Honeywell FIre LIte ALarms D350PL Installation And Maintenance Instructions Manual Download Page 5

Two LEDs on each duct smoke detector may light, if programmed by the system control panel, to provide a local, visible indication.  Remote LED 
annunciator capability is available as an option. Each duct smoke detector can only be wired to one remote accessory.

Fire•Lite panels offer different feature sets across different panel models.  As a result, certain features of the D350PL may be available on some control 

panels, but not on others.  The possible features available in the D350PL, if supported by the control panel are:  
1.  Panel controls the LED operation on the duct smoke detector.  Operational modes are RED blink, RED continuous, GREEN blink, GREEN continu-

ous, and off.  

2.  The remote output may be synchronized to the LED operation or controlled independent of the LEDs. 

Please refer to the operation manual for the UL listed control panel for specific operation of the D350PL  

WIRING INSTRUCTIONS  

Disconnect power from the communication line before installing the D350PL duct smoke detectors.  

Wire the D350PL duct smoke detector per the Control Panel Installation Manual and Figures 9, 10 or 11. Set the desired address on the sensor board 
code wheel address switches.

NOTE:  Some panels support extended addressing. In order to set the sensor above address number 99 on compatible systems, carefully remove 

the stop on the left hand rotary switch with pliers as shown in Figure 7.

[7] Perform Detector Check 
1.  Perform STANDBY AND TROUBLE TEST per Section [9.2.1].
2.  Perform MAGNET TEST per Section [9.2.2.1]. The RTS451 test of Section [9.2.2.2] may substitute for this requirement. 
3.  Perform AIR FLOW TEST per Section [9.1].
4.  Perform SMOKE RESPONSE TEST per Section [9.1.1].

[8] Install The Cover 
Install the cover using the six screws that are captured in the housing cover. Be certain 
filters are installed as specified in Section [5]. Make sure that the cover fits into the base 
groove and that all gaskets are in their proper positions. Tighten the six screws.

[9] Duct Smoke Detector Maintenance and Test Procedures
Test  and  maintain  duct  smoke  detectors  as  recommended  in  NFPA  72. The  tests  con-
tained  in  this  manual  were  devised  to  assist  maintenance  personnel  in  verification  of 
proper detector operation. 

Before conducting these tests, notify the proper authorities that the smoke detection system will be temporarily out of service. Disable the device or 
system under test to prevent unwanted alarms.

9.1] Smoke Entry Tests

[9.1.1] Air Flow

This product is designed to operate over an extended air speed range of 100 to 4000 FPM. To verify sufficient sampling of ducted air, turn the air han-
dler on and use a manometer to measure the differential pressure between the two sampling tubes. The differential pressure should measure at least 
0.0015 inches of water and no more than 1.2 inches of water. Because most commercially available manometers cannot accurately measure very low 
pressure differentials, applications with less than 500 FPM of duct air speed may require one of the following: 1) the use of a current-sourcing pressure 
transmitter (Dwyer Series 607) per Section 9.1.4 or; 2) the use of aerosol smoke per section 9.1.2.

[9.1.2] Air Flow Test using Aerosol Smoke

This test is intended for low-flow systems (100-500 FPM). If the air speed is greater than 500 FPM, use a conventional manometer to measure differ-
ential pressure between the sampling tubes, as described in 9.1.1.

Drill  a 

1

4

  hole  3  feet  upstream  from  the  duct  smoke  detector.  With  the  air  handler  on,  measure  the  air  velocity  with  an  anemometer.  Air  speed 

must  be  at  least  100  FPM.  Spray  aerosol  smoke*  into  the  duct  through  the 

1

4

  hole  for  five  seconds.  Wait  two  minutes  for  the  duct  smoke 

detector  to  alarm.  If  the  duct  smoke  detector  alarms,  air  is  flowing  through  the  detector.  Remove  the  duct  smoke  detector  cover  and  blow 
out  the  residual  aerosol  smoke  from  the  chamber  and  reset  the  duct  smoke  detector.  Use  duct  tape  to  seal  the  aerosol  smoke  entry  hole. 
*Aerosol smoke can be purchased from Home Safeguard Industries, Malibu, CA. Phone: 310/457-5813.

F300-27-00 

I56-1975-004R

BREAKAWAY STOP

Figure 7. Rotary Address Switches

H0138-00

Summary of Contents for FIre LIte ALarms D350PL

Page 1: ...vent the distribution or it can isolate toxic smoke and fire gases throughout the areas served by the duct system Two LEDs on each detector may illuminate if programmed by the system control panel to provide a local alarm indication There is also a remote alarm output for use with auxiliary devices The D350PL has remote test capability with the RTS451 RTS451KEY Remote Test Station CONTENTS OF THE ...

Page 2: ...ore than 8 feet 2 4m wide 4 Step 5 Install the filters 4 Step 6 Field wiring 4 Step 7 Perform detector check 5 Step 8 Install the cover 5 Step 9 Detector Maintenance and Test Procedures 5 1 Verify Duct Air Flow Direction And Velocity The D350PL duct smoke detector is designed to be used in air handling systems having air velocities of 100 to 4000 feet per minute 0 5 to 20 32m s Be sure to check en...

Page 3: ...or 2 Slide the tube into the housing bushing that meets the air flow first Position the tube so that the arrow points into the air flow as shown in Figure 4 3 Secure the tube flange to the housing bushing with two 6 self tapping screws 4 For tubes longer than the width of the air duct the tube should extend out of the opposite side of the duct If there are more than 2 holes in the section of the t...

Page 4: ...pling and exhaust tube holes as shown in Figure 6 If a metal sampling tube is used install the filters over the tube end F300 27 00 4 I56 1975 004R Figure 6 Sampling tube filter installation 6 Field Wiring Installation Guidelines All wiring must be installed in compliance with the National Electrical Code and the local codes having jurisdiction Proper wire gauges should be used The conductors used...

Page 5: ...s 9 Duct Smoke Detector Maintenance and Test Procedures Test and maintain duct smoke detectors as recommended in NFPA 72 The tests con tained in this manual were devised to assist maintenance personnel in verification of proper detector operation Before conducting these tests notify the proper authorities that the smoke detection system will be temporarily out of service Disable the device or syst...

Page 6: ...nce even when up to 90 of the filter is clogged Quarterly visual inspection usually suffices to determine whether the filters should be replaced because only a high percentage of contamination affects performance If further testing is required compare differential pressure readings with and without the filters installed If the difference exceeds 10 replace the filters In no case should the pressur...

Page 7: ...ove and inspect sampling tube filters 3 If filters are heavily coated with dirt replace them with new filters p n F36 09 11 If they are not heavily coated use a vacuum cleaner or compressed air nozzle to remove dust then reinstall the filters 9 3 2 Photo Detector Boards 1 Remove the screen by gently grasping on each side and pulling straight off 2 Lift the photo chamber in the same fashion Vacuum ...

Page 8: ...lay A5067 F300 27 00 8 I56 1975 004R 2008 Fire Lite Alarms FCC Statement This device complies with part 15 of the FCC Rules Operation is subject to the following two conditions 1 This device may not cause harmful interference and 2 this device must accept any interference received including interference that may cause undesired operation Note This equipment has been tested and found to comply with...

Reviews: