background image

 

 

 

44 | 

P a g e

 

 

FLARE 70|70H|70EH  

Suitable for all Flare 70/70H/70EH Fireplaces 

 

 

 

 

 

 

 

 

 

 

 

Vent Restrictor Setting: Set to 1-6 based on Table below. 

X: Run will need to be Power Vented 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Summary of Contents for Flare Corner Left Series

Page 1: ...gas connection must be performed by a licensed plumber or gas fitter in the State of Massachusetts Also see Carbon Monoxide detector requirements on page 56 NOTICE Flare Fireplaces Installation Guide Honeywell CSv7 Flare Double Corner Left Corner Right Corner Front See Through and Room Definer v14 6 FLARE REQUIRES INSTALLATION BE PERFORMED BY AN NFI CERTIFIED INSTALLER OR A CERTIFIED FLAREAUTHORIZ...

Page 2: ... REMOVAL 15 SIDE GLASS TRIM RMEOVAL INSTALLATION FLARE H AND EH 17 REFLECTIVE BACK INSTALL 18 INSTALLATION STEPS 19 INSTALLATION PREPARATION 20 ACCESS PANEL 20 FIREPLACE UNPACKING 21 FIREPLACE TELESCOPIC LEGS SETUP 22 LEG SETUP FOR FRONT AND SEE THROUGH UNITS 23 LEG SETUP FOR CORNER UNITS 24 UNPACKING CONTROL UNIT AND ACCESSORIES 25 FIREPLACE POSITIONING 26 LED LIGHTS 27 LED LIGHT INSTALL AND POWE...

Page 3: ...5 DOUBLE GLASS INSTRUCTIONS 56 TELEVISION MOUNTING ABOVE FIREPLACE 57 TV INSTALL FLAT EXAMPLE 58 TV INSTALL L TYPE EXAMPLE 59 TV INSTALL RECESS 45 DEGREE ELBOW ON TOP OF THE UNIT 60 TV INSTALL WITHOUT RECESS MANTEL INSTALLATION 61 CLEARANCES 62 GENERAL INFORMATION AND STEPS 62 CLEARANCES SPECIFICATION 69 MANTEL CLEARANCE 70 CLEARANCE TO A SPRINKLER 71 HEAT RELEASES 72 AIR INTAKE 72 EXAMPLES OF HEA...

Page 4: ...C AND CONTROL 85 ELECTRIC DIAGRAM SCREEN 85 ELECTRIC DIAGRAM DOUBLE GLASS OR PV 86 DOUBLE GLASS BOARD LED LIGHT GUIDE 87 ELECTRIC DIAGRAM PV SYSTEM 88 REPLACEMENT PARTS 89 MAINTENANCE 90 TROUBLESHOOTING 92 ADJUSTING YOUR AIR SHUTTER TO PREVENT SOOTING 92 APPENDIX 93 MAINTENANCE LOG 93 WARRANTY POLICY 94 ...

Page 5: ...nce should be located out of traffic and away from furniture and draperies Children and adults should be alerted to the hazards of high surface temperature and should stay away to avoid burns or clothing ignition This appliance must be electrically wired and grounded in accordance with local codes or in the absence of local codes with National Electric Code ANSI NFPA 70 latest edition or the Canad...

Page 6: ... a fireplace or stove install an adjustable safety gate to keep toddlers young children and other at risk individuals out of the room and away from hot surfaces WARNING When an existing Category I heater is removed or replaced the original venting system may no longer be sized to properly vent the attached appliances Instructions shall also indicate effects of an improperly sized venting system fo...

Page 7: ...ireplaces have been certified and tested to work with Natural Gas or Propane Certification Information ANSI Z21 88 CSA 2 33 2014 Vented Gas Fireplace Heaters CSA CLASSES CLASS 2901 84 CLASS 2901 04 All fireplaces are rated for commercial and residential use The CSA Mark The Canadian Standards Association CSA is a nonprofit association serving business industry government and consumers in Canada an...

Page 8: ...llation please use the ICC installation guide http icc chimney com en exceldirect support This product is listed to ANSI standards for Vented Gas Fireplace Heaters and applicable sections of Gas Burning Heating Appliances for Manufactured Homes and Recreational Vehicles and Gas Fired Appliances for Use at High Altitudes Installation MUST comply with local regional state and national codes and regu...

Page 9: ... electric power is supplied to it The Fireplace power supply needs to be wired by QUALIFIED ELECTRICIAN The electrician can provide the operator a switch to control the outlet the fireplace is connected to The use of the plug should only be done when access to the outlet is available even after installation is completed This appliance must be grounded In the event of a malfunction or breakdown gro...

Page 10: ...0 P a g e WALL SWITCH The Fireplace ON OFF operation can be done with a standard wallswitch provided by the electrition and wired to control the supply of power to the fireplace outlet or hardwire setup ...

Page 11: ...ont cover view open to be able to view the pilot spark and flame from outside Fireglass a or Fire Glass may be used b When the fireplace viewing window is open and media is placed make sure Fire Glass does not fall on the ceramic glass lower frame as that may cause breakage when putting back the ceramic glass c Make sure pilot is clear of any Fire Glass particles d Flare Fire Glass can be put safe...

Page 12: ...IONS Please follow the below described quantities of media placement in your firebox Please note over saturation of media throughout the firebox may result in improper combustion or Soot within the fireplace or termination cap ...

Page 13: ...hot viewing glass and is provided with this appliance It must remain installed for the protection of children and other at risk individuals Do NOT operate the fireplace without the safety screen barrier Front See Through and Corner Units Safety screen removal requires no tools Push the top frame of the screen up until it clears the bottom of the opening Tilt the bottom of the screen out and pull d...

Page 14: ...hould be done once during install only Attach glass suction cups to the glass Use more than one suction cup if needed any unit above 45 Using suction cups slightly push in the external glass top edge Once glass has been pushed slightly lift the glass to clear bottom part of the glass Remove the glass and place in a secure location Install back external glass Attach glass suction cups to the glass ...

Page 15: ...e done by a licensed or qualified service person Step 1 Attach glass suction cups to the glass Remove the glass lower magnetic trim Place the trim in a secure place Any unit above 45 requires 2 suction cups to hold the glass Step 2 Release the lower glass trim The lower trim bolts can be released by hand and should not require any tools Once bolts are released remove lower glass holder trim Step 3...

Page 16: ... 3 Step 4 1 Step 4 2 When putting back the glass DO NOT overtighten the bolts or glass may break Use step 4 1 for putting the glass back Glass trim screws should be closed hand tight DO NOT overtighten the bolts or glass may break ...

Page 17: ... be done with a cold fireplace fireplace appliance turned off and manual gas valve shutoff Unplug the fireplace from any electric power Double Glass Units The below picture shows the right side glass trim Step 1 Using a drill untighten the screw that is located at the right top of the trim side as shown in picture below Step 2 Move the right trim glass to the left as shown in picture below Step 3 ...

Page 18: ... to clean The reflective back is shipped outside the unit inside a sleeve with the other glass panes It should be mounted at the back of the fireplace placed in the gap between the fire bed shown yellow below and held by the top mounting brackets red circle Carefully carry the reflective back using suction cups and place at a 45 degree angle as shown below Screw the mirror clamp as shown below mak...

Page 19: ... Put the Fireplace in the desired location Verify clearance to non combustible and combustible materials Follow the clearance instruction and example in the manual 5 For LED units connect LED system and test LED 6 Attach the units back bracket to the wall framing 7 For double glass units only remove glass locking screws and discard 8 Adjust Fireplace vent restrictor based on vent configuration and...

Page 20: ...the necessary parts that may need servicing over time While Flare also offers access to these components by going inside the fireplace with instructions HERE you will find having a dedicated area where all your components can be easily accessed for servicing without the need to remove the glass media burner is the preferred method HIDDEN ACCESS PANEL EXAMPLE ...

Page 21: ... and confirm there is no external damage If damage exists please notify Flare Fireplaces immediately Remove the top wood studs and pull the external carton box up Please do not remove the blue wrap completely at this stage Leave the fireplace placed on the pallet for the next step Fireplace legs setup ...

Page 22: ...C LC DC RD front legs will need to be assembled Fireplace must NOT be installed without telescopic legs extracted to a minimum of 3 Installing fireplace without telescopic legs is a fire hazard Installing the Fireplace without legs sitting on the fireplace frame may bend the frame cause glass breakage Fine Tuning After extending the legs to the desired length use the wrench included to fine tune t...

Page 23: ... three screws to secure the telescopic leg in position Note that the top pin inserts into the holes only for alignment The two bottom screws tighten down on the legs Step 5 Repeat Steps 1 4 for each on the fireplace so that they are all extended to the same length Step 6 Stand the fireplace up and fine tune the feet with the wrench included so the fireplace is level Open the screws to raise the fi...

Page 24: ... the 4 screws so that the fireplace will stand at the desired height after the foot for fine tuning is also screwed in Insert the 4 screws into the holes and Rivnuts beneath and tighten Screw in the foot so that it can later be adjusted to slightly raise or lower the fireplace Configure remaining legs to the same height Stand the fireplace up and fine tune the feet with the wrench provided so the ...

Page 25: ...t test of unit Place accessories white bag in a secure location The control unit gas valve and receiver is attached to the fireplace on an umbilical cord Once fireplace is moved to its final location the control unit can be put close to the service access door Gas valve and receiver GAS VALVE WILL COME WRAPPED ONLY TO BE OPENED FOR UNITS FIRST FIREUP Optional control module for double glass units ...

Page 26: ...raming Use the manual clearance guide for more details Attach the fireplace top brackets to the metal stud in the back to secure the fireplace in place The bracket length can be adjusted by releasing the screws on the top Fireplace should remain on the wood pallet when carried to final installation location Do not attempt to use a pallet jack or any other moving tools if the unit has been removed ...

Page 27: ...ED Operation Option 1 LED power is connected to the Flare control system Labeled in picture above as LED Power Outlet and below as Connection C LED will turn On and Off with the fireplace controlled by the fireplace remote or wall switch Color control can be done by the LED remote Once a color is selected the LED remote can be stored away LED to be switched Off when fireplace is turned off LED can...

Page 28: ...pre connected prior to shipping Connect LED connectors points A to the fireplace using the quick connect connectors 3 Connect LED control system to the power supply point B 4 Connect LED Power supply to an external power source point C Do not connect the LED to the Flare control LED plug at this point Use the LED remote to turn the LED on the LED system Once testing is done connect the LED power a...

Page 29: ... owning 64 thousand colors 20 automatic changing modes to choose from RBG Strip is using 24V DC power adapter REMOTE MATERIAL 110x52x20mm POWER AAA Battery 2pcs MATERIAL ABS FABRICATION PROCESSING Multicolor Printing UV Varnish CONTROLLER SIZE 85x45x23mm WORKING VOLTAGE DC12V 24V CONTROL WAY RGB 3 CHANNELS MAX LOAD PER CHANNEL 6A OUTPUT CONNECTION COMMON ANODE TELECONTROL DISTANCE 30 METERS PROGRA...

Page 30: ...LITTERS ADJUSTABLE ADJUSTABLE 16 BLUE COLOR FREQUENTLY BLINKS ADJUSTABLE ADJUSTABLE 17 BLUE COLOR GLITTERS ADJUSTABLE ADJUSTABLE 18 YELLOW COLOR FREQUENTLY BLINKS ADJUSTABLE ADJUSTABLE 19 YELLOW COLOR GLITTERS ADJUSTABLE ADJUSTABLE 20 CIRCULATION MODE Code Matching Please follow the instructions below Confirm it is correctly connected between power supply LED controller LED load Switch the power o...

Page 31: ...e operation of the blowers is controlled with a power ON Off to the outlet they are connected to The customer has the option to Install a smart outlet to control the blowers Use a wall switch to start shutdown the blowers whenever they want An electrician will need to wire the wall switch to control the power to the fireplace fans Buy a remote system for the outlet Please note that the blowers wil...

Page 32: ...lease use the ICC direct vent installation manual http icc chimney com en exceldirect Instructions Where a vent pipe passes through a floor or ceiling a ceiling firestop MUST be used to retain insulation and maintain proper clearances Use roof support brackets where needed Install the first section of vent pipe into the collar on top of the fireplace Connections between each vent system component ...

Page 33: ...s to combustibles is required except for clearances in appliance enclosures Horizontal vents have a minimum 1 4 inch 6mm rise per 1 foot towards the termination When penetrating through combustible walls and ceilings frame a minimum of 10 5 in x 10 5 in opening and ensure that the insulation is kept clear of the vent pipe using either a wall thimble or an attic insulation shield use the DuraVent f...

Page 34: ... vent part used Note size of vents depends upon specific fireplace and cutout sizes vary according to the DuraVent or ICC part number used Minimum height from roof to lowest discharge opening Vertical Vent Termination Opening Framing will depend on the part used See table above or vent installation manual Minimum 24 horizontal clearance to any surface such as an exterior wall for vertical terminat...

Page 35: ...ltiple horizontal terminations See the table on page 32 for minimum cutout dimensions or frame openings around wall venting Make sure clearances to combustible material are maintained based on vent part used Note size of vents depends upon specific fireplace and cutout sizes vary per the DuraVent part number used ...

Page 36: ...rfaces require 24 inches 61 cm min Clearance to unventilated soffit F 6 15 cm min Clearance to outside corner G 6 15 cm min Clearance to inside corner H 3 90 cm min Not to be installed above a meter regulator assembly within 3 feet 90 cm horizontally from the centerline of the regulator I 3 feet 90 cm min Clearance to service regulator vent outlet J 12 inches 30 cm min Clearance to non mechanical ...

Page 37: ...r Clearance in accordance with local installation codes and the requirements of the gas supplier As specified in CGA B149 Installation Codes note local Codes or Regulation may require different clearances For U S A Installations follow the current National Fuel Gas Code ANSI Z223 1 Horizontal vent termination minimum clearance to adjacent structure or fence is 48 Minimum 24 horizontal clearance to...

Page 38: ... The vent restrictor setting is from 1 minimum restriction to 6 maximum restriction The installer will document the restrictor setting in the end of the installation Use the vent planning guide and table to determine the restrictor setting Signs the vent restrictor needs to be adjusted Vent restrictor should be opened if the flame has the following characteristics Flame is excessively tall and lif...

Page 39: ...s the path is not allowed Setting the restrictor to 1 means there is no restriction Numbers in the table represent the restrictor setting to be set Document the restrictor setting configuration prior to leaving the installation site The tables apply to both NG Natural Gas and Propane Minimum 3 ft vertical run A required before any bend or turn o See Flare Front and Flare See Through exception o Se...

Page 40: ...40 P a g e FLARE 30 30H Suitable for all Flare 30 Fireplaces Vent Restrictor Setting Set to 1 6 based on Table below X Run may need to be Power Vented ...

Page 41: ...41 P a g e FLARE 45 45H 45EH Suitable for all Flare 45 45H 45EH Fireplaces Vent Restrictor Setting Set to 1 6 based on Table below X Run may need to be Power Vented ...

Page 42: ...42 P a g e FLARE 50 50H 50EH Suitable for all Flare 50 50H 50EH Fireplaces Vent Restrictor Setting Set to 1 6 based on Table below X Run may need to be Power Vented ...

Page 43: ...43 P a g e FLARE 60 60H 60EH Suitable for all Flare 60 60H 60EH Fireplaces Vent Restrictor Setting Set to 1 6 based on Table below X Run will need to be Power Vented ...

Page 44: ...44 P a g e FLARE 70 70H 70EH Suitable for all Flare 70 70H 70EH Fireplaces Vent Restrictor Setting Set to 1 6 based on Table below X Run will need to be Power Vented ...

Page 45: ...45 P a g e FLARE 80 80H 80EH Suitable for all Flare 80 80H 80EH Fireplaces Vent Restrictor Setting Set to 1 6 based on Table below X Run will need to be Power Vented ...

Page 46: ...46 P a g e FLARE 100 100H 100EH Suitable for all Flare 100 100H 100EH Fireplaces Vent Restrictor Setting Set to 1 6 based on Table below X Run will need to be Power Vented 6ft Minimum Rise ...

Page 47: ...ons allow Flare Fireplaces to operate in vent conditions that would not be possible without the motor unit See the Flare Power Vent Installation Manual for more specific instructions The system is designed and tested with DuraVent 3x5 gasket direct vent pipes It is critical for the safety and operation of the system to use the DuraVent 3x5 gasket system ...

Page 48: ...is less than 12 feet Refer to the Flare Power Vent Installation Manual for more specific instructions Clearance Clearances between the vent pipe and combustible materials must be maintained at 3 inches top and 1 for side and below Maintain the same clearance from the power vent box to any combustible materials Power vent unit must be installed by a qualified installer in accordance with these inst...

Page 49: ...h voltage 4 wire cable labeled below as connection PV Power 115V Cable to be used is 16 AWG 4 copper wire Cable is not included with the PV kit and can be sourced spertly Connect 4 wire high voltage cable from the Power Vent to matching colors white to white black to black green to green and red to red on the PV system The Flare Fireplaces Fan board is a must for operating a Flare Fireplace with a...

Page 50: ... to or less than 1 2 psig 3 5 kPa Move the appliance into position and secure it to the wall using the back or side mount Install a manual gas valve before the connection to the fireplace appliance automatic valve Connect the gas line to the fireplace The appliance is designed to accept a 1 2 13mm gas supply Connect the gas supply in accordance with local codes CAN CSA B149 1 in Canada or to the c...

Page 51: ...h local codes if any If not available follow ANSI 223 1 Installation should be done by a qualified installer approved and or licensed as required by the locality in the Commonwealth of Massachusetts installation must be performed by a licensed plumber or gas fitter ...

Page 52: ...ce and be put next to the access door location Do not place the gas valve or controls above the level of the burner If the fireplace is to sit low on the floor the controls must be placed outside the non combustible zone or insulated from the heat from the fireplace The access door can be placed on any side of the fireplace below the non combustible line The use of a 10 x10 access door is highly r...

Page 53: ...ERSION Your Fireplace may be shipped to support Liquid Propane Gas Check your Flare Fireplaces gas rating plate at the back of your valve to confirm the gas type Use the following link for the Flare Fireplace NG to LPG conversion on SIT ignition Use the following link for the Flare Fireplace NG to LP conversion on Maxitrol ignition NOTICE Flare Fireplaces does offer the ability to run your firepla...

Page 54: ...in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS 4 INSPECTION The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless upon inspection t...

Page 55: ...glass The design allows cool air to flow between the two layers with the help of built in blowers which significantly lowers the temperature of the external glass making it safe for a brief touch Double Glass is suitable for commercial as well as residential use The double glass feature provides a sleek look with no frame while maintaining heating characteristics and efficiency This feature does n...

Page 56: ...are inches OPEN AIR FLOW For fireplace sized 50 and below vent area must be at least 100 square inches OPEN AIR FLOW For fireplaces sized 80 100 vent area must be at least 100 square inches OPEN AIR FLOW Lower Air Intake Optional for normal safety screen installation Required for installation with double glass or safety screen with optional blower kit For fireplaces sized 60 70 vent area must be a...

Page 57: ... to allow cables and other related material to be installed with less concern of blocking hot air flow Use non combustible material for double wall All wires MUST be secured and anchored to the frame to prevent any possibility of wires dropping on top of the Fireplace TV can be recessed when installed above the Fireplace be protected by a mantel or flush installed above the fireplace Wires should ...

Page 58: ... blocking hot air flow THE EXAMPLE SHOWN ABOVE IS NOT AN EXACT RENDERING OF EVERY FIREPLACE STYLE AND VENT PLACEMENT OFFERED BY FLARE BUT MEANT TO CONVEY RELEVANT MEASUREMENTS FOR USE ON ALL UNIT INSTALLATIONS FOR EXACT DRAWINGS OF THE FIREPLACES AND THEIR VENT PLACEMENT PLEASE DOWNLOAD DIMENSION OR FRAMING GUIDES FROM OUR DIRECT VENT DOWNLOAD CENTER ...

Page 59: ...than 10 from the face of your finishing material to the back of the recess as it will hinder air flow damage the TV Warning Maintain Open Air flow between the fireplace and drywall Make sure cables or any other materials are not blocking hot air flow THE EXAMPLE SHOWN ABOVE IS NOT AN EXACT RENDERING OF EVERY FIREPLACE STYLE AND VENT PLACEMENT OFFERED BY FLARE BUT MEANT TO CONVEY RELEVANT MEASUREME...

Page 60: ...You must maintain a 1 clearance from your recess to the vent pipe to prevent overheating 2 Install two 45 elbows directly above the fireplace followed by a minimum 4 ft vertical vent rise The two small elbows will move the vertical section back 5 5 8 Note that the 1 inch clearance from the vent applies also to the back non combustible wall 3 Do not use any elbow with an angle larger than 45 degree...

Page 61: ...elevision manufactures and manuals will instruct the owner not to install television above or near a fireplace Mounting a television above the fireplace is based on the owner s decision and responsibility Flare will not be held liable for any adverse effects on a TV artwork or other equipment located near the Flare appliance It is the customer s or contractor responsibility to verify that their TV...

Page 62: ...a g e CLEARANCES GENERAL INFORMATION AND STEPS All materials inside the chase and above the Fireplace must be non combustible or covered combustible only See more clearance information in the following pages ...

Page 63: ...nt pipe on all horizontal runs to combustibles is required VERTICAL VENT PIPE CLEARANCES A minimum of 1 inch 25mm around the vent pipe on all vertical runs to combustibles is required Except for clearances in appliance enclosures Horizontal Vents must have a minimum 1 4 inch 6mm rise per 1 foot run towards the termination WARNING Never allow the vent to run downward A downward slope can trap heat ...

Page 64: ... sides and back Covered combustible Combustible material at the back or sides of the fireplace MUST be covered with non combustible material that is at least inch thick Covered wood can be placed a minimum 3 away from the side and back Example A non combustible cement board is placed 2 inches from the back of the fireplace The cement board used is inch thick Combustible material can be used behind...

Page 65: ...he 18 must be covered Zone B There should be no combustible materials left uncovered above the fireplace inside the chase Fireplace chase should be designed and built to allow hot air to release from the unit and rise up in a non combustible channel to the heat release 13 Chase celling Top of the chase must be covered with noncombustible material Firestop No exposed combustible materials are allow...

Page 66: ...When bringing your hearth to glass height it must be non combustible for the first 7 extending from the glass before any combustible material can be used to finish the hearth As seen in EXAMPLE 2 15 Adjacent Wall 1 Distance to any side adjacent wall must be at least 7 inches from the glass As seen in EXAMPLE 1 EXAMPLE 1 EXAMPLE 2 ...

Page 67: ...le minimum inch Type X fire rated drywall MUST be used to finish around the front of the appliance Covered combustible material can be used to finish around the fireplace if the proper distance from the fireplace is maintained Use example below to find proper distance See Examples 1 2 below for further details EXAMPLE 1 ...

Page 68: ...68 P a g e DO NOT connect materials to or drill into the metal fireplace frame This can result in excessive heat transfer and or damage to the fireplace and surrounding materials EXAMPLE 2 ...

Page 69: ...he metal fireplace frame This can result in excessive heat transfer and or damage to the fireplace and surrounding materials All joints between the finished wall sheathing and the appliance must be sealed with non combustible materials WARNING Risk of Fire DO NOT apply combustible materials beyond the minimum clearances Comply with all minimum clearances to combustibles as specified in this manual...

Page 70: ...bove the fireplace as anchor points Non combustible mantels do not have a minimum clearance to the fireplace opening and can be brought as close to the glass as allowed by the frame of the fireplace Please keep in mind any material used could potentially heat up dramatically the closer to the fireplace you bring it and the longer the fireplace is on Mantel Clearance table and example REF Height Ma...

Page 71: ...p from the fireplace being operated normally DO NOT INSTALL A SPRINKLER IN THE FIREPLACE CAVITY Please follow local building code to determine what temperature setting is relevant for your installation WARNING VAULTED CEILINGS CAN CREATE A CHANEL THAT FUNNELS HOT AIR DIRECTLY TOWARDS A SPRINKLER HEAD PLACED AT THE PROPER DISTANCE FROM HEAT RELEASE AS STATED ABOVE IF SPRINKLER HEAD SENSOR IS NOT RA...

Page 72: ...le fire stop is placed atop the inside of the chase and is framed in a way that does not allow any pockets of heat to be formed All rising heat should be able rise to the fire stop and freely flow though the heat release opening into the room AIR INTAKE Required for installation with double glass or safety screen with optional blower kit This allows air circulation which cools the external glass a...

Page 73: ...73 P a g e EXAMPLES OF HEAT RELEASES ...

Page 74: ...acuate the cavity above your fireplace the cooler your wall will be Flare offers many ways to implement a heat release that mask its existence allowing you to increase its size dramatically without ruining the visual aesthetic SEE SECTION REFERENCING EXAMPLES OF HEAT RELEASES AND AIR INTAKES IN FLARE INSTALLATION MANUAL For example if you are installing a Flare Fireplace with a 50 length you will ...

Page 75: ...owing you to increase its size dramatically without ruining the visual aesthetic SEE SECTION REFERENCING EXAMPLES OF HEAT RELEASES AND AIR INTAKES IN FLARE INSTALLATION MANUAL For example if you are installing a Flare Fireplace with a 50 length you will need a minimum of 50 SQ of open air flow to cool your double glass successfully But by meeting the minimum specification allowed the glass tempera...

Page 76: ...RE FRONT SEE THROUGH AND CORNER FIREPLACE CLEARANCE FLAT SIDE AND ISOMETRIC VIEW Warning Maintain open Air flow between the fireplace and drywall Make sure cables or any other materials are not blocking hot air flow ...

Page 77: ...p static vent opening The fireplace enclosure must allow air to rise and circulate from the top of the fireplace glass from lower vent opening to be released back to the room from the top To increase heating the enclosure should prevent hot air from being released to the attic by venting it back to the room using the static vent system A Non combustible stud MUST NOT be connected or drilled into t...

Page 78: ...NING Maintain open air between the fireplace and drywall Make sure cables or any other materials are not blocking hot air flow ain open Air flow between the fireplace and drywall Make sure cables or any other materials are not blocking hot air flow ...

Page 79: ...o be released into the room using the top static vent opening The fireplace enclosure must allow air to rise and circulate from the top of the fireplace glass from lower vent opening to be released back to the room from the top To increase heating the enclosure should prevent hot air from being released to the attic by venting it back to the room using the static vent system A Non combustible stud...

Page 80: ...e outdoor kit will tolerate moderate amounts of water on an occasional basis but is not waterproof The fireplace must be enclosed in a weatherproof enclosure covered in typical weatherproof material such as siding stucco stone tile etc and have a weatherproof structure to shed water that extends horizontally beyond the front and side perimeter of the fireplace Water running down vertical surfaces ...

Page 81: ...eplace is fully turned off when attempting to clean the front of the fireplace including pilot Use the Flare architectural guide for information on the window size and opening http flarefireplaces com portfolio items flare outdoor ...

Page 82: ... g e All studs and surrounding should follow the fireplace clearances and non combustible requirements The outdoor window kit should be sealed with non combustible tape prior to covering with brick or stucco ...

Page 83: ...roll to four tabbed charts click DOWNLOAD CENTER BURNER TYPE SIZE cm SIZE in FIREPLACE SIZE OF BURNERS A 55 cm 21 11 16 30 1 B 80 cm 31 12 16 45 1 C 105 cm 40 1 16 50 1 D 125 cm 35 cm 55 cm 35 cm 50 1 16 14 22 14 60 3 E 150 cm 35 cm 80 cm 35 cm 59 15 16 14 32 14 70 3 F 175 cm 35 cm 105 cm 35cm 684 16 14 40 14 80 3 G 215 cm 55 cm 105 cm 55 cm 84 22 40 22 100 3 ...

Page 84: ...l system will need to control the Power supply ON OFF to the fireplace outlet or direct wire connection CAUTION DO NOT CONTROL FIREPLACE FROM OUTSIDE OF HOME USING EXTERNALLY CONNECTED DEVICE ONLY OPERATE 3RD PARTY APPLICATION OR HOME AUTOMATION WHEN YOU CAN PHYSICALLY SEE THE FIREPLACE TURNING ON OFF IT IS NOT MEANT TO OPERATE WITHOUT LINE OF SIGHT TO FIREPLACE ...

Page 85: ...85 P a g e ELECTRIC AND CONTROL ELECTRIC DIAGRAM SCREEN MV MV PV PV ...

Page 86: ...DIAGRAM DOUBLE GLASS OR PV Note That the Wall Switch Wires Carries DC Signal TRANSFORME R L N PV Power 120v optional Wall Switch DC low voltage Honeywell power 110v Source Power 110v LED Power 110v optional Honeywell Valve ...

Page 87: ...o it will bypass the need to verify fan activity The switches are numbered to correlate with the LED lights they are associated with above The third smaller dip switch panel is the Master Bypass option Flipping these on bypasses all checks to the fan system Power Vent FAN LED INDICATORS A Red Fan is not connected or malfunctioning B Off Fan is being bypassed C Green Fan is running properly POWER L...

Page 88: ...88 P a g e ELECTRIC DIAGRAM PV SYSTEM Ports 49 47 are connected to J6 on fireplace main board ...

Page 89: ...ended 36 36 Ignition Cable Extension Brass Honeywell Pilot Connector Brass Pilot Connector for Honeywell System Honeywell Data Cable Data Cable for Honeywell System Honeywell Pilot Assembly Pilot assembly for Honeywell System Honeywell Transformer Main Power Transformer for Honeywell System Honeywell Valve Gas Valve for Honeywell System Honeywell Control Board Main Control Board for Honeywell Syst...

Page 90: ...ration to the product that causes soot or carbon to form and results in damage is not the responsibility of the manufacturer Do not modify or substitute any part of this appliance Inspect the external vent cap on a regular basis to make sure that no debris plants trees or shrubs are interfering with the air flow Do not operate the fireplace without the fireplace glass It is imperative that control...

Page 91: ...ify electronic ignition sparking sequence pilot operation and burner ignition Burner Maintenance The flames from the burner should be visually checked The flame should have a blue base and yellow tops and be candle like in appearance If excessive soot is found inside the firebox area the fireplace will require adjustment Verify the air shutter and vent restrictor setting and document any changes I...

Page 92: ...ead screw that can be turned to either increase or decrease the air to gas mixture See Ex 1 above for visual EX 2 The second option allows you to adjust your Flare Fireplaces air shutter by accessing it from directly underneath the fireplace See Ex 2 above for visual FOR CLARITY ON HOW YOUR ADJUSTMENTS IMPACT THE FLAME COLOR AND SOOTING PLEASE CLICK THIS LINK TO WATCH AN ELABORATE AIR SHUTTER VIDE...

Page 93: ...pany Name_________________________________________________________ Technician NPI ________________________________________________________ Service Information ___________________________________________________________ Yearly Maintenance _________________ Other __________________________ Details __________________________________________________________________________________ ____________________...

Page 94: ...rts include the following components Gas Valve Receiver Remote LED Lighting Strips Remote Controller Authorized Media Wall Switch This warranty does not apply to any component that shows evidence of misuse abuse improper installation exposure to water or moisture excessive heat dust or paint LIMITED FIVE YEAR COVERAGE Effective for five years from the original date of purchase Flare Fireplaces Lim...

Page 95: ...ler is unable to provide necessary parts contact the nearest Flare Fireplaces authorized dealer or supplier EXCLUSIONS This warranty does not apply to any component that shows evidence of misuse abuse improper installation accident or lack of maintenance Flare Fireplaces is not responsible for televisions mantels surrounds or finishing material around the fireplace Flare Fireplaces is not responsi...

Reviews: