EP03-300-200
December,
2003
Release 200
Version 1.0
Experion PKS CEE-based Controller Specifications and Models
17
ControlNet Specifications
Table 4. 9904-KTCX15, TC-PCIC01, TC-CCN013, TC-CCR013, TK-CCR013
Parameter
Specification
Data rate
5 Mbit/sec
Redundancy
Single cable or redundant operation supported
ControlNet Components
End devices (workstations and controllers), taps, trunk cable, cable
connectors, terminators, segments, repeaters, and bridges.
Cable Type and Topology
RG-6 Quad Shield cable, BNC connectors, trunk & drop, bus
topology. See next page for recommended cable types.
Cable Type by Application
•
Light industrial applications
•
Heavy industrial applications
•
High and low temperature applications,
as well as corrosive (harsh) areas
•
Moisture Resistant (direct burial,
flooding, etc.)
•
Standard PVC CM-CL2
•
Lay-on Armored and Interlocking Armor
•
Plenum FEP CMP-CL2P
•
Flood burial
Maximum Distance and Total
number of Repeaters Between any
two (2) Nodes
•
Maximum Coax plus Fiber length of 10 km
•
Maximum of 5 Repeaters (6 Segments)
•
Maximum Coax Segment Length
•
Maximum Fiber Segment Length
•
1000 m (3280 ft.) - 16.3 m (53.4 ft.) x [number of Taps - 2]
•
See Repeater Specifications below
Maximum Total Length Differential
Between A and B Trunk
•
800 m (2624 ft.) (total link)
Fiber Optic Repeater Specifications – TC-RPA002, TC-RPRS01, TC-RPFM01
Mounting
DIN rail mountable (35 mm wide rail)
Maximum number of Fiber Modules per
TC-RPA002 ControlNet Module Adapter
Four (2 ports/module)
Power Requirements (TC-RPA002)
24 VDC, 700 mA maximum
Fiber Optic Repeater Model
TC-RPFS01 (300 M)
TC-RPFM01 (3000 M)
Optical power budget
4.2 dB
9.3 dB
Cable wavelength specification
650
η
m (red)
1300
η
m
Fiber Type
200
µ
m glass (HCM)
62.5
µ
m
Fiber Termination Type
Versalink
ST Termination
Maximum fiber optic segment distance is dependentupon the quality of the fiber, number of splices, and connectors. For more
ControlNet topology information, refer to the Planning Guide in Knowledge Builder or to EP-DCXX21.
Loc al ControlNet Trunk
R1
T1
R 2
T2
TC- RPA001
TC- RPFM01
R1 T1
R2 T2
Remote ControlNet Trunk
Tap
Fiber Segments -- 3 Km m ax each
24 Vdc
TC- RPA001
R1
T1
R2
T2
TC- RPFM01
R1 T1
R2 T2
24 Vdc
Tap
R 1
T1
R 2
T2
TC- RPA001
TC- RPFM01
R1
T1
R2 T2
24 Vdc
R 1
T1
R2
T2
TC- RPFM01
R1
T1
R2 T2
Figure 3. ControlNet Fiber Optic Example -- Use of 2 Fiber Segments to