![Honeywell Gamewell 7100 Series Installation & Operating Manual Download Page 30](http://html.mh-extra.com/html/honeywell/gamewell-7100-series/gamewell-7100-series_installation-and-operating-manual_153484030.webp)
9000-0447 Rev. I
Page 24 of 42
4.2 Panel
Switches
Table 4-2 Switches
Designation Comments
Alarm Acknowledge
Silences the panel audible sounder. This switch must be pressed once for
each Alarm condition present in the system.
Trouble Acknowledge
Silences the panel audible sounder. This switch must be pressed once for
each Trouble or Supervisory condition present in the system.
Signal Silence
Press once and any outputs programmed as silenceable will be
deactivated.
(All applicable silence LEDs will light). A second activation will re-activate
the previously silenced outputs. This switch only functions if an Alarm or
Supervisory condition exists in the system.
Lamp Test/Reset
Press momentarily and all LEDs (including all elements in the display) will
light momentarily. Press and hold to reset the system.
Menu/Back
Used in programming. The display will prompt the operator as to which
function applies. “Menu” is pressed to initially put the 7100 into
programming mode. The “Back” function will step the operator out of the
programming mode one element at a time.
BKSP/Edit
Used in programming. The display will prompt the operator as to which
function applies.
OK
Accepts any changes made in the programming field.
Alphanumeric Keys
These 12 keys allow the user to choose a specific point address by using
the numbers for point sensitivity reading, disabling an address, etc.
Press each key the number of times necessary to display the correct
character on the display.
Example: Pressing the “2” key,
Once will display the letter “A”
Twice will display the letter “B”
Three times will display the letter “C”
Four times will display the number “2”
PK-625 Key Switch
This key switch is keyed alike with the door lock, and must be operated in
order to activate the keypad.
Figure 10 Switches