Part No: 4417341 Revision 10
Installation Manual 40
954 SmartServo FlexLine
External Fusing
The 954 SmartServo FlexLine external fuses must be installed in the mains supply cable
to each 954 SmartServo FlexLine.
mains voltage
fuse value (in accordance with IEC 127-2-3)
220 Vac or 230 Vac
315 mA slow
110 Vac or 130 Vac
630 mA slow
65 Vac
1 A slow
Cable Glands / Conduit
Explosion-proof (Ex d) or increased safe (Ex e) cable glands must be used, depending
on local requirements. Refer to the Ex-marking on the identification label of the 954
SmartServo FlexLine to determine which type of cable glands is required.
NOTE:
Mount the glands according to the supplier’s instructions.
Conduit:
If the 954 SmartServo FlexLine is installed in a hazardous area, threaded rigid metal
conduit or threaded steel intermediate metal conduit shall be used.
NOTE:
If the 954 SmartServo FlexLine is installed in a hazardous area, Ex d certified conduit
seals must be applied directly at the wall of the 954 SmartServo FlexLine to seal the
cabling in the conduit.
Depending on the wiring configuration, one to four ¾” NPT threaded cable glands (or rigid
conduits) may be required with the 954 SmartServo FlexLine.