ComfortPoint
TM
Open System
EN1B-0498GE51 R0512
6
Relay Outputs
Number:
6
Characteristics:
relay outputs (default)
Features:
voltage: 24 Vac/dc, P>50 mW;
max. total current: 3 A (ac or dc);
current per relay: 500 mA
normally-open contacts: P > 50 mW,
voltage: 24 V (ac or dc);
one yellow LED per output
Protection:
protected against voltages of max. 30
VDC and 24 VAC+20 and short-circuit
Table 4. Permissible loads of CPO-IO830A
load
min. load
Per module
(total for all
relay con-
tacts)
24 Vdc/Vac
max. 3 A resistive or induc-
tive, cos
φ
≥ 0.6,
no capacitive load
–
Per normally
open contact
24 Vdc/Vac
min. 0.05 A resistive or
inductive, cos
φ
≥ 0.6,
max. 0.5 A resistive or
inductive, cos
φ
≥ 0.6,
no capacitive load
>50 mW
Status LED Behavior
During engineering, each of the 18 status LEDs can be
configured individually (yellow/OFF [default]).
Given a logical state of "ON," the status LED will be lit
(yellow).
Panel Bus Topologies
I
2
3
O
N
Honeywell
ComfortPoint Open
TM
!
Rx1
Rx3
Rx2 Tx2
Tx1
Tx3
B7
B1 B2 B3 B4 B5 B6
7
1
2
3
4
5
6
8
9
10
11 12
B8 B9 B10 B11 B12 AI5
AI1 AI2 AI3 AI4
41
G1 G2
42
17
13 14 15 16
18 19
20
AI6 AI7 AI8
AO5
25
21 22 23 24
26
27 28
35
29 30
31 32 33 34
36
37
38 39
40
AO1 AO2 AO3 AO4 NO1 NO2 NO3 NO4 NO5 NO6
AO6 AO7 AO8
IN1 IN2 IN3 IN4 IN5 IN6
1
1
2
2
3
3
4
4
5
5
6
6
7
25 26 27 28 35 36 37 38 39 40
1
21 22 23 24 29 30 31 32 33 34
2
8 9
3
10
4
11
5
12
6 13 14 15 16
41 42
7 8 9
10 11 12 17 18 19 20
DI
Binary Inputs
Analog Inputs
Analog Outputs
24V Relays
GND
S2
DO
Honeywell
!
Install. Instr.
EN1B-0375GE51
XF830A
12 BI / 8 AI / 8 AO / 6 RO
24V, 15VA, T50
0706AX0001-XFU830A
Made in Germany
0532
8
2
1 0
F E D
C
B
9
8
7
6
5
4
3
A
40
External
24V for relay 1...5
24V
J1
J2
J3
J4
J5
71
75
76
77
78
COM a
COM b
24V~
24V~0
COM a
COM b
24V~
24V~0
72
73
74
A1 A2 A3 A4 A5 A6 A7 A8 A9
B1 B2 B3 B4 B5 B6 B7 B8 B9
A
A1 A2 A3 A4 A5 A6 A7 A8 A9
B1 B2 B3 B4 B5 B6 B7 B8 B9
B
A1 A2 A3 A4 A5 A6 A7 A8 A9
B1 B2 B3 B4 B5 B6 B7 B8 B9
C
A1 B1 A2 B2 A3 B3 A4 B4 G1
G2
A5 B5 A6 B6 A7 B7 A8 B8
D
PR
ES
S
PR
ES
S
1:ABCDFERTAQWESDERT1
2:ABCDFERTAQWESDERT2
3:ABCDFERTAQWESDERT3
4:ABCDFERTAQWESDERT4
5:ABCDFERTAQWESDERT5
6:ABCDFERTAQWESDERT6
7:ABCDFERTAQWESDERT7
8:ABCDFERTAQWESDERT8
1:ABCDFERTAQWESDERT1
2:ABCDFERTAQWESDERT2
3:ABCDFERTAQWESDERT3
4:ABCDFERTAQWESDERT4
5:ABCDFERTAQWESDERT5
6:ABCDFERTAQWESDERT6
7:ABCDFERTAQWESDERT7
8:ABCDFERTAQWESDERT8
1
2
3
4
5
6
7
8
Honeywell
!
21
9
GND
GND
AI/AO
V
AUX
10
11
12
13
14
15
16
17
18
25
26
22
1
2
3
4
5
6
7
8
GND
BI
13
14
15
16
17
18
19
20
21
22
23
24
25
26
1
2
3
4
5
6
7
8
9
10
11
12
1 2 3 4 5 6 7 8 9 10 11 12
Honeywell
!
1
2
5
3
6
CPO-IO830A
4
Fig. 7. CPO-PC-6A and CPO-IO830A
Legend
1
CPO-PC-6A Plant Controller
2 XS816 Bridge Connector
3 Cable connection
4 Pluggable Panel Bus I/O Modules (shown with Swivel
Label Holders)
5 Stopper (from 3
rd
-party supplier)
6 Auxiliary terminal packages
The CPO-PC-6A features a total of four RS485 interfaces
suitable for configuration,
inter alia,
as Panel Buses and to
which Panel Bus I/O modules (including the CPO-IO830A)
can then be connected. A max. 15 Panel Bus I/O modules per
Panel Bus are allowed. Max. distance between Panel Bus I/O
modules and CPO-PC-6A: 40 m. No bus termination is
necessary, and the Panel Bus is polarity-insensitive. See also
ComfortPoint Open Plant Controller – Installation and
Commissioning Instructions (EN1B-0462GE51) for more
information.
Updating Software and Firmware
The firmware of the CPO-PC-6A includes the firmware for the
Panel Bus I/O modules. Thus, whenever the firmware of the
CPO-PC-6A is updated, the firmware of the Panel Bus I/O
modules is automatically updated, too.
Power Supply
When selecting the appropriate transformer, take into account
the number of individual modules, accessories, and field
devices in determining the total power consumption.