Part No: 4417341 Revision 10
Installation Manual 26
954 SmartServo FlexLine
Installing the Glands, Conduits and Stopping Plugs
CAUTION!
Improper installation of cable glands, conduits, or stopping plugs will invalidate the Ex
approval of the 954 SmartServo FlexLine.
5.5.1. Conduits
Use explosion proof (Ex d) conduits with an appropriate IP value. See the type plate on
the device.
WARNING!
If the 954 SmartServo FlexLine is installed in a hazardous area:
Metal conduits must be used, size 3/4”.
Stopper boxes must be installed within 45 cm (18”) of the device to seal the cabling in the
conduit.
NOTE:
Install the conduits according to the instructions provided by the manufacturer.
5.5.2. Unused Cable Inlets
Seal unused cable inlets with approved
¾” NPT threaded stopping plugs.