R7999C CONTROLINKS™ CONTROLLER
13
32-00081EF—01
44
Feedback potentiometer Interface circuit fault—FGR.
Verify correct wiring of potentiometer.
a
45
Feedback potentiometer wiper resistance problem—Air.
Check for loose potentiometer wiring.
a,c
46
Feedback potentiometer wiper resistance problem—Fuel 1.
Check for loose potentiometer wiring.
a,c
47
Feedback potentiometer wiper resistance problem—Fuel 2.
Check for loose potentiometer wiring.
a,c
48
Feedback potentiometer wiper resistance problem—FGR.
Check for loose potentiometer wiring.
a,c
49
Feedback potentiometer total resistance problem—Air.
Check for loose potentiometer wiring.
a,c
51
Feedback potentiometer total resistance problem—Fuel 1.
Check for loose potentiometer wiring.
a,c
52
Feedback potentiometer total resistance problem—Fuel 2.
Check for loose potentiometer wiring.
a,c
53
Feedback potentiometer total resistance problem—FGR.
Check for loose potentiometer wiring.
a,c
54
Internal memory function problem—Air.
Repeat actuator commissioning ID on-line process.
55
Internal memory function problem—Fuel 1.
Repeat actuator commissioning ID on-line process.
56
Internal memory function problem—Fuel 2.
Repeat actuator commissioning ID on-line process.
57
Internal memory function problem—FGR.
Repeat actuator commissioning ID on-line process.
58
Stuck Reset button.
Turn off remote reset switch; check operation of controller reset button. Check
the manual pot for correct wiring (terminal 36 - 38).
61
Actuator(s) not reaching lightoff point.
Check for actuator wiring problems or stuck valves or dampers. Place controller in
standby and use actuator manual keys to verify actuator travel. Were the actuators
commissioned properly?
65
Internal memory fault.
Reset control.
a
66
Internal Initialization Error. A2D error, 4-20ma (terminal 39-40) is being
overdriven.
Reset control.
a
Remove 39-40 input and reset R7999C, if fault clears,
R7999C is ok, and correct 4-20 source.
67
Fuel actuator off curve (selected fuel type). Actuator did not go to its
commanded position.
Check for stuck fuel actuator and/or proper shielding on actuator interface. Try
changing degree of accuracy to 0.5 degree.
68
FGR actuator off curve.
Check for stuck FGR actuator and/or proper shielding on actuator interface.
69
Air actuator off curve. Actuator did not go to its commanded position.
Check for stuck air actuator and/or proper shielding on actuator interface. Try
changing degree of accuracy to 0.5 degree.
71
Verifies that the Air actuator accepted the offline, online, move counter-clock-
wise and move clock-wise commands. Furthermore, all potentiometer tests
must be successfully passed to bring an actuator online.
Check wiring of actuator, verify correct ID is being used. Watch actuator LED
to verify that the actuator is being brought online.
A fast flash in the actuator equals offline status, while a one-second flash
equals online status.
72
Verifies that the Fuel 1 actuator accepted the offline, online, move counter-
clock-wise and move clock-wise commands. Furthermore, all potentiometer
tests must be successfully passed to bring an actuator online.
Check wiring of actuator, verify correct ID is being used. Watch actuator LED
to verify that the actuator is being brought online.
A fast flash in the actuator equals offline status, while a one-second flash
equals online status.
73
Verifies that the Fuel 2 actuator accepted the offline, online, move counter-
clock-wise and move clock-wise commands. Furthermore, all potentiometer
tests must be successfully passed to bring an actuator online.
Check wiring of actuator, verify correct ID is being used. Watch actuator LED
to verify that the actuator is being brought online.
A fast flash in the actuator equals offline status, while a one-second flash
equals online status.
74
Verifies that the FGR actuator accepted the offline, online, move counter-clock-
wise and move clock-wise commands. Furthermore, all potentiometer tests
must be successfully passed to bring an actuator online.
Check wiring of actuator, verify correct ID is being used. Watch actuator LED
to verify that the actuator is being brought online.
A fast flash in the actuator equals offline status, while a one-second flash
equals online status.
75
Internal memory fault (Microprocessor test failed).
Reset control.
a
76
Internal checksum error (Microprocessor test failed).
Reset control.
a
82
Actuator secondary fault (actuator secondary fault - check footnote a).
Check actuator wiring. See Channel LED for actuator.
83
Air actuator nonresponsive.
Check actuator wiring and stuck damper/valve.
c
Were the actuators
commissioned properly–are they set off their mechanical stops?
84
Fuel 1 actuator nonresponsive.
Check actuator wiring and stuck damper/valve.
c
Were the actuators
commissioned properly–are they set off their mechanical stops?
85
Fuel 2 actuator nonresponsive.
Check actuator wiring and stuck damper/valve.
c
Were the actuators
commissioned properly–are they set off their mechanical stops?
86
FGR actuator nonresponsive.
Check actuator wiring and stuck damper/valve.
c
Were the actuators
commissioned properly–are they set off their mechanical stops?
87
Internal math error (Microprocessor test failed).
Reset control.
a
Table 7. Fault Listings and Descriptions. (Continued)
Fault/
Blink
Code
Description
Corrective Action