Application Examples
Controlling NACs For Sync Follower Operation Using a Control Module
B.2 Controlling NACs For Sync Follower Operation Using a Control Module
In this application, the power supply has been set to operate in slave mode and will follow the sync signal from the FACP. This applica-
tion requires Input #1 to be controlled by the FACP sync output. Input #1 may be wired to the next FL-PS or terminate in and ELR. Input
#2 (or Input #3, if available) will act as the trigger signal for the output circuits. The control module can be powered by one of the FL-PS
output circuits, configured as aux power (24VDC). See Table 3.14 on page 27 DIP switch settings.
The following notes apply to Figure B.2.
•
When the FL-PS power supply is in an inactive state (control module not active), a trouble on the NAC circuits mapped to TB6 will
result in an open circuit condition on the control module output circuit (monitored by End-of-Line Resistor across TB6, Terminals 1
and 4). As an alternative, the trouble contacts at TB1 of the power supply can also be used for limited trouble monitoring excluding
faults reported by Command Input #2 related to Command Input#1 configured for Sync Input mode. Refer to Section 5 for more
information.
•
Refer to Section 3 for instructions on setting the DIP switches.
•
Output faults are reported via Command Input#2 with Command Input#1 configured for Sync Input mode operation.
•
Refer to the FACP manual for load restrictions and line length limitations when wiring multiple power supplies at the input.
•
Wire NACs as shown on page 13.
•
Do not loop wires under screw terminals. Break wires to maintain proper supervision.
•
An End-of-Line Resistor must be installed across all input circuits, Terminals 1 and 4, for control module wiring supervision (the
ELR value is dependent on the module/FACP employed).
•
For a list of compatible devices, refer to the
Fire•Lite Device Compatibility Document #
15384.
•
Refer to the
SLC Wiring Manual
for more information.
NO NC C
NO NC C
TB4
TB15
T
B
2
T
B
1
T
B
1
3
T
B
1
2
T
B
1
1
T
B
1
0
T
B
9
T
B
8
T1
T1
1
T2
T10
T3
T9
T4
T8
T5
T7
T6
Figure B.2 Controlling Multiple Outputs with One Input as Sync Follower
Control Module*
SLC
*If the SLC device does not match
the one in this figure, refer to the
SLC manual wiring conversion
charts for legacy and newer ver-
sions of the modules.
NAC Output Circuits
24VDC power output
NAC Sync
FACP
to next PS Series
Power Supply or ELR