4188-1075 issue 3_Part 1_08/14

Loop Cards

Gent by Honeywell reserves the right to revise this publication from time to time and make changes to the content hereof 

without obligation to notify any person of such revisions of changes.

Hamilton Industrial Park, Waterside Road, Leicester LE5 1TN, UK.

 

Website: www.gent.co.uk

Telephone: +44 (0) 116 246 2000

Tech. Support www.gentexpert.co.uk

Fax (UK) +44 (0) 116 246 2300

2

WEEE Directive:

At the end of their useful life, the packaging, product
and batteries should be disposed of via a suitable 
recycling centre. 
Do not dispose of with your normal household waste. 
Do not burn. 

At the end of their useful life, the packaging,
product and batteries should be disposed of
via a suitable recycling centre and in 
accordance with national or local legislation.

Post March 2014 Loop Cards

Post March 2014 Loop Cards are: 

 

VIG-LPC-EN   (for use in Vigilon 4-6 loop panels only)

 

COMPACT-LPC-EN  (for use in Vigilon Compact panel only)

Condition of use

The Loop Cards (VIG-LPC-EN and COMPACT-LPC-EN) must never be 

fi

 tted as a replacement card in a Vigilon 

panel where 3400 devices are installed on its loop circuits.

The post March 2014 Loop card (VIG-LPC-EN or COMPACT-LPC-EN) can only be used as a replacement card for Older Build 
Loop card (VIG-LPC or COMPACT-LPC) where S4 and S3 Mark 1/2 devices or 34000 devices are installed on the loop circuit.

 

Up to 2Km loop length is possible with 1.5mm² cable with S4 and S3 Mark 1/2 devices installed on a loop circuit. In this case a 
rough method for calculating the loop load and loop cable length is shown in part 2 of this document. Both parts 1 and 2 of this 
document can be downloaded by registered user of Gent Expert forum. For precise loop load and battery standby calculation 
use the ‘Battery Standby and Loop load calculator’ tool.

 

Up to 1Km loop length is possible with 1.5mm² cable where 34000 devices or a mix of 34000, S4 and S3 Mark 1/2 devices 
are installed on a loop circuit. For a precise loop load and battery standby calculation use the ‘Battery Standby and Loop load 
calculator’ tool.

Battery Standby and Loop load calculator tool

The ‘Battery standby and loop load calculator’ tool can be downloaded from www.gentexpert.co.uk website by registered users.

Vigilon Loop Diagnostic tool

The Vigilon Loop Diagnostic Tool must only be used to diagnose loop circuits driven by Post March 2014 Loop Cards 
(VIG-LPC-EN or COMPACT-LPC-EN) 

fi

 tted in a Vigilon panel.

The Loop Diagnostic Tool cannot be used to diagnose Vigilon panel 

fi

 tted with Loop Cards (VIG-LPC or 

COMPACT-LPC).

Summary of Contents for GENT COMPACT-LPC-EN

Page 1: ...arios 2 1 2 1 Loop card MCC MCB and PSU combinations VAD is a Visual Alarm Device The Loop card VIG LPC EN or COMPACT LPC EN must never be used in a Vigilon panel based System having device mix with 3400 sensors T 3 Post March 2014 build of EN Compact Loop card COMPACT LPC EN V4 48 or higher MCB 1 2 V4 52 or higher Post March 2014 build of EN Vigilon Loop card VIG LPC EN V4 48 or higher Pre or Pos...

Page 2: ... EN or COMPACT LPC EN can only be used as a replacement card for Older Build Loop card VIG LPC or COMPACT LPC where S4 and S3 Mark 1 2 devices or 34000 devices are installed on the loop circuit Up to 2Km loop length is possible with 1 5mm cable with S4 and S3 Mark 1 2 devices installed on a loop circuit In this case a rough method for calculating the loop load and loop cable length is shown in par...

Page 3: ...by Lumped alarm devices load If the alarm devices are lumped together on a loop circuit then there is a trade off between the number of alarm devices and loop cable length possible which must be calculated Use the Battery Standby and loop load calculator tool to determine the precise loop length loop load and panel standby In the absence of the tool a rough method to determine loop length and load...

Page 4: ...ent Device part number Description VAD POWER Maximum limit per loop No of Devices on loop Alarm current mA per device Alarm current x VIG RPT 72 Repeat panel 4 ______ x 1 20 VIG MIM A3 A3 Zonal Mimic panel 4 ______ x 1 20 S4 720 Heat Sensor 200 ______ x 0 20 S4 710 Optical Heat Sensor 200 ______ x 0 20 S4 711 Dual Optical Heat Sensor 200 ______ x 0 20 S4 770 S Optical Heat Turbo Sounder 177 ______...

Page 5: ...45 ______ x ______ x ______ x 8 13 3 17 75 S4 911 VAD HPR Dual Optical Heat CO Turbo Voice Red VAD L M H 76 50 39 ______ x ______ x ______ x 10 5 15 8 20 28 Dual Optical Heat CO Non Turbo Voice Red VAD L M H 100 60 45 ______ x ______ x ______ x 8 13 3 17 75 S4 911 replaced with S4 901 Dual Optical Heat Sensor CO 200 ______ x 0 20 S4 34760 Venturi Air Duct Kit 200 ______ x 0 20 S4 34740 Beam sensor...

Page 6: ...150 75 ______ x ______ x 2 60 5 30 S4 711 ST VO Dual Optical Heat Sensor Speech Strobe 55 40 ______ x ______ x 7 00 10 0 S4 911 ST VO Dual Optical Heat Sensor CO Strobe Sounder Speech 55 40 ______ x ______ x 7 00 10 0 A Total Alarm Current Distributed Alarm load Ensure the Total Alarm Current value calculated does not exceed the maximum total alarm current value shown below to achieve 2Km loop len...

Page 7: ... 1 2 2 2 3 2 4 2 5 200 mA 275 mA 300 mA 190 170 150 325 mA 180 170 150 120 100 350 mA 180 150 120 110 100 80 60 375 mA 190 170 150 120 100 80 60 n a n a 400 mA 190 170 150 130 110 90 70 n a n a n a n a Example 1 Devices allowed on a known loop cable length for Lumped alarm load If the loop cable length is known then you can determine the maximum number of devices that can be connected to a loop wh...

Page 8: ... 190 170 160 150 140 600 mA 190 180 170 150 140 100 90 80 60 n a 700 mA 190 170 160 150 130 120 110 100 60 n a n a n a n a 800m A 190 180 160 150 130 120 110 100 80 70 60 n a n a n a n a n a Example 1 Devices allowed on a known loop cable length for Lumped alarm load If the loop cable length is known then you can determine the maximum number of devices that can be connected to a loop where there i...

Page 9: ... an earth fault present before allocation Note An Earth fault post allocation is indicated as Earth fault Use the Loop Diagnostic Tool to diagnose the earth fault condition and rectify it Technical Data Loop Cards VIG LPC EN and COMPACT LPC EN Dimensions VIG LPC EN COMPACT LPC EN 130mm x 100mm x 15mm 120mm x 100mm x 15mm Weight 74g approximately Devices 200 device loop circuit Voltage and Current ...

Page 10: ...ware To enable the new loop card to supply the full alarm load in a system having Vigilon 4 6 loop panel we need the new power supply backplane and loop card The following photos show where to look to identify old and new parts 2211 187 V4 xx Older build of Vigilon PSU VS PSU 24 or VS PSU 72 Post July 2013 build of Vigilon PSU Older build of build of Vigilon LPC Post March 2014 build of Vigilon LP...

Reviews: