FL-PS Series Instruction Manual —
P/N LS10227-001FL-E:B 3/29/2021
Section 3: Programming Options
This section describes the programming options available via DIP switch settings. The FL-PS can be field programmed using DIP
switches S1-S8 which are located at the bottom of the circuit board. S1 controls the global options of the power supply and S2-S8 control
the functions of each output circuit, respectively. Refer to the following illustration for switch locations and DIP switch placement in the
ON and OFF positions.
Important:
Activate output DIP switch changes by setting S1 positions 9 and 10 appropriately. Refer to Table 3.6 on page 24 for DIP
Switch programming settings.
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION AND OTHER INVOLVED
PARTIES
This product incorporates field-programmable software. In order for the product to comply with the requirements in the Standard for Control Units
and Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be limited to specific values or not used at all as
indicated below:
Program feature or
option
Permitted in
UL864/2572 and
ULC S527? (Y/N)
Possible settings
Settings
permitted in
UL 864 / UL2572
Settings
permitted in
ULC S527
Door Holder Dropout
Delay
Y
Refer to “AC Loss Door Holder Dropout Timer” on
page 24.
• Does not drop
• 15 seconds
• 5 minutes
• 60 seconds
• Does not drop
• 15 seconds
• 60 seconds
• 5 minutes
• Does not drop
• 15 seconds
• 60 seconds
• 5 minutes
AC Loss Delay Timer
Y
Refer to “AC Fail Indication Delay” on page 24.
• 30 hours
• 12 hours
• 2 hours
• none
• 2 hours
1
• none
1
A two hour delay is only permitted on an addressable FACP.
• 2 hours
• none
Table 3.1 Agency-Permitted Programming Settings
ON
1 2 3 4 5 6 7 8 9 10
ON
1 2 3 4 5 6 7 8
TB15
Switches 1 through 7 shown
in OFF (Open) position
Switch 8 shown in
ON (Closed) position
Figure 3.1 Field Programming DIP Switches
Switch 10 shown in
ON (Closed) position
Switches 1 through 9 shown
in OFF (Open) position
S1
S2-S8