STRYKER CVAHU ZIO CONFIGURATION GUIDE
21
Sensors
(CVAHU sensor value display)
Click the
PARAMETERS
soft key to display the first
configured category
‘SENSORS’
. Within this
category, one sample Zio display is shown for
reference and the remaining parameters are available
for view only as per the following order.
Following is the path to access the screen as shown
in
CONTRACTOR>PARAMETERS>SENSORS>ZIO
TEMP
Figure 16: Parameters Sensors Zio Temp
Click
CANCEL
to return to
SENSORS.
SENSOR
is parameter group for this parameter.
Click
NEXT
to access parameters in the following
sequence.
ZIO TEMP:
Display Zio temperature which
corresponds to the onboard temperature sensor and
is an output of the Sbus wall module function block.
ZIO HUMIDITY:
Displays Zio humidity (%) sensor
from wall module
ROOMTEMP:
Displays room temperature and is an
input to the Sbus wall module function block.
RH:
Displays room relative humidity (%) and is an
input to the Sbus wall module function block.
CO
2
:
Displays room CO
2
(PPM)
and is an input to the
Sbus wall module function block.
DISCHRG:
Displays discharge air temperature and is
an input to the Sbus wall module function block.
OAT:
Displays outside air temperature and is an input
to the Sbus wall module function block.
OAH:
Displays outside air humidity (%) and is an
input to the Sbus wall module function block.
OCC SNSR:
Displays occupancy sensor and is an
input to the Sbus wall module function block.
Status is displayed as follows
OCC, UNOC, BYPS, STBY, UNDEFINED
Configuration settings in program are as follows:
0 = OCC (Occupancy Mode)
1 = UNOC (UN occupancy Mode)
2 = BYPS (Bypass Mode
3 = STBY (Standby Mode)
4 = UNDEFINED
WINDOW:
Displays window open/closed contact
status and is an input to the Sbus wall module
function block.
Status is displayed as follows:
CLOS, OPEN, UNDEFINED
Configuration settings in program are as follows:
0 = CLOS (Window close status)
1 = OPEN (Window open status)
2 = UNDEFINED
MON SWTH:
Displays monitory switch and is an input
to the Sbus wall module function block.
Status is displayed as follows:
OFF, ON, UNDEFINED
Configuration settings in program are as follows:
0 = OFF
1 = ON
255 = UNDEFINED
MON MODU:
Displays mon modulation and is an
input to the Sbus wall module function block.