background image

[10] Board Replacement
[10.1] Sensor Board Replacement

1.  Remove the two sensor board mounting screws.
2.  Pull gently on the board to remove it. 
3.  To replace the board, align the board mounting features, holes, and the interconnect terminals. Push the board 
 

into place.

4.  Secure board with the two mounting screws.

[10.2] Power Board Replacement

1.  Disconnect wiring from the terminal block.
2.  Remove the two power board mounting screws.
3.  Pull gently on the board to remove it. 
4.  To replace the board, align the board mounting features, holes, and the interconnect terminals. Push the board 
 

into place.

5.  Secure board with the two mounting screws.
6.  Re-connect wiring to terminal block.

[11] Model D350PL Air Duct Smoke Detector Specifications 

Operating Voltage Range 

15 to 32 VDC

Standby Current 

300 

µ

A @ 24 VDC (one communication every 5 seconds with LED blink enabled)

Operating Temperature Range 

32° to 131°F (0° to 55°C)

Storage Temperature Range 

-22° to 158°F (-30° to 70°C)

Humidity Range 

10% to 93% (non-condensing)

Air Velocity 

100 to 4000 ft/min (0.5 to 20.32 m/sec)

Dimensions 

14

3

8

 

 L x 5

1

2

 W x 2

3

4

 D (37 cm L x 14 cm W x 7 cm D)

Programming Specifications/Requirements for Intelligent System Control Panels
There are a limited number of devices that can have their LEDs programmed to illuminate. The actual number of devices is 
determined by the control panel and its ability to supply LED current. Refer to the Control Panel Installation Manual for details.

 

Accessories 

 

 

 

 

 

Part No.

 

Remote LED 

 

 

 

 

 

RA400Z

 

Magnetic Remote Test  

 

 

 

 

RTS451

 

Key-Activated Remote Test   

 

 

 

RTS451KEY

 

Replacement Filters  

 

 

 

F36-09-11

 

Replacement Test Magnet 

 

 

 

 

M02-04-00

 

Replacement Photo Insect Screen 

 

 

 

S08-39-01

 

Replacement End Cap for Plastic Sampling Tube   

 

P48-61-00

 

Replacement End Cap for Metal Sampling Tubes   

 

P48-21-00 

 

Replacement Photoelectric Sensor Board 

 

 

A5053FL

 

Replacement Power Board (w/o relay)   

 

 

A5067

F300-27-00 

I56-1975-004R 

© 2008 Fire • Lite Alarms

FCC Statement

This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this 

device must accept any interference received, including interference that may cause undesired operation.

Note:  This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to 

provide reasonable protection against harmful interference  in  a  residential  installation. This equipment generates, uses and can radiate radio frequency energy and, 

if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no  guarantee that interference 

will not occur in a particular installation. If  this equipment does cause harmful interference to radio or television reception, which  can be determined  by turning the 

equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:

 

 

– Reorient or relocate the receiving antenna.

 

 

– Increase the separation between the equipment and receiver.

 

 

– Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.

 

 

– Consult the dealer or an experienced radio/TV technician for help.

To keep your equipment in excellent working order, ongoing maintenance is required per the manufacturer’s recommendations and UL and NFPA standards. At a minimum, 

the requirements of Chapter 7 of NFPA 72, the National Fire Alarm Code, shall be followed. A preventative maintenance agreement should be arranged through the local 

manufacturer’s representative. Though smoke detectors are designed for long life, they may fail at any time. Any smoke detector, fire alarm equipment, or any component 

of that system which fails shall be repaired or replaced as soon as possible.

Please refer to insert for the Limitations of Fire Alarm Systems

Summary of Contents for FIre LIte ALarms D350PL

Page 1: ...vent the distribution or it can isolate toxic smoke and fire gases throughout the areas served by the duct system Two LEDs on each detector may illuminate if programmed by the system control panel to provide a local alarm indication There is also a remote alarm output for use with auxiliary devices The D350PL has remote test capability with the RTS451 RTS451KEY Remote Test Station CONTENTS OF THE ...

Page 2: ...ore than 8 feet 2 4m wide 4 Step 5 Install the filters 4 Step 6 Field wiring 4 Step 7 Perform detector check 5 Step 8 Install the cover 5 Step 9 Detector Maintenance and Test Procedures 5 1 Verify Duct Air Flow Direction And Velocity The D350PL duct smoke detector is designed to be used in air handling systems having air velocities of 100 to 4000 feet per minute 0 5 to 20 32m s Be sure to check en...

Page 3: ...or 2 Slide the tube into the housing bushing that meets the air flow first Position the tube so that the arrow points into the air flow as shown in Figure 4 3 Secure the tube flange to the housing bushing with two 6 self tapping screws 4 For tubes longer than the width of the air duct the tube should extend out of the opposite side of the duct If there are more than 2 holes in the section of the t...

Page 4: ...pling and exhaust tube holes as shown in Figure 6 If a metal sampling tube is used install the filters over the tube end F300 27 00 4 I56 1975 004R Figure 6 Sampling tube filter installation 6 Field Wiring Installation Guidelines All wiring must be installed in compliance with the National Electrical Code and the local codes having jurisdiction Proper wire gauges should be used The conductors used...

Page 5: ...s 9 Duct Smoke Detector Maintenance and Test Procedures Test and maintain duct smoke detectors as recommended in NFPA 72 The tests con tained in this manual were devised to assist maintenance personnel in verification of proper detector operation Before conducting these tests notify the proper authorities that the smoke detection system will be temporarily out of service Disable the device or syst...

Page 6: ...nce even when up to 90 of the filter is clogged Quarterly visual inspection usually suffices to determine whether the filters should be replaced because only a high percentage of contamination affects performance If further testing is required compare differential pressure readings with and without the filters installed If the difference exceeds 10 replace the filters In no case should the pressur...

Page 7: ...ove and inspect sampling tube filters 3 If filters are heavily coated with dirt replace them with new filters p n F36 09 11 If they are not heavily coated use a vacuum cleaner or compressed air nozzle to remove dust then reinstall the filters 9 3 2 Photo Detector Boards 1 Remove the screen by gently grasping on each side and pulling straight off 2 Lift the photo chamber in the same fashion Vacuum ...

Page 8: ...lay A5067 F300 27 00 8 I56 1975 004R 2008 Fire Lite Alarms FCC Statement This device complies with part 15 of the FCC Rules Operation is subject to the following two conditions 1 This device may not cause harmful interference and 2 this device must accept any interference received including interference that may cause undesired operation Note This equipment has been tested and found to comply with...

Reviews: