39 |
P a g e
CHIMNEY PATH INSTALLATION AND PLANNING
Before vent installation, the installer should read these instructions to ensure the proper vent configuration has been selected.
To calculate the vent runs, use the following tables and instructions. Please note that power vent runs are model (burner)
specific. Use the tables below to calculate the restrictor setting. These fireplaces are designed and tested to function with natural
venting in equal pressure environments. The natural venting allows hot air and CO2 to rise and exhaust out through the vent
naturally while simultaneously creating a slight draft of oxygen to allow the flame to burn clean and efficiently. Please know that
if your installation environment presents negative or positive pressure, caused by strong HVAC systems or kitchen hoods, a
power vent system may be needed to counter this unique environment.
General Instructions
•
Diagonal runs have both vertical and horizontal vent aspects when calculating the effects. Use the rise for the
vertical aspect and the run for the horizontal aspect.
•
Various combinations of vent runs may be used. Refer to the tables below based on Fireplace size.
for clarification on how to use the table.
•
The numbers in the table represent the restrictor setting based on the vent path.
•
Symbol “x” in the table means the path is not allowed.
•
Setting the restrictor to 1 means there is no restriction.
•
Numbers in the table represent the restrictor setting to be set.
•
Document the restrictor setting configuration prior to leaving the installation site.
•
The tables apply to both NG (Natural Gas) and Propane.
•
Minimum 3 ft vertical run (A) required before any bend or turn.
o
See Flare Front and Flare See Through exception.
o
See Flare 50 & 60 5x8 table for exception
•
A maximum of
four
90º vent elbows are allowed in the vent run. Any configuration with more than 4 elbows
requires vent review and approval from Flare Fireplaces.
•
Two 45º elbows may be used in place of one 90º elbow.
•
The tables represent
the manufacturer’s guideline based on testing and design.
Additional external factors may
affect the restrictor choice needed. If flame appears to be not typical, please contact Flare Fireplaces for restrictor
size recommendations
•
Use the empty table in the page below to document and calculate the installation vent path.
•
Any venting pathway that does not appear the tables below require approval from Flare Fireplaces.
•
For optimum performance and flame appearance, keep the vent length to a minimum and limit the number of elbows.
WARNING
l) When an existing Category I heater is removed or replaced, the original venting system may no
longer be sized to properly vent the attached appliances. Instructions shall also indicate effects of
an improperly sized venting system (formation of condensate, leakage, spillage, etc.) and shall
specify the following test procedure.