background image

[4] Sampling Tube Installation for Ducts Greater Than 1

1

Feet 

(0.46m) Wide

The sampling tube is identified by a series of air inlet holes on the tube. 
A plastic tube is included for ducts up to 1

1

2

 feet (0.46m) wide. All other 

lengths  must  be  purchased  separately.  Order  the  correct  length,  as 
specified in Table 1, for width of the duct where it will be installed. It is 
recommended that the sampling tube length extend at least 

2

3

 across the 

duct width for optimal performance. The exhaust tube is molded onto the 
base of the duct housing, and the A2440-00 Exhaust Tube Extension is 
available as an accessory in those cases where the molded exhaust port 
does not extend at least 2 inches into the duct. 

The sampling tube is always installed with the air inlet holes facing into 
the  air  flow.  To  assist  proper  installation,  the  tube’s  mounting  flange  is 
marked with an arrow. Make sure the sampling tube is mounted so that 
the  arrow  points  into  the  air  flow  (see  Figure  4).  Figure  5  shows  the 
various combinations of tube mounting configurations with respect to air 
flow. Mounting the detector housing in a vertical orientation is acceptable, 
provided that a metal sampling tube is used and the air flows directly into 
the sampling tube holes as indicated in Figure 4.

[4.1] Installation For Ducts Greater Than 1

1

2

 Feet (0.46m) But 

Less Than 8 Feet (2.4m) Wide

1.  If the tube is longer than the width of the air duct, drill a 

3

4

 (19mm) hole 

in the duct opposite the hole already cut for the sampling tube. Make 
sure  the  hole  is  1

  to  2

  (25  to  50  mm)  below  the  sampling  hole  on 

the opposite side of the duct to allow moisture drainage away from the 
detector. If the tube is shorter than the width of the air duct, install the 
end cap into the sampling tube as shown in Figure 4. Sampling tubes 
over 3 ft. (0.91m) long must be supported at the end opposite the duct 
smoke detector.

2.  Slide the tube into the housing bushing that meets the air flow first. 

Position the tube so that the arrow points into the air flow, as shown 
in Figure 4. 

3.  Secure the tube flange to the housing bushing with two #6 self-tapping 

screws.

4.  For tubes longer than the width of the air duct, the tube should extend 

out of the opposite side of the duct. If there are more than 2 holes in the 
section of the tube extending out of the duct, select a different length 
using Table 1. Otherwise, trim the end of the tube protruding through 
the duct so that 1

 to 2

 (25 to 50mm) of the tube extend outside the 

duct. Plug this end with the end cap and tape closed any holes in the 
protruding section of the tube. Be sure to seal the duct where the tube 
protrudes.

NOTE: The sampling tube end cap is critical to the proper operation of 

the duct smoke detectors. The end cap is needed to create the 
proper air flow to the sensor of the duct smoke detector.

F300-27-00 

I56-1975-004R

SCREW HOLES FOR

ATTACHING HOUSING

TO DUCT WORK.

Figure 3. Installation of foam gaskets over sampling 
tube bushings:

Figure 5. Tube mounting configurations with varying 
air flow direction:

Table 1. Sampling tubes recommended for different 
duct widths:

 

Outside Duct Width           Sampling Tube Recommended*

 

1 to 2 ft. (0.3 to 0.6 m) 

ST-1.5

 

2 to 4 ft. (0.6 to 1.2 m) 

ST-3

 

4 to 8 ft. (1.2 to 2.4 m) 

ST-5

 

8 to 12 ft. (2.4 to 3.7 m) 

ST-10

*Must extend a minimum of 

2

3

 the duct width.

SAMPLING

TUBE

END CAP

AIR HOLES

ARROW

MUST FACE

INTO AIR FLOW

AIR FLOW DIRECTION

FLANGE

Figure 4. Air duct detector sampling tube:

H0108-02

AIR FLOW

DIRECTION

DETECTOR

HOUSING

DOTS INDICATE POSITION OF SAMPLING TUBE HOLES

AIR FLOW

DIRECTION

DETECTOR

HOUSING

SAMPLING

TUBE

EXHAUST

TUBE

AIR FLOW

DIRECTION

EXHAUST

TUBE

SAMPLING

TUBE

SAMPLING

TUBE

EXHAUST

TUBE

DETECTOR

HOUSING

AIR FLOW

DIRECTION

DETECTOR

HOUSING

A.

B.

C.

D.

HORIZONTAL MOUNTING OF HOUSING

VERTICAL MOUNTING OF HOUSING

NOTE: ONLY METAL SAMPLING TUBES CAN BE INSTALLED IN ORIENTATIONS C AND D.

NOTE:  Only metal sampling tubes can be installed in 
 

orientations C and D. 

H0107-00

H0109-01

Summary of Contents for FIre LIte ALarms D350PL

Page 1: ...vent the distribution or it can isolate toxic smoke and fire gases throughout the areas served by the duct system Two LEDs on each detector may illuminate if programmed by the system control panel to provide a local alarm indication There is also a remote alarm output for use with auxiliary devices The D350PL has remote test capability with the RTS451 RTS451KEY Remote Test Station CONTENTS OF THE ...

Page 2: ...ore than 8 feet 2 4m wide 4 Step 5 Install the filters 4 Step 6 Field wiring 4 Step 7 Perform detector check 5 Step 8 Install the cover 5 Step 9 Detector Maintenance and Test Procedures 5 1 Verify Duct Air Flow Direction And Velocity The D350PL duct smoke detector is designed to be used in air handling systems having air velocities of 100 to 4000 feet per minute 0 5 to 20 32m s Be sure to check en...

Page 3: ...or 2 Slide the tube into the housing bushing that meets the air flow first Position the tube so that the arrow points into the air flow as shown in Figure 4 3 Secure the tube flange to the housing bushing with two 6 self tapping screws 4 For tubes longer than the width of the air duct the tube should extend out of the opposite side of the duct If there are more than 2 holes in the section of the t...

Page 4: ...pling and exhaust tube holes as shown in Figure 6 If a metal sampling tube is used install the filters over the tube end F300 27 00 4 I56 1975 004R Figure 6 Sampling tube filter installation 6 Field Wiring Installation Guidelines All wiring must be installed in compliance with the National Electrical Code and the local codes having jurisdiction Proper wire gauges should be used The conductors used...

Page 5: ...s 9 Duct Smoke Detector Maintenance and Test Procedures Test and maintain duct smoke detectors as recommended in NFPA 72 The tests con tained in this manual were devised to assist maintenance personnel in verification of proper detector operation Before conducting these tests notify the proper authorities that the smoke detection system will be temporarily out of service Disable the device or syst...

Page 6: ...nce even when up to 90 of the filter is clogged Quarterly visual inspection usually suffices to determine whether the filters should be replaced because only a high percentage of contamination affects performance If further testing is required compare differential pressure readings with and without the filters installed If the difference exceeds 10 replace the filters In no case should the pressur...

Page 7: ...ove and inspect sampling tube filters 3 If filters are heavily coated with dirt replace them with new filters p n F36 09 11 If they are not heavily coated use a vacuum cleaner or compressed air nozzle to remove dust then reinstall the filters 9 3 2 Photo Detector Boards 1 Remove the screen by gently grasping on each side and pulling straight off 2 Lift the photo chamber in the same fashion Vacuum ...

Page 8: ...lay A5067 F300 27 00 8 I56 1975 004R 2008 Fire Lite Alarms FCC Statement This device complies with part 15 of the FCC Rules Operation is subject to the following two conditions 1 This device may not cause harmful interference and 2 this device must accept any interference received including interference that may cause undesired operation Note This equipment has been tested and found to comply with...

Reviews: