Honeywell’s Adjustable Turn-On ECM Current Switch 
allows you to set/adjust your turn-on threshold 
appropriately for your application. Set the dial so that the 
turn-on amperage is slightly higher than your ECM stand-
by current. This will typically be around 400mA.

On startup, the sensor output will close when monitored 
current exceeds dial setting, and open if monitored 
current is below the dial setting minus the fixed hysterisis 
value of the current switch.

CSP-NO-AECM SETUP 
(RECOMMENDED)

Follow all safety precautions outlined in this manual.

Follow all requirements in NFPA 70E for safe work 
practices and for Personal Protective Equipment (USA) 
and other applicable local codes when installing this 
product.

Read all warnings carefully.

Respectez toutes les précautions de sécurité décrites 
dans ce manuel.

Respectez toutes les exigences de la norme NFPA 70E 
concernant les pratiques de travail sécuritaires et les 
équipements de protection individuelle (États-Unis), ainsi 
que les autres codes locaux applicables lors de 
l’installation de ce produit.

Lisez attentivement tous les avertissements.

1.

With ECM powered on but not running measure the 
ECM current draw with a meter capable of measur-
ing current.

2.

Turn power off to ECM and set dial on current sensor 
to a value slightly higher than what you measured in 
step 1. Example, measurement of 500mA from 
meter, set dial to about 600mA.

3.

Power on ECM and verify OPEN LED is on.

4.

Next, run ECM at minimum speed and verify 
CLOSED LED is on.

5.

Stop ECM but leave powered on and verify OPEN 
LED is on.

6.

Setup is now complete. You may need to repeat steps 
1 through 5 above during initial setup to get correct 
setting. Once adjusted the Honeywell ECM current 
switch will provide a true status output as shown in 
the chart above. 

CSP-NO-AECM SETUP 
(ALTERNATE)

Follow all safety precautions outlined in this manual.

Follow all requirements in NFPA 70E for safe work 
practices and for Personal Protective Equipment (USA) 
and other applicable local codes when installing this 
product.

Read all warnings carefully.

Respectez toutes les précautions de sécurité décrites 
dans ce manuel.

Respectez toutes les exigences de la norme NFPA 70E 
concernant les pratiques de travail sécuritaires et les 
équipements de protection individuelle (États-Unis), ainsi 
que les autres codes locaux applicables lors de 
l’installation de ce produit.

Lisez attentivement tous les avertissements.

1.

Dial is set from the factory to a value of about 
500mA.

2.

Once installed on the ECM conductor with your 
motor STOPPED but powered on, verify the OPEN 
LED is on. If OPEN LED is off adjust dial clockwise 
until OPEN LED is on.

3.

Turn dial counter clockwise until CLOSED LED is on. 
This is the turn-on amperage or approximate value 
of your ECM stand-by current.

4.

Turn dial clockwise until CLOSED LED is off and 
continue clockwise slightly to give a margin of oper-
ation between the on and off states. Leave dial at 
this setting and you’re done with the current sensor 
setup.

CSP-NO-AVFD 
CALIBRATION/TRAINING

No calibration is necessary. 

Sensor will automatically detect belt loss on motors 
operated by variable speed drive after 10 seconds of 
operation above 40Hz. This is because the device leaves 
the factory in the 40Hz training mode.

OPTIONAL MANUAL SETUP: To reset and restart 
calibration/training, press/hold button for 1 second(40Hz 
mode) or 3 seconds (50Hz mode). LED will make 4 blinks 
in 5 seconds which indicates the device is in “Training” 
mode. Operate motor above 40Hz for 10 seconds (40Hz 
mode) or 50Hz for 10 seconds (50Hz mode), recommend 
45Hz and 55Hz respectively.

To activate go/no mode, press/hold button for 5 seconds. 
LED will make 3 fast blinks.

Summary of Contents for CS Series

Page 1: ...r to installation Use properly rated voltage sensing instrument to determine no voltage is present MISE EN GARDE Risque de décharge électrique d explosion et d arc électrique Respectez TOUTES les exigences de la norme NFPA 70E concernant les pratiques de travail sécuritaires et les équipements de protection individuelle États Unis ainsi que les autres codes locaux applicables lors de l installatio...

Page 2: ... exceed 30VAC DC Tighten ter minals to 3 5 in lb For CS MCS solid core sensors 1 Drill a single 3 32 pilot hole for mounting the sen sor ensure no drill shavings are present in enclo sure 2 Insert INSULATED CONDUCTOR ONLY 600VAC MAX to be monitored through the iris of the sensor 3 Reconnect the conductor and torque appropriately 4 Wire the output of the sensor to a control panel digi tal input loo...

Page 3: ...hrown away in regular trash Instead it should be recycled according to local municipality CSP NO F CS NO F OPERATION The CSP NO F 200A output changes state whenever current above 0 35A is present THE CS NO F 50A output changes state above 0 25A This provides go no status on loads that are not subject to mechanical failures Typical on off status applications include Lighting circuits Heater element...

Page 4: ...insi que les autres codes locaux applicables lors de l installation de ce produit Lisez attentivement tous les avertissements 1 Adjust knob on sensor to maximum FLA Fully clockwise 2 With motor operating normally adjust knob SLOWLY counter clockwise until Hi LED is lit Fig 1 Normal Operation 1 Set knob to motor FLA Fig 2 Small Lightly Loaded Motor Operation 1 Set knob proportionally below FLA 2 Be...

Page 5: ...t switch will provide a true status output as shown in the chart above CSP NO AECM SETUP ALTERNATE Follow all safety precautions outlined in this manual Follow all requirements in NFPA 70E for safe work practices and for Personal Protective Equipment USA and other applicable local codes when installing this product Read all warnings carefully Respectez toutes les précautions de sécurité décrites d...

Page 6: ...Frequency 60Hz 0Hz VFD Broken Belt VFD Normal Operation Trip Area 40Hz Cal Trip Area 50Hz Cal Trip Point 40Hz Trip Point 50Hz Table 2 Specification by Product Product Number Trip Point Core Type Max Current CS NO F 50A Fixed 0 25A SOLID 50A CSP NO F 200A Fixed 0 35A SPLIT 200A MCS NO A 50A Adjustable 0 75 50FLA SOLID 50A CS NO A 50A Adjustable 0 75 50FLA SOLID 50A CSP NO A 100A Adjustable 0 50 100...

Page 7: ...F 200A 0 75 CS NO F 50A 0 52 ADJUSTABLE CURRENT SWITCHES Turn on Amperage CSP NO AVFD 150A 1A 30Hz min 1 5A 20Hz min 2 5A 10Hz min Output Type NO solid state FET Temperature Rating 15 60 C Insulation Class 600V RMS For use on insulated conductors only Use minimum 75 C insulated conductor Sensor Power Induced Frequency Range 50 60Hz CSP NO AVFD 150A 10 120Hz proof of flow loss alarm at 40Hz Dimensi...

Page 8: ...ITCHES Honeywell Building Technologies In the U S Honeywell 715 Peachtree Street NE Atlanta GA 30308 customer honeywell com U S Registered Trademark 2020 Honeywell International Inc 31 00432M 01 M S 10 20 Printed in United States ...

Reviews: