[CODED] 1: Set Day Alarm (MT60) Config
[PATTS] to select condition
Main
Config
Global
Codes
<>: selects response condition from: Day Alarm, Night Alarm,
Action, Supervisory, Aux.
1: Scrolls through coded pattern selections: MT60, MT120,
Temporal, CA Code, Coded 4s.
[L,AAA]
FLR1
Lobby
Config
[LOCTN] 7,9 chng 1st ^
chng 2nd
Main
Config
Global
System
ID
or
Main
Config
Inputs
(or
Outputs)
Select
Location
Enter label using keypad and shift key. Press button until
desired letter appears. Use BKSP/EDIT to capitalize.
Use arrow keys <> to shift message from left to right or vice
versa.
NOTE: If this menu is opened from the Global Config Menu,
System ID selection (Menu 5 option 4), SYSTM ID is displayed;
otherwise, L,AAA LOCTN as shown above.
1: Toggles Multiple Trouble Acknowledge ON/OFF
2: Toggles Alarm/Trouble Reminder ON/OFF
3: Scrolls Walk Test Timeout (30m, 60m, 90m)
4: Toggles RS232 Supervision Message ON/OFF
[MISC] 1: MutiAck (ON) 2: Reminder (ON) Config
[OPTS] 3: WT Timeout (30m)
4: SupvMsg (ON)
Main
Config
Global
Misc.
[6]
[LCD] Number of Remote Displays (1)
[Annunc]
Main
Config
Global
Misc.
[7]
NOTE:
Some menus may appear in different contexts, but with slightly different behavior. For example,
the “Select Device” menu is used in both the Config Inputs and Config Outputs sections to
determine which device is to be affected. The process of selection is the same, but when the
selection is complete, the result (that is, which menu opens next) differs.
NOTE:
The Alarm Verification Feature is disabled when sensor cross-zoning is employed.