CS/CSP/MCS SERIES CURRENT SWITCHES

Honeywell Building Technologies

In the U.S.:

Honeywell

715 Peachtree Street NE

Atlanta, GA 30308

customer.honeywell.com

® U.S. Registered Trademark
©2020 Honeywell International Inc.
31-00432M—01    M.S.  10-20
Printed in United States

Summary of Contents for CS Series

Page 1: ...r to installation Use properly rated voltage sensing instrument to determine no voltage is present MISE EN GARDE Risque de décharge électrique d explosion et d arc électrique Respectez TOUTES les exigences de la norme NFPA 70E concernant les pratiques de travail sécuritaires et les équipements de protection individuelle États Unis ainsi que les autres codes locaux applicables lors de l installatio...

Page 2: ... exceed 30VAC DC Tighten ter minals to 3 5 in lb For CS MCS solid core sensors 1 Drill a single 3 32 pilot hole for mounting the sen sor ensure no drill shavings are present in enclo sure 2 Insert INSULATED CONDUCTOR ONLY 600VAC MAX to be monitored through the iris of the sensor 3 Reconnect the conductor and torque appropriately 4 Wire the output of the sensor to a control panel digi tal input loo...

Page 3: ...hrown away in regular trash Instead it should be recycled according to local municipality CSP NO F CS NO F OPERATION The CSP NO F 200A output changes state whenever current above 0 35A is present THE CS NO F 50A output changes state above 0 25A This provides go no status on loads that are not subject to mechanical failures Typical on off status applications include Lighting circuits Heater element...

Page 4: ...insi que les autres codes locaux applicables lors de l installation de ce produit Lisez attentivement tous les avertissements 1 Adjust knob on sensor to maximum FLA Fully clockwise 2 With motor operating normally adjust knob SLOWLY counter clockwise until Hi LED is lit Fig 1 Normal Operation 1 Set knob to motor FLA Fig 2 Small Lightly Loaded Motor Operation 1 Set knob proportionally below FLA 2 Be...

Page 5: ...t switch will provide a true status output as shown in the chart above CSP NO AECM SETUP ALTERNATE Follow all safety precautions outlined in this manual Follow all requirements in NFPA 70E for safe work practices and for Personal Protective Equipment USA and other applicable local codes when installing this product Read all warnings carefully Respectez toutes les précautions de sécurité décrites d...

Page 6: ...Frequency 60Hz 0Hz VFD Broken Belt VFD Normal Operation Trip Area 40Hz Cal Trip Area 50Hz Cal Trip Point 40Hz Trip Point 50Hz Table 2 Specification by Product Product Number Trip Point Core Type Max Current CS NO F 50A Fixed 0 25A SOLID 50A CSP NO F 200A Fixed 0 35A SPLIT 200A MCS NO A 50A Adjustable 0 75 50FLA SOLID 50A CS NO A 50A Adjustable 0 75 50FLA SOLID 50A CSP NO A 100A Adjustable 0 50 100...

Page 7: ...F 200A 0 75 CS NO F 50A 0 52 ADJUSTABLE CURRENT SWITCHES Turn on Amperage CSP NO AVFD 150A 1A 30Hz min 1 5A 20Hz min 2 5A 10Hz min Output Type NO solid state FET Temperature Rating 15 60 C Insulation Class 600V RMS For use on insulated conductors only Use minimum 75 C insulated conductor Sensor Power Induced Frequency Range 50 60Hz CSP NO AVFD 150A 10 120Hz proof of flow loss alarm at 40Hz Dimensi...