Current

Note some of the values in the table below may not be exactly the same as those in the Battery Standby and 
Loop Load Calculator tool. The values are being used here as a rough guide to determine the total alarm 
current.

 

Device part 
number

Description

V

AD POWER

Maximum 
limit 
per loop

No. of 

Devices 
on loop

 Alarm 

current (mA)
per device

Alarm 
current 

 x 

VIG-RPT-72

Repeat panel 

4

______ x 1.20

VIG-MIM-A3

A3 Zonal/Mimic panel

4

______ x 1.20

S4-720

Heat Sensor

200

______ x 0.20

S4-710

Optical Heat Sensor

200

______ x 0.20

S4-711

Dual Optical Heat 
Sensor

200

______ x 0.20

S4-770-S

Optical Heat Turbo 
Sounder

177

______ x 4.5

Optical Heat Non 
Turbo Sounder

200

______ x 2

S4-771-S

Dual Optical Heat  
Turbo Sounder

177

______ x 4.5

Dual Optical Heat  
Non Turbo Sounder

200

______ x 2

S4-780-S

Heat Turbo Sounder

177

______ x 4.5

Heat Non Turbo 
Sounder

200

______ x 2

S4-711-VAD-HPW

Dual Optical Heat 
Turbo Voice & White 
VAD

L
M
H

76
50
39

______ x
______ x
______ x

10.5
15.8
20.25

Dual Optical Heat 
NonTurbo Voice & 
White VAD

L
M
H

100
60
45

______ x
______ x
______ x

8
13.3
17.75

S4-711-VAD-HPR

Dual Optical Heat 
Turbo Voice & Red 
VAD

L
M
H

76
50
39

______ x
______ x
______ x

10.5
15.8
20.25

Dual Optical Heat non 
Turbo Voice & Red 
VAD

L
M
H

100
60
45

______ x
______ x
______ x

8
13.3
17.75

S4-711-V

Dual Optical Heat  
Turbo Voice

177

______ x 4.5

Dual Optical Heat  non 
Turbo Voice

200

______ x 2

S4-711-VAD-HPW

Dual Optical Heat & 
White VAD

L
M
H

133
70
50

______ x
______ x
______ x

6
11.3
15.75

Key

X  - Signify colour: R - Red &  
      W - White of product 
      body and strobe light

x  - Signify multiply by

~ - A maximum of up to 100
    input channels are
    allowed per loop.

* - Applicable when sounder
    is operating in turbo mode
    or with a bell tone.

# - 8 maximum if outputs are
     sectored     

LV - Low voltage 
MV - Medium voltage

L - Low power Visual Alarm

M - Medium power Visual  
      Alarm

H - High power Visual Alarm

S - Standard power Visual 
      Alarm

Summary of Contents for GENT COMPACT-LPC-EN

Page 1: ...arios 2 1 2 1 Loop card MCC MCB and PSU combinations VAD is a Visual Alarm Device The Loop card VIG LPC EN or COMPACT LPC EN must never be used in a Vigilon panel based System having device mix with 3400 sensors T 3 Post March 2014 build of EN Compact Loop card COMPACT LPC EN V4 48 or higher MCB 1 2 V4 52 or higher Post March 2014 build of EN Vigilon Loop card VIG LPC EN V4 48 or higher Pre or Pos...

Page 2: ... EN or COMPACT LPC EN can only be used as a replacement card for Older Build Loop card VIG LPC or COMPACT LPC where S4 and S3 Mark 1 2 devices or 34000 devices are installed on the loop circuit Up to 2Km loop length is possible with 1 5mm cable with S4 and S3 Mark 1 2 devices installed on a loop circuit In this case a rough method for calculating the loop load and loop cable length is shown in par...

Page 3: ...by Lumped alarm devices load If the alarm devices are lumped together on a loop circuit then there is a trade off between the number of alarm devices and loop cable length possible which must be calculated Use the Battery Standby and loop load calculator tool to determine the precise loop length loop load and panel standby In the absence of the tool a rough method to determine loop length and load...

Page 4: ...ent Device part number Description VAD POWER Maximum limit per loop No of Devices on loop Alarm current mA per device Alarm current x VIG RPT 72 Repeat panel 4 ______ x 1 20 VIG MIM A3 A3 Zonal Mimic panel 4 ______ x 1 20 S4 720 Heat Sensor 200 ______ x 0 20 S4 710 Optical Heat Sensor 200 ______ x 0 20 S4 711 Dual Optical Heat Sensor 200 ______ x 0 20 S4 770 S Optical Heat Turbo Sounder 177 ______...

Page 5: ...45 ______ x ______ x ______ x 8 13 3 17 75 S4 911 VAD HPR Dual Optical Heat CO Turbo Voice Red VAD L M H 76 50 39 ______ x ______ x ______ x 10 5 15 8 20 28 Dual Optical Heat CO Non Turbo Voice Red VAD L M H 100 60 45 ______ x ______ x ______ x 8 13 3 17 75 S4 911 replaced with S4 901 Dual Optical Heat Sensor CO 200 ______ x 0 20 S4 34760 Venturi Air Duct Kit 200 ______ x 0 20 S4 34740 Beam sensor...

Page 6: ...150 75 ______ x ______ x 2 60 5 30 S4 711 ST VO Dual Optical Heat Sensor Speech Strobe 55 40 ______ x ______ x 7 00 10 0 S4 911 ST VO Dual Optical Heat Sensor CO Strobe Sounder Speech 55 40 ______ x ______ x 7 00 10 0 A Total Alarm Current Distributed Alarm load Ensure the Total Alarm Current value calculated does not exceed the maximum total alarm current value shown below to achieve 2Km loop len...

Page 7: ... 1 2 2 2 3 2 4 2 5 200 mA 275 mA 300 mA 190 170 150 325 mA 180 170 150 120 100 350 mA 180 150 120 110 100 80 60 375 mA 190 170 150 120 100 80 60 n a n a 400 mA 190 170 150 130 110 90 70 n a n a n a n a Example 1 Devices allowed on a known loop cable length for Lumped alarm load If the loop cable length is known then you can determine the maximum number of devices that can be connected to a loop wh...

Page 8: ... 190 170 160 150 140 600 mA 190 180 170 150 140 100 90 80 60 n a 700 mA 190 170 160 150 130 120 110 100 60 n a n a n a n a 800m A 190 180 160 150 130 120 110 100 80 70 60 n a n a n a n a n a Example 1 Devices allowed on a known loop cable length for Lumped alarm load If the loop cable length is known then you can determine the maximum number of devices that can be connected to a loop where there i...

Page 9: ... an earth fault present before allocation Note An Earth fault post allocation is indicated as Earth fault Use the Loop Diagnostic Tool to diagnose the earth fault condition and rectify it Technical Data Loop Cards VIG LPC EN and COMPACT LPC EN Dimensions VIG LPC EN COMPACT LPC EN 130mm x 100mm x 15mm 120mm x 100mm x 15mm Weight 74g approximately Devices 200 device loop circuit Voltage and Current ...

Page 10: ...ware To enable the new loop card to supply the full alarm load in a system having Vigilon 4 6 loop panel we need the new power supply backplane and loop card The following photos show where to look to identify old and new parts 2211 187 V4 xx Older build of Vigilon PSU VS PSU 24 or VS PSU 72 Post July 2013 build of Vigilon PSU Older build of build of Vigilon LPC Post March 2014 build of Vigilon LP...

Reviews: