4 FDAP CONFIGURATION
52
3.
On the Property Panel, expand
Register Configuration.
4.
Configure the following under each
Register Config:
•
Slave Addr
: Slave Address
•
Register Addr
:
Register Address
•
Function:
Select required function option from the dropdown list.Options include:
Input Register,
Holding Register
,
Coil
and
Discrete Registers.
•
Data Type:
Select required datat type option from the dropdown list. Options include:
INT16, INT32,
UINT16, UINT32, Float
and
Boolean.
5.
Click
Apply
.
To view the configured Modbus Registers
1.
On the Selection Panel, select
Modbus Register Values
.
2.
On the Property Panel, expand
Register Values.
3.
Now, you can view the respective register values as shown below.