CS/CSP/MCS SERIES CURRENT SWITCHES

3

31-00432M—01

TECH TIPS

On low current loads, wrap sensor 
multiple times to increase sensi-
tivity

CAUTION

Do not exceed sensor 
maximum current. The 
current detected by the 
sensor will increase 1X with 
each wrap.

MISE EN GARDE

Ne dépassez pas le courant maximal du capteur. 
Le courant détecté par le capteur augmentera 
1 fois à chaque tour.

To monitor loads greater than the current sensor maxi-
mum rating

Use a properly rated 5A CT as 
shown below

Pour surveiller les charges 
supérieures à la valeur 
maximale du capteur de courant

Utilisez un CT 5 A avec la tension 
nominale appropriée comme 
indiqué ci-dessous.

CAUTION

5A CTs can present hazardous voltages. Install 
CTs in accordance with manufacturers 
instructions. Terminate the CT secondary wiring 
before energizing primary conductor.

MISE EN GARDE

Les tensions des CT 5 A peuvent présenter des 
dangers. Installez les CT en suivant les 
instructions du fabricant. Terminez le câblage 
secondaire du CT avant d’alimenter le 
conducteur principal.

RECYCLING

Product should not be thrown away in regular trash. 
Instead, it should be recycled according to local 
municipality. 

CSP-NO-F / CS-NO-F OPERATION

The CSP-NO-F-200A output changes state whenever 
current above 0.35A is present; THE CS-NO-F-50A output 
changes state above 0.25A. This provides “go/no” status 
on loads that are not subject to mechanical failures.

Typical on/off status applications include:

• Lighting  circuits
• Heater elements
• Direct drive fans (e.g. exhaust fans)
• Process motors

CSP-NO-A / MCS-NO-A 
UNPOWERED CALIBRATION

A

djust knob on sensor to motor full load amperage 

(FLA) as indicated on motor nameplate or overload 
protection device.

200-500

AMPS

500:5A CT

2-5

AMPS

Table 1. Troubleshooting

Symptom

Causes

Remedy

Sensor output 
does not 
change state

Amperage is below 
sensor minimum 
threshold

Loop monitored 
conductor multiple 
turns through 
sensor. See Tech Tips   

Incorrect control 
wiring

Ensure control loop 
voltage is present 

Testing with ohm 
meter yields 
incorrect results

Solid state output 
may show approx. 1 
ohm or less.

Adjustable CT and 
AECM: Adjustment 
incorrect

See Adjustable 
Conventional 
Calibration or AECM 
setup procedure

AVFD: Minimum 
frequency too low.

Drive must ramp to 
40Hz min. for sensor 
to alarm.

Monitored Load 

Sensor 

Minimum

Current 0.35A

Sensor
Output 

                

Energized

OFF

RUN

Summary of Contents for CS Series

Page 1: ...r to installation Use properly rated voltage sensing instrument to determine no voltage is present MISE EN GARDE Risque de décharge électrique d explosion et d arc électrique Respectez TOUTES les exigences de la norme NFPA 70E concernant les pratiques de travail sécuritaires et les équipements de protection individuelle États Unis ainsi que les autres codes locaux applicables lors de l installatio...

Page 2: ... exceed 30VAC DC Tighten ter minals to 3 5 in lb For CS MCS solid core sensors 1 Drill a single 3 32 pilot hole for mounting the sen sor ensure no drill shavings are present in enclo sure 2 Insert INSULATED CONDUCTOR ONLY 600VAC MAX to be monitored through the iris of the sensor 3 Reconnect the conductor and torque appropriately 4 Wire the output of the sensor to a control panel digi tal input loo...

Page 3: ...hrown away in regular trash Instead it should be recycled according to local municipality CSP NO F CS NO F OPERATION The CSP NO F 200A output changes state whenever current above 0 35A is present THE CS NO F 50A output changes state above 0 25A This provides go no status on loads that are not subject to mechanical failures Typical on off status applications include Lighting circuits Heater element...

Page 4: ...insi que les autres codes locaux applicables lors de l installation de ce produit Lisez attentivement tous les avertissements 1 Adjust knob on sensor to maximum FLA Fully clockwise 2 With motor operating normally adjust knob SLOWLY counter clockwise until Hi LED is lit Fig 1 Normal Operation 1 Set knob to motor FLA Fig 2 Small Lightly Loaded Motor Operation 1 Set knob proportionally below FLA 2 Be...

Page 5: ...t switch will provide a true status output as shown in the chart above CSP NO AECM SETUP ALTERNATE Follow all safety precautions outlined in this manual Follow all requirements in NFPA 70E for safe work practices and for Personal Protective Equipment USA and other applicable local codes when installing this product Read all warnings carefully Respectez toutes les précautions de sécurité décrites d...

Page 6: ...Frequency 60Hz 0Hz VFD Broken Belt VFD Normal Operation Trip Area 40Hz Cal Trip Area 50Hz Cal Trip Point 40Hz Trip Point 50Hz Table 2 Specification by Product Product Number Trip Point Core Type Max Current CS NO F 50A Fixed 0 25A SOLID 50A CSP NO F 200A Fixed 0 35A SPLIT 200A MCS NO A 50A Adjustable 0 75 50FLA SOLID 50A CS NO A 50A Adjustable 0 75 50FLA SOLID 50A CSP NO A 100A Adjustable 0 50 100...

Page 7: ...F 200A 0 75 CS NO F 50A 0 52 ADJUSTABLE CURRENT SWITCHES Turn on Amperage CSP NO AVFD 150A 1A 30Hz min 1 5A 20Hz min 2 5A 10Hz min Output Type NO solid state FET Temperature Rating 15 60 C Insulation Class 600V RMS For use on insulated conductors only Use minimum 75 C insulated conductor Sensor Power Induced Frequency Range 50 60Hz CSP NO AVFD 150A 10 120Hz proof of flow loss alarm at 40Hz Dimensi...

Page 8: ...ITCHES Honeywell Building Technologies In the U S Honeywell 715 Peachtree Street NE Atlanta GA 30308 customer honeywell com U S Registered Trademark 2020 Honeywell International Inc 31 00432M 01 M S 10 20 Printed in United States ...

Reviews: