STRYKER CVAHU ZIO CONFIGURATION GUIDE
45
AO3
(Analog output3 range configuration)
Figure 81: Parameter AO3 Range
RANGE:
Displays and allows modification of analog
output3 range. This can be changed as 0D10, 10D0,
2D10, 10D2, 0A20, 20A0, 0A22, 22A0, 4A20, 20A4,
DIG, and UNDEFINED.
Default Parameter setting:
UNDEFINED
Configuration settings in program are as follows:
0 = 0D10 (Analog voltage 0 to 10VDC direct
output)
1 = 10D0 (Analog voltage 0 to 10VDC reverse
output)
2 = 2D10 (Analog voltage 2 to 10VDC direct
output)
3 = 10D2 (Analog voltage 2 to 10VDC reverse
output)
4 = 0A20 (Analog current 0 to 20 mA direct output)
5 = 20A0 (Analog current 0 to 20 mA reverse
output)
6 = 0A22 (Analog current 0 to 22 mA direct output)
7 = 22A0 (Analog current 0 to 22 mA reverse
output)
8 = 4A20 (Analog current 4 to 20 mA direct output)
9 = 20A4 (Analog current 4 to 20 mA reverse
output)
10 = DIG (Analog as binary output)
255 = UNDEFINED