FIGURE 3. QUADRATIC TOTAL CURRENT LIMIT 

107137-20 -EN  FR26  GLO  305  Printed in Germany

 

20

40

60

80

100

120

0

10

20

30

40

50

60

T (˚C)

32

50

68

86

104

122

140

T (˚F)

Ambient temperature

Quadratic total current (A

2

)

I

2

 (A

2

)

 

 

 
Figure 3 shows the maximal recommended safety 
contact currents at a certain ambient temperature to 
avoid overheating of the safety module. 
 
To use this curve, do the following: 
1.  Square the currents in each safety contact branch 

and sum the square currents to obtain the total 
square limit (in A²). 

2.  Determine the maximal recommended external 

temperature at the total square current limit: 

 
Example: 5 A current per normally open contact:  
Total square current limit :  

 

Ι

2

 

 = (5A)

2

 + (5A)

2

+ (5A)

2  

+

 

(5A)

=

 

100 A² 

Max. external temperature: T = 39 

°

C (102 

°

F). 

 
If the module is located in a higher temperature 
environment, the lifetime of the electronic components 
may be reduced. Ventilation of the cabinet may be 
required.

 

 
MECHANICAL INSTALLATION  

The FF-SRE6029  must be installed inside an IEC IP 54 
(NEMA 3) rating enclosure or better. The module can be 
clipped easily onto a 35 mm (1.38 in.) width rail (see 
figure 5 for installation and removal).  

 

FIGURE 4. MOUNTING DIMENSIONS  

(

for reference only)

 

 

Rail

c

b

a

 

 

a  Width: 22,5 mm / 0.89 in. 
b  Height: 90 mm / 3.55 in. 
c  Depth:  121 mm  4.77 in.

 

FIGURE 5. INSTALLATION DIAGRAM 

 

FSR1 

FSR

E

5929

 
CONTROL RELIABILITY 

“Control Reliability” essentially means that “the device, 
system or interface shall be designed, constructed and 
interfaced such that any single component failure within 
the device, interface or system shall not prevent normal 
stopping action from beeing applied but shall prevent the 
initiation of a successive operation until the failure is 
corrected”. 
OSHA 29 CFR 1910.217 states that “the device shall be 
constructed so that a failure within the system does not 
prevent the normal stopping action from being applied to 
the press when required, but does prevent initiation of a 
successive stroke until the failure is corrected. The 
failure shall be indicated by the system.” 
 

SAFETY CATEGORY OF INTERFACES 

The safety category of the interface is depending on the 
safety category of the main safety device (emergency 
stop module, safety light curtain, safety mat, etc.) and 
the way of interconnecting it to the FF-SRE6029 
Extension module.  
 

Refer to the important application warnings (page 5) 
for more details concerning safety. 
 

FIGURE 6. INTERNAL CIRCUITRY  

 

13 23 33 43

51

Y1

M8561

14 24 34 44

52

Y2

A1(+) A2(-)

A3(+) A4(-)

K1

K2

24V

24V

 

AL6029 

Summary of Contents for FF-SRE6029

Page 1: ...masterelectronics com onlinecomponents com are authorized e commerce distributors of electronic components See full Datasheet below BUY NOW BUY NOW HONEYWELL FF SRE60292 ...

Page 2: ...PROVALS CE The product packaging and documentation of FF SR Series products carry the CE mark the CE declaration of conformity is attached on the last page cURus pending This product is currently being assessed by Underwriters Laboratories Inc according to Canadian and U S safety requirements DIRECTIVE COMPLIANCE Machinery Directive 98 37 EC Low Voltage Directive 73 23 EC Electromagnetic Compatibi...

Page 3: ...e 15 C to 55 C 5 F to 131 F at 90 humidity max Sealing Housing IP 40 Terminals IP 20 Housing material Thermoplastic Vibration resistance IEC EN 60 068 2 6 Amplitude 0 35 mm Frequency 10 to 55 Hz Wire connection Solid wire 1 x 4 mm 2 12 AWG or 2 x 2 5 mm 2 14 AWG Stranded wire with sleeve 1 x 2 5 mm 2 14 AWG or 2 x 1 5 mm 2 16 AWG Wire conductor attachment M3 5 screw terminals Mounting Quick instal...

Page 4: ...oval FIGURE 4 MOUNTING DIMENSIONS for reference only Rail c b a a Width 22 5 mm 0 89 in b Height 90 mm 3 55 in c Depth 121 mm 4 77 in FIGURE 5 INSTALLATION DIAGRAM FSR1 FSRE5929 6 CONTROL RELIABILITY Control Reliability essentially means that the device system or interface shall be designed constructed and interfaced such that any single component failure within the device interface or system shal...

Page 5: ...the machine control circuitry by the module s safety contacts to stop the hazard and remove power As soon as the safety device is released power is applied to A1 A2 A3 A4 and the relays K1 and K2 energise The normally open contacts will close and the normally closed contact will open Both relays K1 and K2 must be energized to have the normally open contacts in a closed condition If one of the safe...

Page 6: ...t the FF SRE6029 extension module to safety devices WITHOUT the EDM function e g FF SYA FF SG FF SLG or FF SLG30 The External Device Monitoring EDM function checks the correct operation of the internal relays before each FF SRE6029 activation and is able to detect failures of the internal relays e g welded safety relay contacts ALWAYS connect the normally closed contact Y1 Y2 of the extension modu...

Page 7: ... The normally open contacts will close and the normally closed contacts will open The LED relay output indicators all illuminate This action will allow the machine to operate FSRE6029_12 APPLICATION NOTES Note A Dual channel output safety devices with relay outputs or safety switches examples This may be a safety device with dual output safety switching devices OSSD emergency stop push button safe...

Page 8: ...acts of the FF SRE6029 module will close and the normally closed contacts will open The LED relay output indicators K1 and K2 illuminate This action will allow the machine to operate FSRE6029_13 APPLICATION NOTES Note A Dual channel output safety devices with static safety outputs AND External Device Monitoring EDM function e g FF SYB safety light curtains Note B CONFIGURATION CARDS Various mode s...

Page 9: ...heck for external causes wiring etc Damaged contacts Ensure maximum load is specification Replace module Are the outputs contacts 13 14 43 44 closed Are K1 AND K2 LEDs OFF Are the contacts 51 52 AND Y1 Y2 closed Replace safety module and activate restart circuitry Is voltage between A1 A2 AND A3 A4 present AND within specifications Yes Machine Working Is the problem resolved No Yes Yes No No No wi...

Page 10: ...nd through our literature and the Honeywell Website it is up to the customer to determine the suitability of the product in the application Specifications may change at any time without notice The information we supply is believed to be accurate and reliable as of this printing However we assume no responsibility for its use TELEPHONE 61 0 2 9370 4500 Australia 33 0 1 60 19 80 40 France 49 0 69 80...