** To comply with UL standard: Per UL 508, paragraph 45.8.4, part a: 

The rated current of the breaker shall be 2~4 times of the maximum rated input current of AC motor drive.

NOTE: Fuses with specification smaller than the data in the following table are allowed

Table 6. Fuse and Non-fuse Circuit Breaker

Model 230V

Input Current I(A)

Line Fuse

Recommended non-

fuse breaker (A) **

Normal Duty

Heavy Duty

I (A)

Bussmann P/N

HCRDA0010A1000T

6.4

3.9

15

JJN-15

15

HCRDA0020A1000T

9.6

6.4

20

JJN-20

20

HCRDA0030A1000T

15

12

30

JJN-30

30

HCRDA0050A1000T

22

16

40

JJN-40

40

HCRDA0075A1000T

25

20

50

JJN-50

50

HCRDA0100B1000T

35

28

60

JJN-60

60

HCRDA0150B1000T

50

36

100

JJN-100

100

HCRDA0200B1000T

65

52

125

JJN-125

125

HCRDA0250C1000T

83

72

150

JJN-150

150

HCRDA0300C1000T

100

83

200

JJN-200

200

HCRDA0400C1000T

116

99

225

JJN-225

225

HCRDA0500D1000T

146

124

250

JJN-250

250

HCRDA0600D1000T

180

143

300

JJN-300

300

HCRDA0750E1000T

215

171

400

JJN-400

400

HCRDA1000E1000T

276

206

450

JJN-450

450

HCRDA1250E1000T

322

245

600

JJN-600

600

Model 460V

Input current (A)

Line Fuse

Recommended non-

fuse breaker (A) **

Normal Duty

Heavy Duty

I (A)

Bussmann P/N

HCRDC0010A1000T

4.3

3.5

10

JJS-10

5

HCRDC0020A1000T

5.4

4.3

10

JJS-10

10

HCRDC0030A1000T

7.4

5.9

15

JJS-15

15

HCRDC0050A1000T

11

8.7

20

JJS-20

20

HCRDC0075A1000T

18

15.5

30

JJS-30

30

HCRDC0100A1000T

20

17

40

JJS-40

40

HCRDC0150B1000T

25

20

50

JJS-50

50

HCRDC0200B1000T

33

26

60

JJS-60

60

HCRDC0250B1000T

39

35

75

JJS-75

75

HCRDC0300C1000T

47

40

100

JJS-100

100

HCRDC0400C1000T

58

47

125

JJS-125

125

HCRDC0500C1000T

76

63

150

JJS-150

150

HCRDC0600D1000T

91

74

175

JJS-175

175

HCRDC0750D1000T

110

101

250

JJS-250

250

HCRDC1000D1000T

144

114

300

JJS-300

300

HCRDC1250D1000T

180

157

300

JJS-300

300

Summary of Contents for CORE Drive

Page 1: ...on Storage and Transportation 3 Specification Tables 4 Minimum Mounting Clearances 7 Specifications for Wiring Terminals 9 Frame A 11 Frame B 12 Frame C 12 Frame D 13 Frame E 14 KeypadBasics 15 Start up Wizard Guide 17 Menu Structure 18 Warning Codes and Descriptions 19 Fault Codes and Descriptions 20 Wiring Diagrams 23 H W Q 0 5012613200 2011 11 ...

Page 2: ...ge level is reached DO NOT install the VFD in a place subjected to high temperature direct sunlight and inflammable materials See specification data in this manual for details WARNING Never apply power to the output terminals U T1 V T2 W T3 of the VFD Please stop operation immediately when a fault occurs during operation of the VFD and motor and refer to fault code information to reset the drive D...

Page 3: ...is installed at altitude 0 1000m follow normal operation restriction If it is installed at altitude 1000 3000m decrease 2 of rated current or lower 0 5o C of temperature for every 100m increase in altitude Maximum altitude for Corner Grounded is 2000m Package Drop Storage ISTA procedure 1A according to weight IEC60068 2 31 Transportation Vibration 1 0mm peak to peak value range from 2Hz to 13 2 Hz...

Page 4: ...itch S curve accel deccel 3 wire sequence Auto Tuning rotational stationary Frequency upper lower limit settings Cooling fan on off switch Slip compensation Torque compensation JOG frequency MODBus communication RS 485 RJ45 max 115 2 kbps DC injection braking at start stop Smart Stall PID control with sleep function Energy saving control Fan Control 230V series Model HCRDA0200B1000T 20HP and above...

Page 5: ... 4 6 8 10 13 20 26 30 36 48 58 72 86 102 Rated Output Current A 4 6 5 8 11 17 25 33 49 65 75 90 120 146 180 215 255 Applicable Motor Output kW 0 4 0 75 1 5 2 2 3 7 5 5 7 5 11 15 18 5 22 30 37 45 55 75 Applicable Motor Output HP 0 5 1 2 3 5 7 5 10 15 20 25 30 40 50 60 75 100 Overload tolerance 120 of rated current for 1 minute 160 of rated current for 3 seconds Max output frequency Hz 600 00Hz 55KW...

Page 6: ...8 58 73 88 120 Rated Output Current A 2 8 3 4 6 10 5 12 18 24 32 38 45 60 73 91 110 150 Applicable Motor Output kW 0 4 0 75 1 5 2 2 4 5 5 7 5 11 15 18 5 22 30 37 45 55 75 Applicable Motor Output HP 0 5 1 2 3 5 7 5 10 15 20 25 30 40 50 60 75 100 Overload tolerance 120 of rated current for 1 minute 160 of rated current for 3 seconds Max output frequency Hz 600 00Hz 90KW 400 00Hz Carrier Frequency kH...

Page 7: ...VERTER INVERTER INVERTER INVERTER INVERTER INVERTER INVERTER INVERTER INVERTER INVERTER INVERTER INVERTER INVERTER INVERTER INVERTER INVERTER INVERTER NOTE THE MOUNTING CLEARANCES SHOWN IN THE LEFT FIGURE ARE NOT FOR INSTALLING THE DRIVE IN A CONFINED SPACE SUCH AS CABINET OR ELECTRIC BOX WHEN INSTALLING IN A CONFINED SPACE BESIDES THESE SAME MINIMUM MOUNTING CLEARANCES IT NEEDS TO HAVE THE VENTIL...

Page 8: ... 157 727 HCRDA0250C1000T C 166 12 178 282 20 302 622 218 840 HCRDA0300C1000T C 166 12 178 282 20 302 777 197 974 HCRDA0400C1000T C 146 12 158 248 20 268 878 222 1100 HCRDA0500D1000T D 179 30 209 304 51 355 1271 311 1582 HCRDA0600D1000T D 179 30 209 304 51 355 1550 355 1885 HCRDA0750E1000T E 228 73 301 387 124 511 1762 489 2251 HCRDA1000E1000T E 228 73 301 387 124 511 2020 574 2594 HCRDA1250E1000T ...

Page 9: ...Terminal D 2 1 Torque 90 Kg cm 78 2 lb in 8 83Nm 10 Use 600V 90oC wired for UL installation for HCRDA0400C1000T install in ambient temperature exceeds 40oC HCRDA0300C1000T 1 0 AWG 53 5mm2 HCRDA0400C1000T 1 0 AWG 53 5mm2 HCRDC0300C1000T 4 AWG 21 2mm2 HCRDC0400C1000T 4 AWG 21 2mm2 HCRDC0500C1000T 2 AWG 33 6mm2 HCRDA0500D1000T 4 0 AWG 107mm2 4 0 AWG 107mm2 M8 200kg cm 173 lb in 19 62Nm Use the specif...

Page 10: ...0300C1000T 100 83 200 JJN 200 200 HCRDA0400C1000T 116 99 225 JJN 225 225 HCRDA0500D1000T 146 124 250 JJN 250 250 HCRDA0600D1000T 180 143 300 JJN 300 300 HCRDA0750E1000T 215 171 400 JJN 400 400 HCRDA1000E1000T 276 206 450 JJN 450 450 HCRDA1250E1000T 322 245 600 JJN 600 600 Model 460V Input current A Line Fuse Recommended non fuse breaker A Normal Duty Heavy Duty I A Bussmann P N HCRDC0010A1000T 4 3...

Page 11: ...DC0050A1000T 5 2 8 HCRDA0075A1000T HCRDC0075A1000T 7 5 2 8 HCRDC0100A1000T 10 2 8 HCRDA0100B1000T 10 4 6 B 190 7 48 320 12 60 190 7 48 173 6 81 303 11 93 77 9 3 07 8 5 0 33 22 2 0 87 34 1 34 28 1 10 HCRDA0150B1000T HCRDC0150B1000T 15 4 6 HCRDA0200B1000T HCRDC0200B1000T 20 5 6 HCRDC0250B1000T 25 HCRDA0250C1000T 25 10 5 C 250 9 84 400 15 75 210 8 27 231 9 09 381 15 00 92 9 3 66 8 5 0 33 22 2 0 87 34...

Page 12: ...E C Fig 4 Frame C Units in mm inches See also Table 7 M31496 SEE DETAIL A SEE DETAIL B DETAIL A MOUNTING HOLE DETAIL B MOUNTING HOLE S1 S1 D D1 W W1 H1 H 1 1 3 3 1 2 CORE CORE M31497 SEE DETAIL A SEE DETAIL B DETAIL A MOUNTING HOLE DETAIL B MOUNTING HOLE S1 S1 W1 W D1 D H1 H 1 3 2 1 1 1 3 CORE CORE ...

Page 13: ... 22 550 21 65 107 2 4 22 11 0 0 43 76 2 3 00 34 0 1 34 22 0 0 87 HCRDA0600D1000T HCRDC0600D1000T 60 35 5 HCRDC0750D1000T 75 35 5 HCRDC1000D1000T 100 40 5 HCRDC1250D1000T 125 40 5 HCRDA0750E1000T 75 45 7 E 370 14 57 715 8 28 18 300 11 81 335 13 19 589 23 19 143 0 5 63 13 0 0 51 22 0 0 87 34 0 1 34 92 0 3 62 HCRDA1000E1000T 100 46 2 HCRDA1250E1000T 125 54 7 SEE DETAIL A SEE DETAIL B W1 W D1 D H1 H D...

Page 14: ... DRIVE 62 0410 04 14 FRAME E Fig 6 Frame E Units in mm inches See also Table 8 SEE DETAIL A SEE DETAIL B DETAIL B MOUNTING HOLE DETAIL A MOUNTING HOLE S3 D2 S1 S2 D1 D W1 W H1 H2 H3 H M31499 1 1 2 2 2 2 3 3 CORE CORE ...

Page 15: ...P when this button is pressed The RESET key can be used to reset the drive after the fault occurs For those faults that can t be reset by the RESET key see the fault records after pressing MENU key for details This key controls the operational direction of the motor NOT activated out of the box Press ENTER and go to the next submenu If at the parameter level press enter to modify and press enter t...

Page 16: ...ol from a remote speed and start command source Table 9 Descriptions of Keypad Functions F1 F2 F3 F4 HAND AUTO Table 10 Descriptions of LED Functions LED Descriptions Steady ON operation indicator for the VFD including DC brake zero speed standby restart after fault and speed search Blinking VFD is decelerating to stop Steady OFF VFD is not running Steady ON VFD is stopped Blinking VFD is in the s...

Page 17: ...tor s rated RPM based upon Motor Name Plate data Press F4 to accept factory defaults Use arrow keys to adjust ONLY if needed PRESS ENTER to save changes 9 ACCEL TIME The time required to accelerate from the motor s current speed reference to a new speed reference Acceleration time is factory set for typical Fan and Pump needs Use arrow keys to adjust Press ENTER to save changes F4 to advance witho...

Page 18: ...cated here STARTUP WIZARD parameters are also listed in this menu Keypad Lock The keypad is locked when ENTER is pressed When any key is pressed the following screen will appear Language Use the arrow key to move up and down to change the language selection Display Setup Display Setup Menu allows the user to adjust the backlight time and contract UP and DOWN arrows are used to adjust settings ENTE...

Page 19: ...viation Warn Over speed deviation warning PHL Phase Loss Warn Phase loss ot1 Over Torque 1 Over torque 1 ot2 Over Torque 2 Over torque 2 oH3 Motor Over Heat Motor over heating oSL Over Slip Warn Over slip tUn Auto Tuning Auto tuning processing OPHL Output PHL Warn Output phase loss warning Ecid ExCom ID failed Duplicate MAC ID error ECLv ExCom pwr loss Low voltage of communication card Ectt ExCom ...

Page 20: ...g Check for possible motor stall 3 AC motor drive output power is too small Replace the AC motor drive with the next higher power model ocS oc at stop Hardware failure in current detection Return to the factory GFF Ground fault Ground fault When one of the output terminal s is grounded short circuit current is more than 50 of AC motor drive rated current the AC motor drive power module may be dama...

Page 21: ...that the ventilation holes are not obstructed 1 to15HP 90 oC 3 Remove any foreign objects from the heatsinks and check for possible dirty heat sink fins 20 to 100HP 100 oC 4 Check the fan and clean it 5 Provide enough spacing for adequate ventilation oH2 CAP over heat Heatsink overheating 1 Ensure that the ambient temperature falls within the specified temperature range Capacitance temperature exc...

Page 22: ...lt has been cleared bb Base block External Base Block 1 When the external input terminal B B is active the AC motor drive output will be turned off 2 Deactivate the external input terminal B B to operate the AC motor drive again Pcod Password error Password is locked Keypad will be locked Cycle power OFF and then ON to re enter the correct password See Pr 00 07 and 00 08 ccod SW Code Error Softwar...

Page 23: ... WHILE USING INTERNAL POWER TO RUN SINK MODE FACTORY SETTING POWER REMOVAL SAFETY FUNCTION FOR EMERGENCY STOP DIGITAL SIGNAL COMMON TERMINAL 10V 20mA 0 10V 0 20mA 0 20mA 0 10V ANALOG SIGNAL COMMON TERMINAL 3 2 1 5KΩ MAIN CIRCUIT POWER TERMINALS CONTROL TERMINALS SHIELDED LEADS CABLES 10V AVI1 ACI AVI2 ACM AFM1 ACM AFM2 ANALOG MULTI FUNCTION OUTPUT TERMINAL 0 10V 0 20mA ANALOG SIGNAL COMMON TERMINA...

Page 24: ...PUT FREQUENCY TERMINALS 250VAC 5A MULTI FUNCTION OUTPUT FREQUENCY TERMINALS 250VAC 5A 30VDC 5A DCM SCM S1 DIGITAL SIGNAL COMMON TERMINAL WHILE USING INTERNAL POWER TO RUN SINK MODE FACTORY SETTING POWER REMOVAL SAFETY FUNCTION FOR EMERGENCY STOP DIGITAL SIGNAL COMMON TERMINAL 10V 20mA 0 10V 0 20mA 0 20mA 0 10V ANALOG SIGNAL COMMON TERMINAL 3 2 1 5KΩ MAIN CIRCUIT POWER TERMINALS CONTROL TERMINALS S...

Reviews: