Error! Use the Home tab to apply Überschrift 1 to the text that you want to appear here.
ComfortPoint
TM
Open System
EN1B-0498GE51 R0512
2
Safety Information
General Safety Information
►
When performing any work (installation, mounting, start-
up), all instructions given by the manufacturer and in
particular the safety instructions provided in these
Installation and Commissioning Instructions are to be
observed.
►
The ComfortPoint
TM
Open Mixed Panel Bus I/O Module
CPO-IO830A and related devices (Field Bus Adapters,
etc.) may be installed and mounted only by authorized and
trained personnel.
►
Rules regarding electrostatic discharge should be followed.
►
If the ComfortPoint
TM
Open Mixed Panel Bus I/O Module
CPO-IO830A is modified in any way, except by the
manufacturer, all warranties concerning operation and
safety are invalidated.
►
FCC-CERTIFIED: This device complies with Part 15 of the
FCC Rules. Operation is subject to the following two
conditions: (1) This device may not cause harmful inter-
ference, and (2) this device must accept any interference
received, including interference that may cause undesired
operation.
►
Make sure that the local standards and regulations are
observed at all times. Examples of such regulations are
VDE 0800 and VDE 0100 or EN 60204-1 for earth
grounding.
►
Use only accessory equipment which comes from or has
been approved by Honeywell.
►
It is recommended that devices be kept at room tem-
perature for at least 24 hours before applying power. This
is to allow any condensation resulting from low
shipping/storage temperatures to evaporate.
►
The ComfortPoint
TM
Open Mixed Panel Bus I/O Module
CPO-IO830A must be installed in a manner (e.g., in a
lockable cabinet) ensuring that uncertified persons have no
access to the terminals.
►
Investigated according to United States Standard UL-
60730.
►
Investigated according to Canadian National Standard(s)
C22.2, No. 205-M1983 (CNL-listed).
►
Do not open the CPO-PC-6A, as it contains no user-
serviceable parts inside!
►
CE declarations according to LVD Directive 2006/95/EC
and EMC Directive 2004/108/EC.
►
Product standards are EN 60730-1 and EN 60730-2-9.
Safety Information as per EN60730
Purpose
The ComfortPoint
TM
Open Mixed Panel Bus I/O Module CPO-
IO830A is intended for home (residential, commercial, and
light-industrial) environments.
The CPO-IO830A is an independently mounted electronic
control unit with fixed wiring.
The CPO-IO830A is suitable for mounting in fuse boxes con-
forming with standard DIN43880, and having a slot height of
max. 45 mm.
It is suitable for panel rail mounting on 35 mm standard panel
rail (both horizontal and vertical rail mounting possible).
The CPO-IO830A is used for the purpose of building HVAC
control and is suitable for use only in non-safety controls for
installation on or in appliances.
Table 1. Safety information as per EN 60730
Shock protection
24 V-powered controls: Class III
mains-powered controls: Class II
Pollution degree
Pollution Degree 2,
suitable for use in home and industrial
environments.
Installation
Class 3
Overvoltage
category
24 V-powered controls: Category I
mains-powered controls: Category II
Rated impulse
voltage
330 Vac for Category I
2500 Vac for Category II
Automatic action
Type 1.C
(micro-interruption for the relay
outputs)
Software class
Class A
Enclosure
IP20 according to EN-60529
Ball-pressure test
temperature
75 °C for all housing and plastic parts
125 °C in the case of devices applied
with voltage-carrying parts and
connectors
Electromagnetic
interference
Tested at 230 Vac, with the modules
in normal condition;
suitable for use in home, commercial,
and light industrial environments.
System
transformer
Europe: safety isolating transformers
according to IEC61558-2-6
U.S.A. and Canada: NEC Class-2
transformers