Sensors occupy Addresses 01-99 on the signaling line
circuits. Sensors are ion, photoelectronic, or thermal. They
are latching and non-verified when autoconfigured.
Monitor/Control modules occupy Addresses 101-198. The
type of device assigned to a monitor module during
autoconfiguration depends on the address as shown below:
5.0 System
Programming
5.1
MAIN Menu Selections
CONFIG
Where automatic configuration of the
system is accomplished, as well as all of
the system global programming, input to
output group programming and NAC
coding.
WALK/DRILL
Allows the user to select Audible or Silent
Walk Test as well as activating and de-
activating the System Drill function.
I/O
Allows the user to activate (turn on) or de-
activate (turn off) any output in the system.
CLOCK
Selection supplies the options for
programming the system time, date,
day/night weekend and holidays.
LOG
Options for manipulating the Event Log are
display, print, clear (buffer) and selecting
to print only the Sensitivity Report.
INFO
Gives the user basic system information
such as the current firmware version, the
last configuration date as well as the last
menu Designation used during the last
system configuration update.
5.1.1
Addresses/Default settings after Autoconfiguration
Address Device
100-149 Manual
station
150-159 Supervisory
switch
160-169 Waterflow
switch
170 Silence
switch
171 Reset
switch
172 Fire
Drill
switch
173 Alarm/Acknowledge
switch
174 Trouble/Supv.
Acknowledge
switch
175 Aux
switch
176-179 Tamper
switch
180-184 Control
panel
185-189 Remote
zone
190-198
Normally open contacts
AOM modules are silenceable and activate on general alarm (day or night). AOM modules modified
by breaking off tabs are non-silenceable and activate on general alarm (day or night).
System programming can be performed either by front
panel programming as shown below or via portable
computer and the Gamewell-FCI Field Configuration
Program.