background image

[9.1.3] Smoke Entry Test

To  determine  if  smoke  is  capable  of  entering  the  sensing  chamber,  visually  identify  any  obstructions.  Plug  the  exhaust  and  sampling  tube  holes 
to  prevent  ducted  air  from  carrying  smoke  away  from  the  detector  head,  then  blow  smoke  such  as  cigarette,  cotton  wick,  or  punk  directly  at  the 
head to cause an alarm. REMEMBER TO REMOVE THE PLUGS AFTER THIS TEST, OR THE DETECTOR WILL NOT FUNCTION PROPERLY.

 

 

[9.1.4] Air Flo Test Using Dwyer Series 607 Differential Pressure Transmitter

Verify the air speed of the duct using an anemometer. Air speed must be at least 100 FPM. Wire the Dwyer transmitter as shown in Figure 8. Connect 
the leads of the meter to either side of the 1000

Ω

 resistor. Allow unit to warm up for 15 seconds. With both HIGH and LOW pressure ports open to 

ambient air, measure and record the voltage drop across the 1000

Ω

 resistor (measurement 1), 4.00 volts is typical. Using flexible tubing and rubber 

stoppers, connect the HIGH side of the transmitter to the sampling tube of the duct smoke detector housing, and the LOW side of the transmitter to 
the exhaust tube of the duct smoke detector housing. Measure and record the voltage drop across the 1000

Ω

 resistor (measurement 2). Subtract the 

voltage recorded in measurement 1 from the voltage recorded in measurement 2. If the difference is greater than 0.15 volts, there is enough air flow 
through the duct smoke detector for proper operation.

[9.1.5] Filter Replacement

The filters do not substantially affect smoke performance even when up to 90% of the filter is clogged. Quarterly visual inspection usually suffices to 
determine whether the filters should be replaced because only a high percentage of contamination affects performance. If further testing is required, 
compare differential pressure readings with and without the filters installed. If the difference exceeds 10% replace the filters. In no case should the 
pressure differential fall below 0.0015 inches of water.
 

[9.2.1] Standby Alarm, And Sensitivity Tests
[9.2.1] Standby And Trouble

Standby — 

If programmed by the system control panel, look for the presence of the flashing LEDs through the transparent housing cover.  The 
LED will flash with each communication. 

Trouble — 

If programmed by the system control panel and the detector LEDs do not flash, then the detector lacks power (check wiring, panel 
programming, or power supply), the detector board is missing (replace), or the unit is defective (return for repair).

Test — 

The trouble condition can be caused intentionally to verify correct operation of the system. Remove the detector board to cause a 
trouble condition locally and at the system control panel.

F300-27-00 

I56-1975-004R

Figure 8. Procedure for verifying air flow:

HIGH

LOW

9 VOLT

BATTERY

9 VOLT

BATTERY

9 VOLT

BATTERY

TO SAMPLING TUBE
TO EXHAUST TUBE

DIFFERENTIAL 

PRESSURE 

TRANSMITTER 

MODEL #607-01

15 TO 36 

VDC SUPPLY

1000 OHM 5%

1 WATT RESISTOR

VOLT METER FLUKE 

MODEL 87 OR 

EQUIVALENT

+

Figure 9. Wiring Diagram for D350PL Duct Smoke Detector using a UL listed control panel

TEST

RA400Z

R

T

S451

KEY

COMMON

COM(+)

COM(–)

TEST

RA400Z

R

T

S451

KEY

COMMON

COM(+)

COM(–)

+

COM (+) COM (–)

COM (+) COM (–)

1ST DETECTOR

IN LOOP

2ND DETECTOR

IN LOOP

COMM.

LINE

UL LISTED 

CONTROL 

PANEL

H0105-00

H0136-01

Summary of Contents for FIre LIte ALarms D350PL

Page 1: ...vent the distribution or it can isolate toxic smoke and fire gases throughout the areas served by the duct system Two LEDs on each detector may illuminate if programmed by the system control panel to provide a local alarm indication There is also a remote alarm output for use with auxiliary devices The D350PL has remote test capability with the RTS451 RTS451KEY Remote Test Station CONTENTS OF THE ...

Page 2: ...ore than 8 feet 2 4m wide 4 Step 5 Install the filters 4 Step 6 Field wiring 4 Step 7 Perform detector check 5 Step 8 Install the cover 5 Step 9 Detector Maintenance and Test Procedures 5 1 Verify Duct Air Flow Direction And Velocity The D350PL duct smoke detector is designed to be used in air handling systems having air velocities of 100 to 4000 feet per minute 0 5 to 20 32m s Be sure to check en...

Page 3: ...or 2 Slide the tube into the housing bushing that meets the air flow first Position the tube so that the arrow points into the air flow as shown in Figure 4 3 Secure the tube flange to the housing bushing with two 6 self tapping screws 4 For tubes longer than the width of the air duct the tube should extend out of the opposite side of the duct If there are more than 2 holes in the section of the t...

Page 4: ...pling and exhaust tube holes as shown in Figure 6 If a metal sampling tube is used install the filters over the tube end F300 27 00 4 I56 1975 004R Figure 6 Sampling tube filter installation 6 Field Wiring Installation Guidelines All wiring must be installed in compliance with the National Electrical Code and the local codes having jurisdiction Proper wire gauges should be used The conductors used...

Page 5: ...s 9 Duct Smoke Detector Maintenance and Test Procedures Test and maintain duct smoke detectors as recommended in NFPA 72 The tests con tained in this manual were devised to assist maintenance personnel in verification of proper detector operation Before conducting these tests notify the proper authorities that the smoke detection system will be temporarily out of service Disable the device or syst...

Page 6: ...nce even when up to 90 of the filter is clogged Quarterly visual inspection usually suffices to determine whether the filters should be replaced because only a high percentage of contamination affects performance If further testing is required compare differential pressure readings with and without the filters installed If the difference exceeds 10 replace the filters In no case should the pressur...

Page 7: ...ove and inspect sampling tube filters 3 If filters are heavily coated with dirt replace them with new filters p n F36 09 11 If they are not heavily coated use a vacuum cleaner or compressed air nozzle to remove dust then reinstall the filters 9 3 2 Photo Detector Boards 1 Remove the screen by gently grasping on each side and pulling straight off 2 Lift the photo chamber in the same fashion Vacuum ...

Page 8: ...lay A5067 F300 27 00 8 I56 1975 004R 2008 Fire Lite Alarms FCC Statement This device complies with part 15 of the FCC Rules Operation is subject to the following two conditions 1 This device may not cause harmful interference and 2 this device must accept any interference received including interference that may cause undesired operation Note This equipment has been tested and found to comply with...

Reviews: