Table 2. 230V Series
Frame size
A
B
C
D
E
Model
HCRDAxxxxx1000T
1hp 2hp 3hp 5hp 7.5hp 10hp 15hp 20hp 25hp 30hp 40hp 50hp 60hp 75hp 100hp 125hp
Outpu
t Ra
ti
ng
Normal
“HVAC”
Duty -
Variable
Torque
Rated Output
Capacity (kVA)
2
3
4
6
8.4
12
18
24
30
36
42
58
72
86
110
128
Rated Output
Current (A)
5
7.5
10
15
21
31
46
61
75
90
105
146
180
215
276
322
Applicable
Motor Output
(kW)
0.75 1.5 2.2 3.7
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
Applicable
Motor Output
(HP)
1
2
3
5
7.5
10
15
20
25
30
40
50
60
75
100
125
Overload
tolerance
120% of rated current for 1 minute
Max. output
frequency (Hz)
600.00Hz (55KW~: 400.00Hz)
Carrier
Frequency
(kHz)
2~15kHz (8KHz)
2~10kHz (6kHz)
2~9kHz (4KHz)
Heavy
Duty -
Constant
Torque
Rated Output
Capacity (kVA)
1.8
2
3.2 4.4
6.8
10
13
20
26
30
36
48
58
72
86
102
Rated Output
Current (A)
4.6
5
8
11
17
25
33
49
65
75
90
120
146
180
215
255
Applicable
Motor Output
(kW)
0.4 0.75 1.5 2.2
3.7
5.5
7.5
11
15
18.5
22
30
37
45
55
75
Applicable
Motor Output
(HP)
0.5
1
2
3
5
7.5
10
15
20
25
30
40
50
60
75
100
Overload
tolerance
120% of rated current for 1 minute, 160% of rated current for 3 seconds
Max. output
frequency (Hz)
600.00Hz(55KW~: 400.00Hz)
Carrier
Frequency
(kHz)
2~15kHz (8KHz)
2~10kHz (6kHz)`
2~9kHz(4KHz)
Input Rating
Input Current (A) Normal
Duty
6.4 9.6
15
22
25
35
50
65
83
100
116
146
180
215
276
322
Input Current (A) Heavy
Duty
3.9 6.4
12
16
20
28
36
52
72
83
99
124
143
171
206
245
Rated Voltage/Frequency
3-phase AC 200V~240V (-15% ~ +10%), 50/60Hz
Operating Voltage Range
170~265Vac
Frequency Tolerance
47~63Hz
Cooling method
Natural
Cooling
Fan Cooling
Braking Chopper
Frame A,B,C: Built-in
Frame D and above: Optional
DC choke
Frame A, B,C: Optional
Frame D and above: 3% built-in
EMI Filter
Optional