Notes: 

-  For the fixing of the device basis only use installation material that is suitable for the on-site installation and that ensures a safe and durable fixing. 
-  When fixing the device basis, attention has to be paid to the marking for the connection of the pipe system (see fig. A).  
 
3.  Open the necessary pre-punched cable entries in the device basis (max. 8 x M20 and 6 x M25). If necessary, use a screwdriver.  
4.  Carefully equip the cable entry/entries with M20 or M25 cable entries (2 x M25, 1 x M20 included in the delivery) by inserting them into the corre-

sponding cable entries. 

5.  Insert the required connection cable(s) (max. 2,5 mm

2

) into the prepared cable entries and wire the devices according to the circuit connections 

described at the following page.  

Note: 

If the detection unit of Honeywell COMPACT is to be installed at a later stage, the mounted device basis can be protected against excessive con-
tamination by using the bottom of the supplied card box.

 

In order to use the bottom of the card box as a dust protection, please proceed as follows: 
1.  Carefully separate the cover along the pre-punched perforation from the bottom of the carton.  
2.  Open the required openings for the connections of the pipe system, the air return and the cable entries by separating the openings carefully along 

the pre-punched perforation from the bottom of the card box. 

3.  Put the bottom of the card box as protection over the mounted device basis. 

 

 
 

Summary of Contents for compact asd

Page 1: ...be blocked the distance between the air outlet and adjacent objects e g wall is to be at least 10 cm The device basis can be mounted with the aspiration pointing upwards or downwards The connection for the air sampling pipe is marked with a V see fig A If the aspiration comes from downwards make sure no impurities enter the air outlet which then points upwards Procedure 1 First clearly mark the fi...

Page 2: ...connection cable s max 2 5 mm2 into the prepared cable entries and wire the devices according to the circuit connections described at the following page Note If the detection unit of Honeywell COMPACT is to be installed at a later stage the mounted device basis can be protected against excessive con tamination by using the bottom of the supplied card box In order to use the bottom of the card box ...

Page 3: ...pply voltage 2b 0 V Supply voltage 3b Alarm element line fire alarm 4b Alarm element line fire alarm 5b Termination element line fault 6b Termination element line fault 7b Data bus A 8b Data bus B connection for accessories 24V 0V 1a 2a 3a 4a 5a 6a 7a 8a 1b 2b 3b 4b 5b 6b 7b 8b Data bus 24V 0V Data B Data A L1 L1 L1 L1 Reset Data B 24V 24V 0V RA RE RE RA RE Alarm element Termination element Elemen...

Page 4: ...of conformity has been issued by notified product certification body ID no 0786 VdS The CE designation according to DIN EN 54 20 has been carried out 0786 WAGNER Group GmbH Schleswigstrasse 1 5 30853 Langenhagen 07 Nr 0786 CPD 20322 EN 54 20 2006 Air sampling smoke detector for fire detection and fire alarm systems in buildings 0 1 light obscuration m Class A B and C 0 5 light obscuration m Class ...

Reviews: